Emerson Rosemount 8732 manual

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172

Go to page of

A good user manual

The rules should oblige the seller to give the purchaser an operating instrucion of Emerson Rosemount 8732, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.

What is an instruction?

The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of Emerson Rosemount 8732 one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.

Unfortunately, only a few customers devote their time to read an instruction of Emerson Rosemount 8732. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.

What should a perfect user manual contain?

First and foremost, an user manual of Emerson Rosemount 8732 should contain:
- informations concerning technical data of Emerson Rosemount 8732
- name of the manufacturer and a year of construction of the Emerson Rosemount 8732 item
- rules of operation, control and maintenance of the Emerson Rosemount 8732 item
- safety signs and mark certificates which confirm compatibility with appropriate standards

Why don't we read the manuals?

Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of Emerson Rosemount 8732 alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of Emerson Rosemount 8732, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the Emerson service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of Emerson Rosemount 8732.

Why one should read the manuals?

It is mostly in the manuals where we will find the details concerning construction and possibility of the Emerson Rosemount 8732 item, and its use of respective accessory, as well as information concerning all the functions and facilities.

After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.

Table of contents for the manual

  • Page 1

    www .rosemount.com Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 Integral Mount or Remote Mount Magnetic Flowmeter System with Profibus-P A[...]

  • Page 2

    [...]

  • Page 3

    Reference Manual 00809-0100-4 665, Rev AA August 2010 Rosemount 8732 www .rosemount.com Integral Mount or Remote Mount Magnetic Flo wmeter System with Pr ofib us-P A NOTICE Read this manual before working with the prod uct. For personal and system safety , and for optimum product performance, make sure you thoroughly understand the contents before [...]

  • Page 4

    [...]

  • Page 5

    Reference Manual 00809-0100- 4655, Rev AA August 2010 TOC -1 Rosemount 8732 SECTION 1 Introduction System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2 Service Support . . . . . . . . . . . . . . . . . [...]

  • Page 6

    Reference Manual 00809-0100- 4655, Rev AA August 2010 Rosemount 8732 TOC -2 APPENDIX B Approval Information Product Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1 Sensor Approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-5 APPENDIX C Diagnostics Diagnostic Ava[...]

  • Page 7

    Reference Manual 00809-0100-4 665, Rev AA August 2010 Rosemount 8732 www .rosemount.com Section 1 Introduction System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1- 1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-2 Service Support . . . . . . . . . . . . . . . . . . . . . .[...]

  • Page 8

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 1-2 SAFETY MESSAGES Procedures and instr uctions in this man ual may require special p recautions to ensure the safety of th e personnel pe rforming the opera tions. Refer to the safety messages listed at the beginni ng of each section before performing any operations. SERVICE SUP[...]

  • Page 9

    Reference Manual 00809-0100-4 665, Rev AA August 2010 Rosemount 8732 www .rosemount.com Section 2 Inst allation Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1 T ransmitter Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p age 2-2 Pre-Inst allation . . . . . . . . . . . . . . . . . . . . [...]

  • Page 10

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 2-2 TR A N S M I T T E R SYMBOLS Caution symbol — check product document ation for details Protective conductor (grou nding) terminal PRE-INSTALLATION Before installing the Rosemount 8732 Ma gnetic Flowmeter T ransmitter , there are several pre-inst allation steps that should be[...]

  • Page 11

    Reference Manual 00809-0100- 4665, Rev AA August 2010 2-3 Rosemount 8732 Figure 2-1. Rosemount 8732 Dimensional Drawing ENVIRONMENT AL CONSIDERATIONS T o ensure maximum transmitter life, avoid temperature extremes and vibration. T ypical proble m ar ea s inc lude: • high-vibration lines with in tegra lly moun ted transmitters • warm-climate ins[...]

  • Page 12

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 2-4 Hardware Jumpers/Switches The 8732 Profibus P A electronics board is equipped with two user-sele ctable hardware switches. These switches do not have any fu nc tion a lity an d sh ou ld be left in the default po sitions as listed below: Changing the switch position will have n[...]

  • Page 13

    Reference Manual 00809-0100- 4665, Rev AA August 2010 2-5 Rosemount 8732 Figure 2-2. Cable Prep aration Detail Electrical Considerations Before making any electrical connections to the Rosemount 8732, consider the following st andards and be sur e to have the proper powe r supply , conduit, and other accessories. When prep ar ing all wire conne cti[...]

  • Page 14

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 2-6 Figure 2-3 shows the supply curren t for each corresponding supply voltage. For combinations n ot shown, you can calculate the maximum dist ance given the supply current, the volt age of the source, and the minimum st art-up voltage of the transmitter , 12 V DC, using the foll[...]

  • Page 15

    Reference Manual 00809-0100- 4665, Rev AA August 2010 2-7 Rosemount 8732 Figure 2-4. AC T ransmitter Power Connections Connect Profibus P A Wiri ng The Profibus P A signal provides the ou tput information from the transmitter . T ransmitter Communication Input The Profibus P A communication requires a minimum of 9 V dc and a maximum of 32 V dc at t[...]

  • Page 16

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 2-8 NOTE The number of devices on a Profibus segment is limited by the power supply voltage, th e resistance of the cable, an d the amount of current drawn by each device. T ransmitter W iring Connection T o connect the 8732 to the Profibus P A segment, complete the following step[...]

  • Page 17

    Reference Manual 00809-0100- 4665, Rev AA August 2010 2-9 Rosemount 8732 Figure 2-6. Ros em o un t 87 32 T ransmitt er Field Wirin g (T runk) (Spur) Te r m i n a t o r s (The power supply , filter, first termina tor , and configuration tool are typically located in the control room.) Devices 1 through 1 1 * * Intrinsically saf e inst allations may [...]

  • Page 18

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 2-10 SENSOR CONNECTIONS This section covers the st eps required to physically install the transmitter including wiring and calibration. Rosemount Sensors T o connect the transmitter to a non-Rosemount sensor , refer to the appropriate wiring dia gram in “Universal Sensor Wiring [...]

  • Page 19

    Reference Manual 00809-0100- 4665, Rev AA August 2010 2-1 1 Rosemount 8732 Rosemount recommends usin g the combination signal and coil drive for N5 , E5 approved sensors for optimum pe rformance. Remote transmitter inst allations require equal lengths of signal and coil drive cables. Integrally mounted transmitters are factory wired and do not requ[...]

  • Page 20

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 2-12 Figure 2-9. Wiring Diagram T ransmitter Te r m i n a l Sensor T erminal Wire Gau ge Wire Color 1 1 14 Clear or Red 2 2 14 Black 14 Shield 17 17 20 Shield 18 18 20 Black 19 19 20 Clear or Red[...]

  • Page 21

    Reference Manual 00809-0100-4 665, Rev AA August 2010 Rosemount 8732 www .rosemount.com Section 3 Configuration Quick St art-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1 Assigning Device T a g and Node Address . . . . . . . . . . . . page 3-2 Basic Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [...]

  • Page 22

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 3-2 The calibration number is more than a correction factor , or K- factor , for the sensor . The first five digi ts repres en t the low freq ue nc y ga in. T he nint h through thirteenth di git s represe nt the high frequ ency gain. Both nu mbers are normalized from an ideal numb[...]

  • Page 23

    Reference Manual 00809-0100- 4665, Rev AA August 2010 3-3 Rosemount 8732 AI Block Para meter Attribute Definitions The following t able describes the p arameters that are available in the analog input function block. Each line item in the table defines the element and specifies the requirement s for each element. Absolute Index Parameter Descriptio[...]

  • Page 24

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 3-4 33 FSAFE_ TYPE Defines the reaction of device , if a fault is detected. The calculated ACTUAL MODE remains in AUTO. 0: value FSAFE_V ALUE is used as OUT S tatus - UNCERT AIN_Substitute V alue, 1: use last stored valid OUT value S tatus - UNCERT AIN_LastUsableV alue if there is[...]

  • Page 25

    Reference Manual 00809-0100- 4665, Rev AA August 2010 3-5 Rosemount 8732 T ot alizer Block T otalizer 1 is Slot 2 T otalizer 2 is Slot 3 T otalizer 3 is Slot 4 The 8732E transmitter has three independent totaliz er blocks. These blocks can be used to totalize indepen dently over dif ferent time ranges or using dif ferent units o f measure. T ot ali[...]

  • Page 26

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 3-6 Profibus P A specific Parameters 26 TOT A L The Function Block parameter TOT AL contains the integrated quantity of the rate parameter provided by CHANNEL and the associa ted status. 27 UNIT_TOT Unit of the totalized quantity . 28 CHANNEL Reference to the active Transducer Blo[...]

  • Page 27

    Reference Manual 00809-0100- 4665, Rev AA August 2010 3-7 Rosemount 8732 T R ANSDUCER BLOCK PV The process variables (PV) measure flow in seve ral ways that reflect your needs and the configurat ion of your flowmeter . When commissioning a flowmeter , re view each process variable, its function an d output, and take corrective action if necessary b[...]

  • Page 28

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 3-8 Options for Flow Rate Unit s Line Size The line size (sensor size) must be set to match th e actual sensor connected to the transmitter . The size must be specified in inches accordin g to the available sizes listed below . If a valu e is entered from a control system that doe[...]

  • Page 29

    Reference Manual 00809-0100- 4665, Rev AA August 2010 3-9 Rosemount 8732 Upper Range V alue This parameter se t the flow rate in engineerin g units that corres ponds to 100% flow . This p arameter is configured in the T ransducer Block. The Upper Range V alue can be set for bo th forward or reverse flow rates. Flow in th e forward direction is repr[...]

  • Page 30

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 3-10 NOTE Be sure the calibration number reflects a calibration to a Rosemount reference transmitter . If the calibration number was generated by a mea ns other than a certified Rosemount flow lab, accur acy of the system may be compromised. If your sensor is not a Rosemount senso[...]

  • Page 31

    Reference Manual 00809-0100-4 665, Rev AA August 2010 Rosemount 8732 www .rosemount.com Section 4 Operation Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1 Local Operator Interface . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1 Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . [...]

  • Page 32

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 4-2 Dat a Entry The LOI keypad does not have nu merical keys. Numerical data is en tered by the following proced ure. 1. Access the appropriate function . 2. Use the RIGHT ARROW key t o move to th e value to change. 3. Use the UP and DOWN ARROWS to change the h ighlighted value. F[...]

  • Page 33

    Reference Manual 00809-0100- 4665, Rev AA August 2010 4-3 Rosemount 8732 Class 2 Masters There are a number of available PROFIB US co nfiguration tools. Th ese Class 2 Masters are m anufacturer-independent to ols for the operation, configuration, maintenance, and diagnosis of intelligent field devices. Device descriptor based Class 2 Masters allo w[...]

  • Page 34

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 4-4 Basic Diagnostics The basic diagnostics menu con tain s all of th e stan dard diagno stics and test s that are available in the 8732E tr ansmitter . Empty Pipe Limit s Empty Pipe allows you to view the current value and configu re the diagnostic parameters. F or more detail on[...]

  • Page 35

    Reference Manual 00809-0100- 4665, Rev AA August 2010 4-5 Rosemount 8732 Run 8714i Run the meter verifi cation test to check the transmitter , sensor , or entire installation. Full Meter V erific ation Run the internal meter verification to check the entire inst allation, sensor and transmitter at the same time. T rans mitter Only Run the internal [...]

  • Page 36

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 4-6 Sensor Calibration Result Displays the result of the sensor ca libration verification test as p ass or fail. For more detai ls on this parameter see App end ix C: Diagnostics. Coil Circuit Result Displays the result of the coil circuit test as pass or fail. For more det ails o[...]

  • Page 37

    Reference Manual 00809-0100- 4665, Rev AA August 2010 4-7 Rosemount 8732 Set Pass/Fai l Criteria Set the maximum allowable d eviation percentage test criteria for the 8714 i Meter V erification test. There are three te sts that this criteria can be set for: • Full Pipe; No Flow (Best test condition) – Default is 2% • Full Pipe; Flowing – De[...]

  • Page 38

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 4-8 Licensing If a diagnostic suite was not ordered in itially , advanced diagnostics can be licensed in the field. Access the licens ing information from this men u. For more detai ls on licensing, see Appendix C: Diagnostics. License S tatus Determine if a diagnostics suite has [...]

  • Page 39

    Reference Manual 00809-0100- 4665, Rev AA August 2010 4-9 Rosemount 8732 8714i Result s Review the result s of the 8714i Meter V e rification tests. For more det ails on these results and what they mean, see Appendix C: Diagnostics. T est Condition Displays the conditions that the 8714i Meter V erification test was performed under . For mor e detai[...]

  • Page 40

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 4-10 Tr i m s T rims are used to calibrate the transmitter , re-z ero the transmitter , and calibrate the transmitter with another manufacturer ’s sensor . Proceed with caution whenever per forming a trim function. Electronics T rim Electronics trim is the function by whic h the[...]

  • Page 41

    Reference Manual 00809-0100- 4665, Rev AA August 2010 4-1 1 Rosemount 8732 Universal T rim The Universal T rim function enables the Rosemount 87 32E to calibrate sensors that were not calibrated at th e Rosemount factory . The function is activated as one step in a procedure known as in-proce ss calibration. If your Rosemount se nsor has a 16-d igi[...]

  • Page 42

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 4-12 ADVANCED CONFIGURATION In addition to the basic configuration op tions and the diagnostic information and controls, the 8 732 has many advanced functions that can also be configured as req u ire d by th e ap plic ation. DET AILED SETUP The det ailed setup function provides ac[...]

  • Page 43

    Reference Manual 00809-0100- 4665, Rev AA August 2010 4-13 Rosemount 8732 Signal Processing The 8732E contains several advanced fu nctions that can be used to stabilize erratic output s caused by process noise. The signal processing menu contains this functionality . Below is sample PDM screen shot of Signal Processing. Operating Mode (Operation) T[...]

  • Page 44

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 4-14 Time Limit 0 to 256 Seconds The time limit param eter forces the output and running average values to the new value of an actual flow rate change that is out side the percent limit boundaries. It thereby limit s response time to flow ch anges to the time limit value rather th[...]

  • Page 45

    Reference Manual 00809-0100- 4665, Rev AA August 2010 4-15 Rosemount 8732 DSP Sof tware Rev This function displays the s oftware re vision number of the tr ansmitter . Construction Mate rials Construction materials cont ain information about the sensor that is connected to the transmitter . This in formation is configured into the transmi tter for [...]

  • Page 46

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 4-16 Electrode Material Electrode Material enables you to se lect the electrode material for your magnetic transmitter system. This varia ble only needs to be changed if you have replaced electrodes o r if you have replaced yo ur sensor . Options for this value are: • 316L SST ?[...]

  • Page 47

    Reference Manual 00809-0100-4 665, Rev AA August 2010 Rosemount 8732 www .rosemount.com Section 5 Sensor Inst allation Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-1 Sensor Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-3 Sensor Mounting . . . . . . . . . . . . . . . . .[...]

  • Page 48

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 5-2 Explosions could resu lt in death or serious injury: Installation of this transmitter in an explosiv e environment must be in accordance with the appropriate local, national, and international standards, codes, and prac tices. Please review the approvals section of the 8732 re[...]

  • Page 49

    Reference Manual 00809-0100- 4665, Rev AA August 2010 5-3 Rosemount 8732 SENSOR HANDLING Handle all part s carefully to prevent damage. Whenever possible, transport the system to the installa tion site in the original shipping cont aine rs. PTFE-lined sensors are shipped with end cover s that protect it from both mechanical damage and normal unrest[...]

  • Page 50

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 5-4 SENSOR MOUNTING Physical mounting of a sensor is similar to installing a typical section of pipe. Conventional tools, equip ment, and accessories (bolt s, gaskets, and grounding hard ware) are required. Up stream/Downstream Piping T o ensure specification accuracy ov er widely[...]

  • Page 51

    Reference Manual 00809-0100- 4665, Rev AA August 2010 5-5 Rosemount 8732 Figure 5-4. Incline or Decline Orientation Horizontal installation should be restri cted to low piping sections that are normally full. Orient the electr ode plan e to within 45 degrees of horizont al in horizontal inst allations. A deviation of more than 45 degrees of horizon[...]

  • Page 52

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 5-6 The electrodes in the Rosemount 871 1 are properly oriented wh en the top of the sensor is either vertica l or horizo ntal, as shown in Figure 5-6. Av oid any mounting orient ation that positions the to p of the sensor at 45 degre es from the vertical or hori zo ntal positio n[...]

  • Page 53

    Reference Manual 00809-0100- 4665, Rev AA August 2010 5-7 Rosemount 8732 INST ALLATION (FLANGED SENSOR) The following section shou ld be used as a guide in t he installation of the flange-type Rosemount 870 5 and Rose mount 8707 High-Signal Sensors. Refer to page 5-10 for inst allation of the wafer-t y pe R os em o unt 87 1 1 Sensor . Gasket s The [...]

  • Page 54

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 5-8 NOTE Do not bolt one side at a time. T ighten each sid e si multaneously . Example: 1. Snug left 2. Snug righ t 3. T ighten left 4. T ighten right Do not snug and tighten the up stream side and then snug and tighten the downstream side. Failu re to alternate between the upstr [...]

  • Page 55

    Reference Manual 00809-0100- 4665, Rev AA August 2010 5-9 Rosemount 8732 Figure 5-10. Flange Bolt T orquing Sequence T able 5-2. Flange Bolt T orque and Bolt Load S pecificatio ns for Rosemount 8705 PTFE/ETFE liner Size Code PN10 PN 16 PN 25 PN 40 Line Size (Newton-meter) (N ewton) (Newton-m eter) (Newton) (New ton-meter) (Newton ) (Newton-meter) ([...]

  • Page 56

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 5-10 INSTALLATION (W AFER SENSOR) The following section shou ld be used as a guide in t he installation of the Rosemount 871 1 Sensor . Refer to page 5-7 for installation of the flange-type Rosemount 8705 and 8707 High-Signal sensor . Gasket s The sensor requires a gasket at each [...]

  • Page 57

    Reference Manual 00809-0100- 4665, Rev AA August 2010 5-1 1 Rosemount 8732 3. Place the sensor between the flanges. Make sure that the ce ntering rings are properly placed in the stu ds. The studs should be aligned with the markings on the rings tha t correspond to the flange you are using. 4. Insert the remaining studs, washers, and nu ts. 5. Tigh[...]

  • Page 58

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 5-12 INST ALLATION (SANIT ARY SENSOR) Gasket s The sensor requires a gasket at each of its connections to a djacent devices or piping. The gasket material selected must be compatible with the process fluid and operating co nditions. Gaskets are supplied with a ll Rosemount 8721 Sa[...]

  • Page 59

    Reference Manual 00809-0100- 4665, Rev AA August 2010 5-13 Rosemount 8732 NOTE Consult factory for installations requirin g cathodic protection or situations where ther e are high cu rrents or high pot ential in the pro cess. The sensor case should alwa ys be earth groun ded in accordance with national and local electrica l codes. Failure t o do so[...]

  • Page 60

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 5-14 Figure 5-14. Grounding with Grounding Rings or Lining Protectors Figure 5-15. Grounding with Grounding Rings or Lining Protectors Grounding Ring s or Lining Prote ctors Grounding Rings or Lining Prote ctors[...]

  • Page 61

    Reference Manual 00809-0100- 4665, Rev AA August 2010 5-15 Rosemount 8732 Figure 5-16. Grounding with Grounding Electrodes[...]

  • Page 62

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 5-16 PR OCESS LEAK PR OTECTION (OPTIONAL) The Rosemount 8705 and 8707 High- Signal Sensor housing is fabricated from carbon steel to perform two sepa rate functions. First, it provides shielding for the sensor magnetics so that external disturbances cannot interfere with th e ma g[...]

  • Page 63

    Reference Manual 00809-0100- 4665, Rev AA August 2010 5-17 Rosemount 8732 Relief V alves The first optional configuration, identif ied by the W1 in the model number option code, uses a completely welded coil housing. This configuration doe s not provide sep arate electrode comp artments with externa l el ectrod e a ccess. This optional housing conf[...]

  • Page 64

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 5-18 Figure 5-19. Housing Configuration — Sealed Electrode Compartmen t (O ption Code W3) If necessary , capture any process fluid lea kage, connect the appropriate piping to the d rainports, and p rovide for proper disp osal (see Figure 5-19). Fused Glass Seal Sealed Electrode [...]

  • Page 65

    Reference Manual 00809-0100-4 665, Rev AA August 2010 Rosemount 8732 www .rosemount.com Section 6 Maintenance and T roubleshooting Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6-1 Inst allation Check and Guide . . . . . . . . . . . . . . . . . . . . . . page 6-2 Diagnostic Messages . . . . . . . . . . . . . [...]

  • Page 66

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 6-2 INST ALLATION CHECK AND GUIDE Use this guide to check new installatio ns of Rosemount magnetic flowmeter systems that appear to malfunction. Before Y ou Begin Tr a n s m i t t e r Apply power to your system before ma king the following transmitt er checks. 1. V erify that the [...]

  • Page 67

    Reference Manual 00809-0100- 4665, Rev AA August 2010 6-3 Rosemount 8732 DIAGNOSTIC MESSAGES Problems in the magnetic flo wmeter system are u sually indicated by incorr ect output readings from the syste m, error me ssages, or failed te st s. Consider all sources in identifyin g a pr ob lem in you r sys te m. T able 6-1. Rosemount 8732 Basic Diagno[...]

  • Page 68

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 6-4 T able 6-2. Rosemount 8732 Advanced Diagnos tic Mess ages (Suite 1 - Option C ode D01) T able 6-3. Rosemount 8732 Advanced Diagnos tic Mess ages (Suite 2 - Option C ode D02) “DSP Hardwar e not compatible with software” Incompatible SW DSP Software Revision is not equal to [...]

  • Page 69

    Reference Manual 00809-0100- 4665, Rev AA August 2010 6-5 Rosemount 8732 TR A N S M I T T E R T ROUBL ESHOOTING T able 6-4. Advanced T roubleshooting–Rosemount 8732 Symptom Potential Cause Corrective Action Does not appear to be within rated accuracy T ransmitter , control system, or other receiving device not configured properly Check all config[...]

  • Page 70

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 6-6 Meter output is unstable Medium to low conductivity flu ids (10– 25 microsiemens/cm) combined with cable vibration or 60 Hz interference Eliminate cable vibration: • Integral mount • Move cable to lower vibration run • Tie down cable mechanically • Trim electrode and[...]

  • Page 71

    Reference Manual 00809-0100- 4665, Rev AA August 2010 6-7 Rosemount 8732 QUICK T ROUBL ESHOOTING Step 1: W iring Errors Th e most common magmeter pro blem is wiring between the se nsor and the transmitte r in remote moun t inst allations. The signal wire and coil drive wire must be twis ted shielded ca ble: 20 AWG twisted shield ed cable for the el[...]

  • Page 72

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 6-8 T o test the sensor , a multimeter capabl e of mea suring conductance in nanosiemens is pref erred. Nanosiemen s is the reciprocal of resistance. or T able 6-5. Sensor T est T est Sensor Location Required Equipment Measuring at Connections Expected Value Potential Cause Correc[...]

  • Page 73

    Reference Manual 00809-0100- 4665, Rev AA August 2010 6-9 Rosemount 8732 Figure 6-1. Sensor Cir cuit Diagram Step 4: Uninst alled Sensor T est s An uninstalled sensor can also be used for sensor troubleshooting. T o interpret the result s, the hazardous locatio n certification for the sensor must be known. Applicable code s for the Rosemount 8705 a[...]

  • Page 74

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 6-10 Figure 6-2. 45° Elec trode Plane T o insure accuracy of re sistance readings, zer o out multimeter by shorting and touching the leads together . T able 6-6. Uninstalled Rosemount 87 05 / 8707 Flanged Sensor T ests Measuring at Connections Hazardous Location C ertifications N[...]

  • Page 75

    Reference Manual 00809-0100-4 665, Rev AA August 2010 Rosemount 8732 www .rosemount.com Appendix A Reference Dat a Functional Specificat ions . . . . . . . . . . . . . . . . . . . . . . . . . page A-1 E-Series Advanced Diagnostics Capabilities . . . . . . . . . . page A-4 Output Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [...]

  • Page 76

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 A-2 Figure A-1. AC Current Requirements Figure A-2. Ap parent Power DC Supply Current Requirements Units powe red by 12 -4 2 V DC po wer sup ply may dr aw up to 1 amp of current steady state. Figure A-3. DC Current Requirements DC Load Limit ations (Analog Output) Maximum loop res[...]

  • Page 77

    Reference Manual 00809-0100- 4665, Rev AA August 2010 A-3 Rosemount 8732 Figure A-4. 8732E DC Load Limitations Power Consumption 10 watts maximum Switch-on current AC: Maximum 26 A (< 5 ms) at 250 V AC DC: Maximum 30 A (< 5 ms) at 42 V DC Ambient T emperature Limit s Operating –58 to 165 °F (–50 to 74 °C) without local op erator interfa[...]

  • Page 78

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 A-4 Low Flow Cutoff Adjust able between 0.01 and 38 .37 ft./s (0 .003 and 1 1.7 m/s). Below selected value, output is driven to th e zero flow rate signal level. Overrange Capability Signal output will remain linear until 1 1 0% of upper range va lue or 44 ft./s (13 m/s). The sign[...]

  • Page 79

    Reference Manual 00809-0100- 4665, Rev AA August 2010 A-5 Rosemount 8732 Profibus P A Function Blocks Physical Block - Slot 0 The Physical Bloc k contains physica l transmitter information, including available me mory , manufacturer identific ation, device type, software tag, and unique identification. T ransduce r Block - Slot 5 The transducer bl [...]

  • Page 80

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 A-6 PERFORMANCE SPECIFICATIONS (System specifica tions are given using the frequency output and with the u nit at reference conditions.) Accuracy Includes the combined effects of linear ity , hysteresis, repeatability , and calibration uncertainty . Rosemount E Series with 8705 /8[...]

  • Page 81

    Reference Manual 00809-0100- 4665, Rev AA August 2010 A-7 Rosemount 8732 Optional high accuracy is ±0.25% of rate from 3 to 39 f t./s (1 to 12 m/s). Rosemount E-Series with Legac y 8705/8707 Sensors: S tandard system accuracy is ±0.5% of ra te from 1 to 39 f t./s (0.3 to 12 m/s); between 0.04 and 1.0 ft./s (0.0 1 and 0.3 m/s), the system has an a[...]

  • Page 82

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 A-8 PHYSICAL SPECIFICATIONS Materials of Construction Housing Low copper aluminum, T ype 4X and IEC 60529 IP66 Paint Polyurethane Cover Gasket Rubber Electrical Connectio ns Tw o 1 / 2 –14 NPT connections provided on the transmitter housing (o ptional third connection available)[...]

  • Page 83

    Reference Manual 00809-0100- 4665, Rev AA August 2010 A-9 Rosemount 8732 ORDERING INFORMATION T able A-1. Rosemount 8732E/ Profibu s P A Orderi ng Information Model Product Description 8732E 8732E Magnetic Flowmeter Transmitter • T ransmitter Style St anda rd Standa rd S S tandard • ★ T ransmitter Mount St anda rd Standa rd T Integral Mount ?[...]

  • Page 84

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 A-10 IECEx Standa rd Standard EF IECEx flameproof Ex de IIB T6 Gb and IECEx Dust Approval; Ex de [ia IIC Ga] IIB T6 Gb w ith IS Output • ★ NF Ex tD A20 IP66 T100 °C or Ex tD A20 IP66 T100 °C [Ex ia Ga] IIC • ★ Expanded E7 IECEx flameproof Ex de IIC T6 Gb and IECEx D ust [...]

  • Page 85

    Reference Manual 00809-0100- 4665, Rev AA August 2010 A-1 1 Rosemount 8732 YG German • YH Finnish • YI Italian • YJ Japanese • YL Polish • YM Mandarin • YN Norwegian • YP Portuguese • YS S panish • YR Russian • YW Swedish • T ypical Model Number: 8732E S T 1 A 1 N0 DA1 DA2 M4 (1) Adapters are used for this conduit entr y type [...]

  • Page 86

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 A-12[...]

  • Page 87

    Reference Manual 00809-0100-4 665, Rev AA August 2010 Rosemount 8732 www .rosemount.com Appendix B Approval Information Product Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . page B-1 Approved Manufacturing Locations . . . . . . . . . . . . . . . . . page B-1 European Directive Information . . . . . . . . . . . . . . . . . .[...]

  • Page 88

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 B-2 For Rosemount 8732E transmitters: IEC 60079-0: 2004 IEC 60079-0: 2007 IEC 60079-1: 2007 IEC 60079-7: 2006 IEC 60079-1 1: 2006 IEC 60079-15: 200 5 IEC 61241-0: 2004 IEC 61241-1: 2004 NOTE For intrinsically safe (IS) outputs on th e 8732E output option code B, F , or P must be s[...]

  • Page 89

    Reference Manual 00809-0100- 4665, Rev AA August 2010 B-3 Rosemount 8732 European Certifications E1 A TEX Flamepro of Certificate No.: KEMA 07A TEX0073 X II 2G Ex de IIC or Ex de [ia] IIC T6 (-50°C  Ta  +60 °C) with LOI (-20°C  Ta  +60 °C) V max = 250 V AC or 42 V DC 0575 ED A TEX Flameproof Certificate No.: KEMA 07A TEX0073 X II 2G[...]

  • Page 90

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 B-4 International Certifications IECEx E7 IECEx Flameproof Certificate No.: KEM 07.0038 X Ex de IIC T6 Gb or Ex de [ia Ga] II C T6 Gb (-50 °C  Ta  +60 °C) with LOI (-20°C  Ta  +60 °C) V max = 250 V AC or 42 V DC EF IECEx Flameproof Certificate No.: KEM 07.0038 X Ex[...]

  • Page 91

    Reference Manual 00809-0100- 4665, Rev AA August 2010 B-5 Rosemount 8732 InMetro - Brazil E2 InMetro Flameproof Cert ificate No.: NCC 5030/08 BR-Ex de IIC or BR-Ex de [ia] IIC T6 (-50 °C  Ta  +60 °C) with LOI (-20°C  Ta  +60 °C) V max = 250 V AC or 42 V DC EB InMetro Flameproof Cert ificate No.: NCC 5030/08 BR-Ex de IIB or BR-Ex de [...]

  • Page 92

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 B-6 Figure B-1. A T EX Installation Drawings ECO PENDING Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary[...]

  • Page 93

    Reference Manual 00809-0100- 4665, Rev AA August 2010 B-7 Rosemount 8732 Figure B-2. A T EX Installation Drawings (Cont.) ECO PENDING Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary[...]

  • Page 94

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 B-8 Figure B-3. A T EX Installation Drawings (Cont.) ECO PENDING Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary[...]

  • Page 95

    Reference Manual 00809-0100- 4665, Rev AA August 2010 B-9 Rosemount 8732 Figure B-4. A T EX Installation Drawings (Cont.) ECO PENDING Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary[...]

  • Page 96

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 B-10 Figure B-5. A T EX Installation Drawings (Cont.) ECO PENDING Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary[...]

  • Page 97

    Reference Manual 00809-0100- 4665, Rev AA August 2010 B-1 1 Rosemount 8732 Figure B-6. A T EX Installation Drawings (Cont.) ECO PENDING Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary[...]

  • Page 98

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 B-12 Figure B-7. Installation Drawings with FM Certified I.S. Output Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary[...]

  • Page 99

    Reference Manual 00809-0100- 4665, Rev AA August 2010 B-13 Rosemount 8732 Figure B-8. Installation Drawings with FM Certified I.S. Output (Cont.) Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary[...]

  • Page 100

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 B-14 Figure B-9. Installation Drawings with FM Certified I.S. Output (Cont.) Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary[...]

  • Page 101

    Reference Manual 00809-0100- 4665, Rev AA August 2010 B-15 Rosemount 8732 Figure B-10. Installation Drawings with FM Certified I.S. Output (Cont.) Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary[...]

  • Page 102

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 B-16 Figure B-1 1. Ins tallation Drawings with CSA Certified I.S. Output Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary[...]

  • Page 103

    Reference Manual 00809-0100- 4665, Rev AA August 2010 B-17 Rosemount 8732 Figure B-12. Installation Drawings with CSA Certified I.S. Output (Cont.) Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary[...]

  • Page 104

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 B-18 Figure B-13. Installation Drawings with CSA Certified I.S. Output (Cont.) Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary[...]

  • Page 105

    Reference Manual 00809-0100- 4665, Rev AA August 2010 B-19 Rosemount 8732 Figure B-14. Installation Drawings with CSA Certified I.S. Output (Cont.) Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary[...]

  • Page 106

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 B-20 Figure B-15. Installation Drawings Hazard ous (Classified Location) Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary[...]

  • Page 107

    Reference Manual 00809-0100- 4665, Rev AA August 2010 B-21 Rosemount 8732 Figure B-16. Installation Drawings Factory Mutual Hazardous Location Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary[...]

  • Page 108

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 B-22[...]

  • Page 109

    Reference Manual 00809-0100-4 665, Rev AA August 2010 Rosemount 8732 www .rosemount.com Appendix C Diagnostics Diagnostic A vailabil ity . . . . . . . . . . . . . . . . . . . . . . . . . . . . page C-1 Licensing and Enabling . . . . . . . . . . . . . . . . . . . . . . . . . . . p age C-2 T unable Empty Pipe Detection . . . . . . . . . . . . . . . .[...]

  • Page 110

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 C-2 LICENSING AND ENABLING All non-basic diagnostics must be licensed by order ing option code D01, D02, or both. In the event that a diagno stic optio n is not ordered, advanced diagnostics can be license d in the field through the use of a license key . T o obtain a license key [...]

  • Page 111

    Reference Manual 00809-0100- 4665, Rev AA August 2010 C-3 Rosemount 8732 Empty Pipe T rigger Lev el Limits: 3 to 2000 This value con figures the th reshold limit th at the Empty Pip e V a lue must exceed before the Empty Pipe diagn ostic alert a ctivates. Th e default sett ing from the factory is 100. Empty Pipe T rigge r Count Limits: 5 to 50 This[...]

  • Page 112

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 C-4 T r oubleshooting Empty Pipe The following actions can be t aken if Empty Pipe detection is unexpe cted. 1. V erify the sensor is full. 2. V erify that the sensor has no t been installed with a measurement electrode at the top of the pipe . 3. Decrease the sensitivity by setti[...]

  • Page 113

    Reference Manual 00809-0100- 4665, Rev AA August 2010 C-5 Rosemount 8732 T r oubleshooting Ground/Wiring Fault The transmitter detected high levels o f 50/60 Hz noise caused by improper wiring or poor process grounding . 1. V erify that the transmitter is earth grou nded. 2. Connect ground rings, groundin g electrode, lining protector , or groundin[...]

  • Page 114

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 C-6 High Process Noise Parameters The High Process Noise diagno stic has tw o read -only p arameters. It does no t have any configurable par ameters. This diagnostic requires that flow be present in the pipe and the velocity be > 1 ft/s. 5 Hz Signal to Noise Ratio Reads the cur[...]

  • Page 115

    Reference Manual 00809-0100- 4665, Rev AA August 2010 C-7 Rosemount 8732 NOTE In applications where very high levels of noise are a concern, it is recommended that a d ual- calibr ated Rosemo unt High -Signal 8 707 sensor be used. These sensors can be calibrate d to run at lower coil drive current supplied by the st andard Rosemount transmitters, b[...]

  • Page 116

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 C-8 8714I METER V ERIFICATION The 8714i Meter V erificatio n diagnostic provides a means of verifying the flowmeter is within calibration without re moving the sensor from the process. This is a manually initiated diagnostic test that provides a r eview of the transmitter and sens[...]

  • Page 117

    Reference Manual 00809-0100- 4665, Rev AA August 2010 C-9 Rosemount 8732 Tr a n s m i t t e r Run the 8714i Mete r V erifica tion test on the transmitte r only . This result s in the verification test only checking the tr ans mitter calibration to the limits of the test criteria selected wh en the 8714i Meter V erification test was initiated. 8714i[...]

  • Page 118

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 C-10 8714i Meter V erification T est Result s Parameters Once the 8714i Meter V erification test is initiated, the transmitter will make several measurement s to verify the transmitter calibra tio n, se nsor ca libration, coil circuit health, and electrode circuit h ealth. The res[...]

  • Page 119

    Reference Manual 00809-0100- 4665, Rev AA August 2010 C-1 1 Rosemount 8732 Sensor Calibration V erific at ion Displays the results of the sen sor calibration verification test as either a Pass or Fail. Coil Circuit V erification Displays the results of the coil circ uit health check as either a Pass or Fail Electrode Circuit V erification Displays [...]

  • Page 120

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 C-12 T r oubleshooting the 8714i Meter V erification T est In the event that the 8714i Meter V eri fi cation test fails, the following step s can be used to determin e the appropriate co urse of action. Begin by reviewing the 8714i results to deter mine the specific test that fail[...]

  • Page 121

    Reference Manual 00809-0100- 4665, Rev AA August 2010 C-13 Rosemount 8732 8714i Meter V erification Measurement s The 8714i Meter V erification test will make measuremen ts of the coil resistance, co il signature, and electrod e resistance and comp are these values to the values take n during the sensor signature process to determine the sensor cal[...]

  • Page 122

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 C-14 ROSEMOUNT MAGNETIC FLOWMETER CALIBRATION V ERIFICATION REPORT Calibration V erification Report Parameters User Name: _________________________________________ ____ Calibration Conditions: □ Internal □ External T ag #:_____________________________ _____________________ T e[...]

  • Page 123

    Reference Manual 00809-0100-4 665, Rev AA August 2010 Rosemount 8732 www .rosemount.com Appendix D Digit al Signal Processing Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page D-1 Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page D-2 SAFETY MESSAGES Instructions and proced[...]

  • Page 124

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 D-2 PROCEDURES If the output of your Ro semount 8732 is unstable , first check the wiring and grounding associated with the magnetic flowmeter system. Ensure that the following conditions are met: • Ground straps ar e attached to the adjacent flange or gr ound ring? • Groundin[...]

  • Page 125

    Reference Manual 00809-0100- 4665, Rev AA August 2010 D-3 Rosemount 8732 This software techn ique, known as signal proc essing, “qua lifies” individual flow signals based on historic flow infor ma tion and three user-definable paramete rs, plus an on/off c ontrol. These p arameters are: 1. Number of samples: The n umber of samples function set [...]

  • Page 126

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 D-4 x : Input flow signal from sensor . o : Average flow signals and transmitter outp ut, determined by the “number of samples” parameter . T olerance band, determined by the “percent limit” p arameter . – Upper va lue = average flow + [(per cent limit/100) average flow [...]

  • Page 127

    Reference Manual 00809-0100-4 665, Rev AA August 2010 Rosemount 8732 www .rosemount.com Appendix E Universal Sensor W iring Diagrams Rosemount Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page E-3 Brooks Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page E-6 Perform the Universal Au to T rim func t[...]

  • Page 128

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 E-2 T able E-1. Sensor Cross References Rosem ount T ransmitter Sensor Manufa cturer Page Numbe r Rosemount Rosemount 8732 Rosemount 8705, 8707, 871 1 page E-3 Rosemount 8732 Rosemount 8701 page E-4 Brooks Rosemount 8732 Model 5000 page E-6 Rosemount 8732 Model 7400 page E-7 Endre[...]

  • Page 129

    Reference Manual 00809-0100- 4665, Rev AA August 2010 E-3 Rosemount 8732 ROSEMOUNT SENSORS Rosemount 8705/8707/871 1/8721 Sensors to Rosemount 8732 T ransmitter Connect coil drive and electrode cables as shown in Figure . Figure E-1. Wiring Diagra m to a Rosemount 8732 T ransmitter T a ble E-2. Rosem ount 8705/8707/871 1/8721 Sensor Wiring Connecti[...]

  • Page 130

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 E-4 Rosemount 8701 Sensor to Rosemount 8732 T r ansmitter Connect coil drive and electrode cables as shown in Figure E-2 on page E-4. Figure E-2. Wiring Diagra m for Rosemount 8701 Sensor and Rosemount 8732 T ransmitter T able E-3. Rosemount 8701 Sensor Wiring Connections 2 1 19 1[...]

  • Page 131

    Reference Manual 00809-0100- 4665, Rev AA August 2010 E-5 Rosemount 8732 Connecting Sensors of Other Manufacturers Before connecting another manufacture r ’s sensor to the Rosemount 8732 transmitter , it is necessary to perform the following functions. 1. Turn of f the AC power to the se nso r and transmitt er . Failure to do so could result in e[...]

  • Page 132

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 E-6 BROOKS SENSORS Connect coil drive and electrode cables as shown in Figure E-3. Model 5000 Sensor to Rosemount 8732 T r ansmitter Figure E-3. Wiring Diagra m for Brooks Sensor Model 5000 an d Rosemount 8732 T able E-4. Brooks Model 5000 Sensor Wiring Connections BROOKS MODEL 50[...]

  • Page 133

    Reference Manual 00809-0100- 4665, Rev AA August 2010 E-7 Rosemount 8732 Model 7400 Sensor to Rosemount 8732 T r ansmitter Connect coil drive and electrode cables as shown in Figure E-4. Figure E-4. Wiring Diagra m for Brooks Sensor Model 7400 an d Rosemount 8732 T able E-5. Brooks Model 7400 Sensor Wiring Connections BROOKS MODEL 7400 ROSEMOUNT 87[...]

  • Page 134

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 E-8 ENDRESS AND HAUSER SENSORS Connect coil drive and electrode cables as shown in Figure E-5. Endress and Hauser Sensor to Rosemount 8732 T r ansmitter Figure E-5. Wiring Diagra m for Endress and Hauser Sensors and Rosemount 8732 T a ble E-6. Endres s and Hauser Sensor Wiring Con[...]

  • Page 135

    Reference Manual 00809-0100- 4665, Rev AA August 2010 E-9 Rosemount 8732 FISCHER AND PORTER SENSORS Connect coil drive and electrode cables as shown in Figure E-6. Model 10D1418 Sensor to Rosemount 8732 T r ansmitter Figure E-6. Wiring Diagra m for Fischer and Porter Sensor Model 10D1418 an d Rosemount 8732 T a ble E-7. Fische r and Porter Model 10[...]

  • Page 136

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 E-10 Model 10D1419 Sensor to Rosemount 8732 T r ansmitter Connect coil drive and electrode cables as shown in Figure E-7. Figure E-7. Wiring Diagra m for Fischer and Porter Sensor Model 10D1419 and Rosemoun t 8732 T a ble E-8. Fische r and Porter Model 10D141 9 Sensor Wiring Conne[...]

  • Page 137

    Reference Manual 00809-0100- 4665, Rev AA August 2010 E-1 1 Rosemount 8732 Model 10D1430 Sensor (Remote) to Rosemount 8732 T r ansmitter Connect coil drive and electrode cables as shown in Figure E-8. Figure E-8. Wiring Diagra m for Fischer and Porter Sensor Model 10D1430 (Remote) and Rosemount 8732 T a ble E-9. Fische r and Porter Model 10D1430 (R[...]

  • Page 138

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 E-12 Model 10D1430 Sensor (Integral) to Rosemount 8732 T r ansmitter Connect coil drive and electrode cables as shown in Figure E-9. Figure E-9. Wiring Diagra m for Fischer and Porter Sensor Model 10D1430 (Int eg ra l) an d Rosemount 8732 T able E-10. Fischer and Porter Model 10D1[...]

  • Page 139

    Reference Manual 00809-0100- 4665, Rev AA August 2010 E-13 Rosemount 8732 Model 10D1465 and Model 10D1475 Sensors (Integral) to 8732 T r ansmitter Connect coil drive and electrode cables as shown in Figure E-10. Figure E-10. Wiring Diagram for Fischer and Porter Sensor Model 10D1465 and Model 10D1475 (Integral) an d Rosemount 8732 T able E-1 1 . Fi[...]

  • Page 140

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 E-14 Fischer and Porter Sensor to Rosemount 8732 T r ansmitter Connect coil drive and electrode cables as shown in Figure E-1 1. Figure E-1 1. Generic Wiring Diagram for F ischer and Porter Sensors and Rosemount 873 2 T able E-12. Fischer and Porter Generic Sensor Wiring Connectio[...]

  • Page 141

    Reference Manual 00809-0100- 4665, Rev AA August 2010 E-15 Rosemount 8732 FOXBORO SENSORS Connect coil drive and electrode cables as shown in Figure E-12 . Series 1800 Sensor to Rosemount 8732 T r ansmitter Figure E-12. Wiring Diagram for Foxboro Series 1800 and Rosemount 8732 T able E-13. Foxboro Generic Sensor Wiring Connections ROSEMOUNT 8732 T [...]

  • Page 142

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 E-16 Series 1800 (V ersion 2) Sensor to Rosemount 8732 T r ansmitter Connect coil drive and electrode cables as shown in Figure E-13. Figure E-13. Wiring Diagram for Foxboro Series 1 800 (V ersion 2) and Rosemount 8732 T able E-14. Foxboro Generic Sensor Wiring Connections FOXBORO[...]

  • Page 143

    Reference Manual 00809-0100- 4665, Rev AA August 2010 E-17 Rosemount 8732 Series 2800 Sensor to 8732 T ransmitter Connect coil drive and electrode cables as shown in Figure E-14. Figure E-14. Wiring Diagram for Foxboro Series 2800 and Rosemount 8732 T able E-15. Foxboro Series 2800 Sensor Wiri ng Connections ROSEMOUNT 8732 T RANSMITTER Coil Connect[...]

  • Page 144

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 E-18 Foxboro Sensor to 8732 T r ansmitter Connect coil drive and electrode cables as shown in Figure E-15 . Figure E-15. Generic Wiring Diagram for F oxboro Sen sors and Rosemount 8732 T able E-16. Foxboro Sensor Wiring Connections Electrodes Coils Ground ROSEMOUNT 8732 TR A N S M[...]

  • Page 145

    Reference Manual 00809-0100- 4665, Rev AA August 2010 E-19 Rosemount 8732 KENT V ERIFLUX VTC SENSOR Connect coil drive and electrode cables as shown in Figure E-16. V eriflux VTC Sen sor to 8732 T ransmitter Figure E-16. Wiring Diagram for Kent V eriflux VTC Sensor and Rosemount 8732 T able E-17. Kent V eriflux VTC Sensor Wiring Connections Electro[...]

  • Page 146

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 E-20 KENT SENSORS Connect coil drive and electrode cables as shown in Figure E-17. Kent Sensor to Rosemount 8732 T r ansmitter Figure E-17. Generic Wiring Diagram for Ke nt Sensors an d Rosemount 8732 T a ble E-18. Kent Sensor Wiring Connections Coils Electrodes SCR OUT ROSEMOUNT [...]

  • Page 147

    Reference Manual 00809-0100- 4665, Rev AA August 2010 E-21 Rosemount 8732 KROHNE SENSORS Connect coil drive and electrode cables as shown in Figure E-18. Krohne Sensor to Rosemount 8732 T r ansmitter Figure E-18. Generic Wiring Diagram for Krohne Sensor s and Rosemount 8732 T a ble E-19. Krohne Sensor Wiring Connections Electrodes Coils Coil Shield[...]

  • Page 148

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 E-22 T AYLOR S ENSORS Connect coil drive and electrode cables as shown in Figure E-19. Series 1 100 Sensor to Rosemount 8732 T r ansmitter Figure E-19. Wiring Diagram for T a ylor Series 1 100 Sensors and Rosemount 8732 T a ble E-20. T aylor Series 1 100 Sensor Wiring Connections [...]

  • Page 149

    Reference Manual 00809-0100- 4665, Rev AA August 2010 E-23 Rosemount 8732 T aylor Sensor to Rosemount 8732 T r ansmitter Connect coil drive and electrode cables as shown in Figure E-20. Figure E-20. Generic Wiring Diagram for T aylor Sensors and Rosemount 8732 T able E-21. T aylor Sensor Wiring Connections Electrodes Coils Green ROSEMOUNT 8732 T RA[...]

  • Page 150

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 E-24 Y AMATAKE HONEYWELL SENSORS Connect coil drive and electrode cables as shown in Figure E-21. Y amatake Honeywell Sensor to Rosemount 8732 T r ansmitter Figure E-21. Generic Wiring Diagram for Y amatake Honeywell Sensors and Rosemount 8732 T a ble E-22. Y amatake Honeywell Sen[...]

  • Page 151

    Reference Manual 00809-0100- 4665, Rev AA August 2010 E-25 Rosemount 8732 Y OKOGAWA SENSORS Connect coil drive and electrode cables as shown in Figure E-22 . Y okogawa Sensor to Rosemount 8732 T r ansmitter Figure E-22. Generic Wiring Diagram for Y okogawa Sensors and Rosemount 8732 T able E-23. Y okogawa Sensor Wiring Connections Electrodes Coils [...]

  • Page 152

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 E-26 GENERIC MANUFACTURER SENSORS Generic Manufacturer Sensor to Rosemount 8732 T r ansmitter Identify the T erminal s First check the sensor manu facturer ’s manual to identify the app ropriate terminals. Otherwise, perform the following procedure. Identify coil and electrode t[...]

  • Page 153

    Reference Manual 00809-0100-4 665, Rev AA August 2010 Rosemount 8732 www .rosemount.com Appendix F Physical Block Physical Block Paramete r Attribute Definitions . . . . . . . page F-1 I&M Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page F-4 PHYSICAL BLOCK PARAMETER ATTRIBUTE DEFINITIONS The following table de[...]

  • Page 154

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 F-2 26 DEVICE_M AN_ID Mapped to Mfg_ID parameter in Manufacturing Block 27 DEVICE_I D Mapped to DEV_T YPE parameter in Manufacturing Block 28 DEVICE_S ER_NUM Mapped to last 16 characters of DEVICE_ID_ STRING par ameter in Manufacturing Block 29 DIAGNOSIS Detailed information of th[...]

  • Page 155

    Reference Manual 00809-0100- 4665, Rev AA August 2010 F-3 Rosemount 8732 40 IDENT_NUMBER_SELECTOR 0: profile specific Ident_Number V3.0 (mandatory) 1: manufacturer specific Ident_Number V3.0 (optional) 41 HW_WRITE_PROTECTION Not supported in the device 42 FEA TU RE Supported: Expanded diag, cond ensed status Enabled: Expanded diag,condensed status [...]

  • Page 156

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 F-4 I&M PARAMETERS T able F-2. I&M Parameters Index - The I&M bl ock index Sub Index - IM_INDEX values Element - The sub p arameter index within the I&M paramete r Parameter Mnemonic - Usage identifier for the I&M p arameter Parameter Name - This simply gives a[...]

  • Page 157

    Reference Manual 00809-0100-4 665, Rev AA August 2010 Rosemount 8732 www .rosemount.com Appendix G T ransducer Block T ransduce r Block Parameter Attribute Definitions . . . . . p age G-1 T RANSDUCER BLOCK PARAMETER ATTRIBUTE DEFINITIONS The following table describes the parameters that are available in the transducer block. Each line item in the t[...]

  • Page 158

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 G-2 25 LOW_FLOW_CUTOFF When flow rate is less than this entered value, flow rate output will be set to 0.0 flow. See section Engineering Units for supported unit codes. 26 MEASUREMENT_MODE Mode of flow measurement, either unidirectional or bidi rectional measurement. 27 FLOW_DIREC[...]

  • Page 159

    Reference Manual 00809-0100- 4665, Rev AA August 2010 G-3 Rosemount 8732 78 EP_TRIG_COUNTS Number of EP measurements that must be above the trigger level to set e mpty pipe. 79 EP_TRIG_LEVEL Empty Pipe T rigger Level. 80 EP_V ALUE V alue of the Empty Pipe measure ment. (Same scale as EP_TRIG_LEVEL). 81 ELECT_TEMP Compensated electronics temperature[...]

  • Page 160

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 G-4 11 7 METER_VERIF_TEST_COND_IN Incoming T est Condition of the Flowmeter V erification T est Note: This parameter needs to be configured before the Meter V erification is st arted via the PERFORM_METER_VERIFY parameter . 11 8 METER_VERIF_TEST_COND_OUT Actual T est Condition of [...]

  • Page 161

    Reference Manual 00809-0100- 4665, Rev AA August 2010 G-5 Rosemount 8732 142 FINGERPRINT_SELECT Components to re-fingerprint. Note: This parameter needs to be configured before the Refingerprint op eration is started via the PERFORM_REFINGERPRINT_FLOWTUBE parame ter . 143 SENSOR_RANGE_LO Sensor range parameter used to calculate if the PV value is f[...]

  • Page 162

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 G-6[...]

  • Page 163

    Reference Manual 00809-0100-4 665, Rev AA August 2010 Rosemount 8732 www .rosemount.com Appendix H GSD File for Rosemount 8732E Magnetic Flow T ransmitter Profibus DP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p age H-1 Module Related Information . . . . . . . . . . . . . . . . . . . . . . . p age H-2 Extended Diagnos[...]

  • Page 164

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 H-2 MODULE RELATED INFORMATION DESCRIPTION OF EXTENDED DP FEATURES DESCRIPTION OF PHYSICAL INTERFACE FOR ASYNC. AND SYNC. TRANSMISSION DESCRIPTION OF DEVICE RELATED DIAGNOSIS Modular S tation 1; 1: Modular Device MaxModule 4 ;No. of(AI + T otalizer): 1-AI, 3-T otalizer Max Input L[...]

  • Page 165

    Reference Manual 00809-0100- 4665, Rev AA August 2010 H-3 Rosemount 8732 EXTENDED DIAGNOSTIC BYTES - MANUFACTURER SPECIFIC MODULE DETA ILS Unit Diag Bit(34) Configuration invalid Unit Diag Bit(35) Restart Unit Diag Bit(36) Coldstart Unit Diag Bit(37) Maintenance required Unit Diag Bit(38) Characteristics invalid Unit Diag Bit(39) Ident_Number viola[...]

  • Page 166

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 H-4 DESCRIPTION OF THE MODULE ASSIGNMENT The numbers co rresponding against a p articular slot indica tes which module is default for this slot. The module references sepe rated by commas that follow next indicate which mo dules are allo wed to be inserted into the relevant slot. [...]

  • Page 167

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Index-1 Rosemount 8732 A Action Keys Handheld Communicator .H - 1 AI Block Configuration . . . . . . . . . 3-2 Assigning Device Tag and Node Address . . . . . . . . . . . . . . . . 3-2 Auto Zero . . . . . . . . . . . . . . . D-2 B Block Configuration AI Block Flow-specific Block Configuration 3-[...]

  • Page 168

    Reference Manual 00809-0100- 4665, Rev AA August 2010 Rosemount 8732 Index-2 P Piping . . . . . . . . . . . . . . . . . . 5-4 Power Supply Load Limitations A-3 Process Grounding . . . . . . . 5-12 Process Leak Containment . . . . . . . . . 5-17 Protection Overcur rent . . . . . . . . . . 2-6 Protective Ground Connection . . . . 5-13 R Relief Valves[...]

  • Page 169

    [...]

  • Page 170

    [...]

  • Page 171

    [...]

  • Page 172

    Emerson Process Management The Emerson logo is a trade mark and se rvice mar k of Emerson Electric Co. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc. PlantWeb is a registered trademark of one of t he Emerson Process Management group of companies. All other marks are the property of their respective owners. S tandar[...]