Simplicity LINC GATEWAY 514067-UAD-A-0509 manual

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18

Go to page of

A good user manual

The rules should oblige the seller to give the purchaser an operating instrucion of Simplicity LINC GATEWAY 514067-UAD-A-0509, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.

What is an instruction?

The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of Simplicity LINC GATEWAY 514067-UAD-A-0509 one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.

Unfortunately, only a few customers devote their time to read an instruction of Simplicity LINC GATEWAY 514067-UAD-A-0509. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.

What should a perfect user manual contain?

First and foremost, an user manual of Simplicity LINC GATEWAY 514067-UAD-A-0509 should contain:
- informations concerning technical data of Simplicity LINC GATEWAY 514067-UAD-A-0509
- name of the manufacturer and a year of construction of the Simplicity LINC GATEWAY 514067-UAD-A-0509 item
- rules of operation, control and maintenance of the Simplicity LINC GATEWAY 514067-UAD-A-0509 item
- safety signs and mark certificates which confirm compatibility with appropriate standards

Why don't we read the manuals?

Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of Simplicity LINC GATEWAY 514067-UAD-A-0509 alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of Simplicity LINC GATEWAY 514067-UAD-A-0509, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the Simplicity service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of Simplicity LINC GATEWAY 514067-UAD-A-0509.

Why one should read the manuals?

It is mostly in the manuals where we will find the details concerning construction and possibility of the Simplicity LINC GATEWAY 514067-UAD-A-0509 item, and its use of respective accessory, as well as information concerning all the functions and facilities.

After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.

Table of contents for the manual

  • Page 1

    514067-UAD-A- 0509 APPLICATION GUIDE OVERVIEW The Simplicity ® LINC Gateway operates as a Modbus® Client providing an interface between a BACnet® MS/TP control system and devices that communicate using the Modbus RTU protocol. The Simplicity ® LINC allows monitoring and cont rol by a third-party BACnet Building Automation System (BAS). The Simp[...]

  • Page 2

    514067-UAD -A-0509 2 Johnson Controls Unitary Products CONNECTION The Simplicity ® LINC has 2 ports, one fo r connection to the BAS network (BACnet) and one to the Simplicity ® board (Modbus). BACNET NETWORK The only connection required in the field is to the BACnet (BAS) network. NOTE: Proper termination and groun ding of the shields must be obs[...]

  • Page 3

    514067-UAD-A-0509 Johnson Controls Unitary Products 3 FLASH MEMORY MANAGEMENT The Flash Memory chip used in the Simp licity ® controllers has a 1,000,000 write cycle rating. To prevent premature failure of the flash memory, it should not be written to more often than once every 10 minutes, on average. ADDITIONAL CAPABILITY MODBUS COMMUNICATION ALA[...]

  • Page 4

    514067-UAD -A-0509 4 Johnson Controls Unitary Products TABLE 2: POINTS LIST IN DESCRIPTION ORDER Read/ Write BACnet Object T ype BACnet Object Inst Descriptor Default Min Max Point Description R (2) A V 14 ACC_OVER_TME – – – Accumulated Unoccupied Override T ime (in hours) R (2) A V 15 ACTIVE_ALARM – – – Active Alarm R (5) BV 16 AIR_PRO[...]

  • Page 5

    514067-UAD-A-0509 Johnson Controls Unitary Products 5 TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED) Read/ Write BACnet Object T ype BACnet Object Inst Descriptor Default Min Max Point Description R/W (2) A V 20 ECO_1ST_STPT 55 40 65 Economizer First Stage Setpoint R (5) BV 7 ECONO_INST – – – Economizer Installed R (5) BV 36 ECO_L_TO_S[...]

  • Page 6

    514067-UAD -A-0509 6 Johnson Controls Unitary Products TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED) Read/ Write BACnet Object T ype BACnet Object Inst Descriptor Default Min Max Point Description R (5) BV 44 E_HPS1 – – – Elite High Pressure Switch for Compressor #1 Input Status (1=closed, 0=open/fault) R (5) BV 48 E_HPS2 – – – [...]

  • Page 7

    514067-UAD-A-0509 Johnson Controls Unitary Products 7 TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED) Read/ Write BACnet Object T ype BACnet Object Inst Descriptor Default Min Max Point Description R (5) BV 66 E_FREEZE_ST – – – Hot H2O Freeze Thermostat Switch #1 Input Status (1=closed, 0=open/fault) R (2) A V 55 HW_VL V_OUT – – –[...]

  • Page 8

    514067-UAD -A-0509 8 Johnson Controls Unitary Products TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED) Read/ Write BACnet Object T ype BACnet Object Inst Descriptor Default Min Max Point Description R (5) BV 14 LOW_SUP_VOL T – – – Low Supply V oltage (0=comps not overrid- den by LSV , 1=comps overridden) R/W (5) BV 96 MANUAL_WRITE – ?[...]

  • Page 9

    514067-UAD-A-0509 Johnson Controls Unitary Products 9 TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED) Read/ Write BACnet Object T ype BACnet Object Inst Descriptor Default Min Max Point Description R/W (2) A V 71 SPCE_ALM_TMP 0 0 25 Space Sensor Alarm T emperature (degrees F , 0 = disabled) R/W (2) A V 72 SPCE_ALM_TIM 0 0 120 Space Sensor Ala[...]

  • Page 10

    514067-UAD -A-0509 10 Johnson Controls Unitary Products TABLE 3: POINTS LIST IN OBJECT ORDER Read/ Write BACnet Object T ype BACnet Object Inst Descriptor Default Min Max Point Description R/W (2) A V 1 OCC_COOL_SP 72 45 99 Occupied Cooling Setpoint R/W (2) A V 2 UNOC_COOL_SP 85 45 99 Un-Occupied Cooling Setpoint R/W (2) A V 3 SA T_COOL_SP 50 40 65[...]

  • Page 11

    514067-UAD-A-0509 Johnson Controls Unitary Products 11 TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED) Read/ Write BACnet Object T ype BACnet Object Inst Descriptor Default Min Max Point Description R (2) A V 38 ALARM_3 – – – System Alarm #3 R (2) A V 39 ALARM_4 – – – System Alarm #4 R (2) A V 40 ALARM_5 – – – System Alarm #5 R ([...]

  • Page 12

    514067-UAD -A-0509 12 Johnson Controls Unitary Products TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED) Read/ Write BACnet Object T ype BACnet Object Inst Descriptor Default Min Max Point Description R/W (2) A V 69 OP_STPT_DIF 1 1 5 Operating Setpoint Differential R/W (2) A V 70 SA T_ALM_COOL 0 0 80 Supply Air T emperature Alarm Setpoint for Cooli[...]

  • Page 13

    514067-UAD-A-0509 Johnson Controls Unitary Products 13 TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED) Read/ Write BACnet Object T ype BACnet Object Inst Descriptor Default Min Max Point Description R (5) BV 19 LOW_AMB_OVRD – – – Low Ambient T emperature (0=comps not overridden by LA T , 1=comps overridden) R (5) BV 20 POP_ENABLED – – ?[...]

  • Page 14

    514067-UAD -A-0509 14 Johnson Controls Unitary Products TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED) Read/ Write BACnet Object T ype BACnet Object Inst Descriptor Default Min Max Point Description R (5) BV 47 E_LPS2 – – – Elite Low Pressure Switch for Compressor #2 Input Status (1=closed, 0=open/fault) R (5) BV 48 E_HPS2 – – – Elite[...]

  • Page 15

    514067-UAD-A-0509 Johnson Controls Unitary Products 15 TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED) Read/ Write BACnet Object T ype BACnet Object Inst Descriptor Default Min Max Point Description R (5) BV 71 I_IF AN_ST A T – – – Intelli-Comfort Indoor Fan Output Status (0=output is OFF , 1=output is ON) R (5) BV 72 I_F AN_OVER – – –[...]

  • Page 16

    514067-UAD -A-0509 16 Johnson Controls Unitary Products TROUBLESHOOTING The Simplicity ® LINC Gateway consists of two printed circuit boards. TABLE 4: SIMPLICITY ® LINC GATEWAY RS485 BOARD (Bottom) BacNET Board (Top) Normal Board Op eration Normal Board Op eration The PWR LED should be on during operation. The RX and T X LEDs should flash when a [...]

  • Page 17

    514067-UAD-A-0509 Johnson Controls Unitary Products 17 FIGURE 3: SIMPLICITY ® LINC GATEWAY LED LOCATION PWR (RS485) PWR (BACnet) GP105 (BACnet) LB (BACnet) RX (RS485) TX (RS485) LA (BACnet) TX (BACnet) RX (BACnet)[...]

  • Page 18

    Subject to change without notice. Print ed in U.S.A. 514067-UAD-A-0509 Copyright © 2009 by Johnson Controls, Inc. Al l rights reserved. Supersedes: Nothing Johnson Contro ls Unitary Products 5005 York Drive Norman, OK 73069[...]