Raypak B6000 manual

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51

Go to page of

A good user manual

The rules should oblige the seller to give the purchaser an operating instrucion of Raypak B6000, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.

What is an instruction?

The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of Raypak B6000 one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.

Unfortunately, only a few customers devote their time to read an instruction of Raypak B6000. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.

What should a perfect user manual contain?

First and foremost, an user manual of Raypak B6000 should contain:
- informations concerning technical data of Raypak B6000
- name of the manufacturer and a year of construction of the Raypak B6000 item
- rules of operation, control and maintenance of the Raypak B6000 item
- safety signs and mark certificates which confirm compatibility with appropriate standards

Why don't we read the manuals?

Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of Raypak B6000 alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of Raypak B6000, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the Raypak service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of Raypak B6000.

Why one should read the manuals?

It is mostly in the manuals where we will find the details concerning construction and possibility of the Raypak B6000 item, and its use of respective accessory, as well as information concerning all the functions and facilities.

After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.

Table of contents for the manual

  • Page 1

    Catalog No.: 5000.51J Effective: 10-14-05 Replaces: 06-15-03 B6000 BOILER MANAGEMENT SYSTEM Inst allation and Operating Manual Part No. 240564 TM SYSTEM CONTROL BOILER MONITOR[...]

  • Page 2

    Page 2 is a registered trademark of UnderWriters Laboratories Inc. ® is a registered trademark of UnderWriters Laboratories-Canada Inc.® ______________________________________________________________________________________ Before operating this product, please read these instructions completely.[...]

  • Page 3

    B6000 BOILER MANAGEMENT SYSTEM (BMS) Content s Equipment Quantity B6000 System Control 1 B6000 Boiler Monitor, Installed on Boiler(s) As Ordered Outdoor Temperature Sensor Assy. (064140) 1 Water Temperature Sensor Assy. (064139) 1 Optional Equipment As Ordered Check packaging for damage or missing components. IMPORT ANT NOTICE: These instructions a[...]

  • Page 4

    Page 4 T ABLE OF CONTENTS PAGE Contents 3 Getting Started 5 Foreword 5 Installation and Mounting 7 Mechanical Installation 7 Electrical Installation 8 Check Your Power Source 8 Air Temperature Sensor 9 Water Temperature Sensor 10 Important Configuration Note 12 Wiring - Air and Water Sensors 12 Communication (RS485) Wiring 13 Wiring: Power Source t[...]

  • Page 5

    Page 5 Thank you for selecting the Raypak B6000 Boiler Management System (BMS). It is our sincere hope that you will enjoy its power, ease of use and energy saving features. GETTING STARTED To learn about the B6000 BMS, simply install it and start using it. The following steps will outline the things you will need for installation and to prepare it[...]

  • Page 6

    Page 6 Each Boiler Monitor Module contains • The boiler on-off power switch. • The boiler manual override switch, which allows the boiler to operate independently in the event of a system control failure. • Standard indicator lights: "Power On" - green, indicates the boiler is powered. "Manual Override" - red, indicates bo[...]

  • Page 7

    INST ALLA TION AND MOUNTING The System Control module should be mounted on a permanent base not subject to vibrations, moisture or dust. It should be mounted with the display screen at a convenient height for reading and for access to the alarm silence button located on the top of the cabinet. Dimensions & Weight Boiler Monitor System Control 1[...]

  • Page 8

    CB WHITE GROUND BLACK GREEN A B C PIDOMA VOM A sub-panel containing the disconnect switches and surge suppressors is required at or near the equipment location(s). For accessibility remove the lower interior panel, by removing the four (4) access screws. INSTALL CONDUIT AS APPROPRIATE. NOTE: Shielded cable, Belden #8132 or #9842 or equivalent, must[...]

  • Page 9

    Page 9 AIR TEMPERA TURE SENSOR • INSTALLATION Fig. #9040 TYPICAL AIR TEMPERATURE SENSOR Air Temperature Sensor Installation Notes: • Locate on coldest side of building, usually (North or West) side. • Install the sensor in a shaded area, out of direct sunlight. • Locate no higher than 2/3 way up side of building or between 2nd and 3rd floor[...]

  • Page 10

    W A TER TEMPERA TURE SENSOR • INSTALLATION The water sensor should be installed in the system supply. Multiple Boilers Single Boiler Water Sensor TYPICAL WATER SENSOR Water Temperature Sensor Installation Notes: • Locate sensor in system piping within a minimum of three (3) feet or prior to the first take off connection, on the downstream side [...]

  • Page 11

    WATER TEMPERATURE SENSOR INSTALLATION (Domestic Hot Water Supply) Page 11 SIMPLIFIED DIAGRAM OF TYPICAL PIPING (PIPING LAYOUT MAY VARY PER SPECIFIC APPLICATION) AIR TEMPERATURE SENSOR MUST BE INSTALLED ACROSS AIR TEMPERATURE SENSOR CONTACTS. THE SENSOR IS NOT ACTIVATED AND CAN BE LEFT STORED IN B6000 ENCLOSURE. BOILER HOT WATER SUPPLY IMMERSION WEL[...]

  • Page 12

    Page 12 IMPORT ANT Configuration Note: If your System Control Module is supplied with a single Field Wiring Teminal Strip use "Alternate" wiring. (See page 36-38) WIRING - AIR AND W A TER SENSORS TO THE SYSTEM CONTROL MODULE WATER SENSOR OUTDOOR SENSOR SYSTEM CONTROL TERMINAL TB 2 BELDEN #8132 OR BELDEN #9842 NOTE: Tighten terminal strip [...]

  • Page 13

    COMMUNICA TION (RS 485) WIRING System Control Boiler Monitor • Use Belden #9842 Cable Or Equivalent (See Note). Polarity must be observed. Make use of wire color coding to ensure proper polarity. • The shielding foil wrapper - bare wire (drain) - MUST be grounded. Grounding is done at the System Control Module only. DO NOT ground at Boiler Moni[...]

  • Page 14

    WIRING: WIRING: WIRING: WIRING: WIRING: P P P P P o o o o o w w w w w er Sour er Sour er Sour er Sour er Sour ce to System Contr ce to System Contr ce to System Contr ce to System Contr ce to System Contr ol and Boiler Mod- ol and Boiler Mod- ol and Boiler Mod- ol and Boiler Mod- ol and Boiler Mod- ules. ules. ules. ules. ules. Page 14 • Observe [...]

  • Page 15

    POWER TEST CHECK POWER Utilizing a Volt-Ohm-Meter (VOM) monitor the following on the "System Control Module" and "Boiler Monitor(s)" for proper voltage levels. POWER TEST TABLE Module Test Points Indication System Control TB1-1- TB1-2 108 VAC to 132 VAC System Control TB1-1- TB1-3 108 VAC to 132 VAC System Control TB1-2- TB1-3 L[...]

  • Page 16

    SWITCH POSITION BOILER NUMBER SWITCH 1234 5 678 8 OOOO O OOO 7 OOOO O OOO 6 OOOO O OOO 5 OOOO O OOO 4 OOOO O OOO 3 OOOO X X X X 2 O O X X O O X X 1 O X O X O X O X IMPORTANT: The Boiler Monitor control board has a series of dip switches which iden- tify the boiler(s) (SW2). It is required that the switches be set as shown in the switch position tab[...]

  • Page 17

    BOILER MONITOR COMMUNICA TIONS JUMPER W1 • Located in the upper left hand corner of the "LAST" Boiler Monitor board. • NOTE: The jumper indicates to the System Controller logic that the "Last" wired boiler has been communicated with over the RS485 BUSS Link. • Definition: The "LAST" wired boiler is physically wir[...]

  • Page 18

    OPTIONAL BOILER MONIT OR • Wiring • Contact Authorized Raypak representative for other wiring options Dia. #2 Page 18 NOTE: Tighten terminal strip clamping screws 20 lbs - In (2.26N.m) Breakage from over torquing is not covered under warranty. Use copper conductors only. For supply connections use wires sized on the basis of 60°C Ampacity and [...]

  • Page 19

    Page 19 Field Wiring - Multiple Boilers Dia. #7[...]

  • Page 20

    INST ALLA TION VERIFICA TION PROCEDURE REGISTER Before proceeding any further, please verify that the user registration form has been completed and mailed (reference: Registration Card ). MECHANICAL INSTALLATION Verify installation has been completed (reference: Mechanical Installation ). AIR TEMPERATURE SENSOR Verify installation parameters have b[...]

  • Page 21

    Page 21 SYSTEM CONTROL/DISPLA Y F AMILIARIZA TION The System is set up by using the selector buttons and the displays on the System Control module. There are ten or more displays. Each display provides information regarding the system operating parameters and system component status. Some displays provide information only, such as current outdoor t[...]

  • Page 22

    Page 22 NOTE: Nite setback feature must be set at the B6000 BMS Control Panel to "ON". This results in display change that shows NITE rather than DAY. The BMS can change "SETBACK TIMES" up to six selections for each of the seven days. WARNING WARNING WARNING WARNING WARNING WARNING When the initialize control selection is set to[...]

  • Page 23

    DISPLAYS System Temperatures * Indicates selectable item Program the System Control Module to meet the design conditions of the installation. Return to System Temperature Display by pressing the "MENU" button until screen appears as below. Current Outdoor Air Current System Target Temperature Temperature Water Temperature System Design Te[...]

  • Page 24

    Boiler Status Operating status of boiler *Boiler Ok or Fault Indicator Pushing "+" or "-" buttons will show status of other boiler(s) in system READOUT Readout OK - boiler operation normal FAULT indications: MAX TEMP - Target exceeds Max Temp -Not a fault- THERMOSTAT - Operating aquastat - Not a fault - LWCO - low water cutoff -[...]

  • Page 25

    Page 25 GREEN RED A MBER GR EEN RED Power Manual Call Pump Low System Cont rol On Over- f or On W ater Display ride Heat  Cu toff OK x x x System operating normally L W C O x xxx Low w ater in boiler LOW PRES W ATER x x x W ater Press u re t oo low LO PR ESS GAS x x x Gas pressure below setting HIGH P RESS GAS x x x Gas pressure on m ani f ol d [...]

  • Page 26

    Primary Control Parameters *System water temperature *RESET RATIO * Rise is the temperature rise in desired at outdoor Ratio of outdoor temperature system when all boilers are at full temperature of 70°. to water system temperature. rate. (ÐT of system) Range 1 -99 Range 40 - 200 Range: 0.0:1 to 20: and "None" Default value is 20°F Def[...]

  • Page 27

    PUSH SELECT RATIO – Sets the desired change in system water temperature increases as the outdoor temperature decreases. The reset ratio is expressed as follows: 2:1 for every 2 degree change in outdoor temperature the sytem temperature will change 1 degree. Temperature °F e.g: Set = 135°F Ratio Outdoor System 2:1 60 140 40 1 50 20 1 60 Suggeste[...]

  • Page 28

    Page 28 *C Band is a range of temperature above and below the target temperature. Range 1-9 Default value is 3°F. *O/Cdb, Outdoor cutoff deadband is the number of degrees below O/C where O/C reset occurs. Range 1-9 Default value is 4°F. *O/C Maximum outdoor temperature that heat is desired, set at 70°, Range 35° to 199°. Default value is 65. *[...]

  • Page 29

    L e a d # o f B o i l e r s XX *STEP Enter desired valve firing increments. Recommended setting is between 5% and 20% for Modulating Boiler. Or Enter 1S If Gas Valve is an On-Off or Single Stage Or Enter 2S If Gas Valve is 2 Stage Firing Or Enter 20% If the control boilers include modulating and 2 stage or single stage boilers under control of a si[...]

  • Page 30

    LEAD LAG , NIGHT SET BACK Automatic Lead Lag *Lead Change Hours Designated lead boiler will change when remaining hours reaches 0. Range 0-225 hrs. Default value is 100 hrs. If set at 0 hours lead will not change. Hours remaining will automatically total. Enter the desired number of hours of lead boiler operation before change. Hours re- maining is[...]

  • Page 31

    Night Setback "OFF" indicates the system is in the Normal or design operating mode. "ON" indicated the system is operating in a programmed night setback mode. LEAD LAG , NIGHT SET BACK Automatic Lead Lag *Set Time of day ** Day of Week *** On or Off This screen shows the time and day of the week. Default values: Monday for the d[...]

  • Page 32

    Page 32 Set Back Example: Period SETBACK SETBACK "ON" "OFF" DAY 1 xx:xx 05:00 am Monday 2 10:00 pm xx:xx Monday 1 xx:xx 05:00 am Tuesday 2 10:00 pm xx:xx Tuesday 1 xx:xx 05:00 am Wednesday 2 10:00 pm xx:xx Wednesday 1 xx:xx 05:00 am Thursday 2 10:00 pm xx:xx Thursday 1 xx:xx 05:00 am Friday 2 10:00 pm xx:xx Friday 1 xx:xx xx:xx [...]

  • Page 33

    *Pconst is the proportional ratio which causes the boiler to step up or down, faster or slower (over- shoot or undershoot) and finally end up offset from desired tem- perature. Default is 1/3. *Dconst is the derivative ratio which tells the system how first to react to differing changes in water temperature. Default is 3/1. *Wait is the time contro[...]

  • Page 34

    Page 34 *Pconst Proportional ratio which causes the boiler to step up or down, faster or slower. *WAIT Wait as time controller hesitates before acting on a temperature change. *Dconst Derivative ratio speeds or slows boiler response compensating for overshoot and undershoot. *Pconst is the proportional ratio which causes the boiler to step up or do[...]

  • Page 35

    T e m p : XXX ( XXX ) m : x XXX% XXX% XXX% XXX% X X X% tandard Initialize LEAD LAG , NIGHT SET BACK Initialize Y - Yes N - No Version # of software. * This will initialize all previous selectable values to default values. Should not be used unless operator wants to reprogram new values. Should be used at Start-up to clear the control memory. This s[...]

  • Page 36

    Page 36 IMPORTANT START "ALTERNATE" If your system module(s) are supplied with a single Field Wiring Terminal Strip use this method for wiring. WIRING - AIR AND WATER SENSORS To The System Control Module WATER SENSOR OUTDOOR SENSOR BELDEN #8132 or BELDEN #9842 Dia. #10 AIR/WATER TEMPERATURE SENSOR SCHEMATIC BARE WIRE (SHIELD/ DRAIN) TO: S[...]

  • Page 37

    Page 37 "ALTERNATE" Continued COMMUNICATION (RS 485) WIRING From: System Control Module To: Boiler Module • Shielded communications cable - Belden #9842 must be used. Polarity must be observed. Make use of wire color coding to ensure polarity. • The shielding [foil wrapper - bare wire (drain)] MUST be grounded. Grounding is done at th[...]

  • Page 38

    WIRING: Power Source to Control and Boiler Modules • Observe Polarity very important. • Observe wire colors • Provide external surge suppressor capable of maintaining system integrity. • Provide overload protection and discon- nect means as required by code and for equipment serviceability. • Conduit can NOT be used as ground. * Must be &[...]

  • Page 39

    "ALTERNATE" POWER TEST CHECK POWER Utilizing a Volt-Ohm-Meter (VOM) monitor the following on the "System Control" and "Boiler Monitor(s)" for proper voltage levels. Check at the Terminal Block (TB). POWER TEST TABLE SYSTEM CONTROL INDICATION From: To: TB pin 1 TB pin 2 108 VAC to 132 VAC TB pin 1 SPG 108 VAC to 132 VAC[...]

  • Page 40

    Page 40 Fig. # 9458[...]

  • Page 41

    Page 41 Fig. # 9459[...]

  • Page 42

    SYSTEM CONTROL BOARD Page 42 Fig. # 9460[...]

  • Page 43

    Page 43 Replacement Parts List New Part # CP10.0_ _ _ CP10.0N _ _ CP10.0NMn 90FI 90EI 900D[...]

  • Page 44

    Replacement Parts List Page 44[...]

  • Page 45

    Page 45 BOILER MONITOR CONTROL BOX Located in place of ignition control on C2 boilers only. Fig. # 9461[...]

  • Page 46

    Replacement Parts List CALL OUT B 6000 SYSTEM PART NO. Boiler Monitor Control Box B-1 Control PC Board 004795F B-2 Power/Manual or Override Switch 650745 B-3 Transformer, 120/8.5 VAC C.T. 064921 B-4 Transformer, 120/24 VAC C.T. 650495 B-5 Transformer, 120/24 VAC (C2 Units only) 650495 B-6 Ignition Control with Lockout 004818B F1 & F2 Fuse, AGC [...]

  • Page 47

    B6000 BOILER MANAGEMENT SYSTEM START-UP DATA SYSTEM SETTINGS ENTERED ON DATE:_____________________________________ Temperature Scale °F or °C Standard Set _____ Deg. Ratio _____ : 1 Rise _____ Deg. System Water Temp. @ Oc Reset Ratio-Outdoor: System Design Temp. Diff. Default Value 100°F (38°C) Default Value: 1.0:1 Default Value: 20°F (7°C) S[...]

  • Page 48

    Page 48 The procedures outlined below assume that the initial installation / turn on / power up procedures have been completed and that the B6000 was operational. This guide is a basic instruction to determine if an authorized Raypak representative should be contacted. If you follow the instructions in this manual and have difficulty operating the [...]

  • Page 49

    Trouble Shooting Guide-Continued Symptom Boiler # x "Not on Line" Displayed Outdoor Temp. Sensor readings are high. Sensor reading 220°F. Sensor reading - 35°F. Low water cut-off alarm. Power lamp off on Boiler Monitor. Pump not running. Off at flow switch. Off on High Limit. Corrective Action Check primary power. Correct as necessary. [...]

  • Page 50

    LIMITED WARRANTY B6000, Y-Series, E-4 & Accessories SCOPE OF WARRANTY : Raypak, Inc. ("Raypak") warrants to the original owner the Control System to be free from defects in materials and workmanship under normal use and service for the applicable warranty period. In accordance with the terms of this Limited Warranty, RAYPAK will furni[...]

  • Page 51

    Design and specifications subject to change without notice. This symbol on the nameplate means the product is listed by Underwriters Laboratories, Inc. ® Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 • (805) 278-5300 • FAX (800) 872-9725 Litho in U.S.A. www .raypak.com U L ®[...]