A good user manual

The rules should oblige the seller to give the purchaser an operating instrucion of Hubbell Electric Heater Company " SE ", along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.

What is an instruction?

The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of Hubbell Electric Heater Company " SE " one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.

Unfortunately, only a few customers devote their time to read an instruction of Hubbell Electric Heater Company " SE ". A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.

What should a perfect user manual contain?

First and foremost, an user manual of Hubbell Electric Heater Company " SE " should contain:
- informations concerning technical data of Hubbell Electric Heater Company " SE "
- name of the manufacturer and a year of construction of the Hubbell Electric Heater Company " SE " item
- rules of operation, control and maintenance of the Hubbell Electric Heater Company " SE " item
- safety signs and mark certificates which confirm compatibility with appropriate standards

Why don't we read the manuals?

Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of Hubbell Electric Heater Company " SE " alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of Hubbell Electric Heater Company " SE ", and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the Hubbell Electric Heater Company service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of Hubbell Electric Heater Company " SE ".

Why one should read the manuals?

It is mostly in the manuals where we will find the details concerning construction and possibility of the Hubbell Electric Heater Company " SE " item, and its use of respective accessory, as well as information concerning all the functions and facilities.

After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.

Table of contents for the manual

  • Page 1

    OPERATING AND MAINTENANCE MANUAL FOR COMMERCIAL ELECTRIC WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL “ SE ”[...]

  • Page 2

    2 HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203) 378-2659 FAX: (203) 378-3593 INTERNET: http://www.hubbellheaters.com/ -- IMPORTANT -- Always reference the f ull model num ber and serial number when calling the factory. WARNING / CAUTION 1. Tank is to be complete ly fille d with water and a ll air is to be vente d bef[...]

  • Page 3

    3 TABLE OF CONTENTS SECTION TITLE PAG E # I GENERAL DESCRI P TI ON AND CONSTRUCTION 5 II INSTAL LATI ON 10 III S C H E D U LE D M A IN TE NANC E AND OPERATION 12 I V TROUBL ES HOOTI NG 14 V SERVICI NG AND REPLACEMENT OF PARTS 16 VI MI SCELL ANEOUS C HARTS AND FORMULAS 24[...]

  • Page 4

    4[...]

  • Page 5

    5 SECTION I - GENERAL DESCRIPTION AND CONST RUCTION GENERAL DESCRIPTION This book describes a packaged electric water heater that is a stationary, self-contained unit. The complete assembly consists of the storage tank, immersion electric heating element(s), thermostat, safety relief valve, safety high temperature cut out, magnetic contactor(s), an[...]

  • Page 6

    6 CONTROL THERMOS TAT The water heater is supplied with either a surface mounted or immersion thermostatic switch that is installed and wired at the factory . See drawing for specific details. The surface mounted thermostat can be adjusted through a range of 110° - 170° F . The immersion thermostat can be adjusted through a range of 100° - 190°[...]

  • Page 7

    7 MAGNETIC CONTACTOR The magnetic contactor(s) is a heavy -duty resistive load ty pe rated for 100,000 cy cles. T he co nt act o r su ppl i es p ow er t o t he hea ti ng e le men t( s) and is si z ed b as ed on t he resistive load (non-inductive) rating of the circuit. The contactor supplies power on ly whe n t he t he rm os ta ti c s wit ch is en [...]

  • Page 8

    8 Fused Low Voltage Transformer A fused low voltage transformer may be supplied. This option is used to step down higher voltages to 120-volt for the control circuit. Dial Temperature an d Pressure Gauge A combination temperature (70° - 250° F) and pressure (0 – 200 psi) gauge with 2½-inch dial may be supplied for in-line installation (shipped[...]

  • Page 9

    9 On/Off Switch A built-in non-fused On/Off disconnect switch may be supplied with the control panel to disconnect power to the control panel control and power circuit wiring. Individually Fused Ele me nts To prevent the possibility of damag e to circuits and elements in c ase of electrical overloa ds, fuses may be supplied for each circuit. Two ty[...]

  • Page 10

    10 SECTION II – INSTALLATION WARNING / CAUTION DO NOT TURN ON THE ELECTRI C POWER SUPPL Y to this equipment until heate r is completely filled with water and all air has been re leased. If the heater is NOT fille d with water when the power is turned on, the heating elements will burn out. For protection against excessive pressures and temperatur[...]

  • Page 11

    11 Outlet to floor drain Install into provided tapping Manual Release Lev e r Temperature Probe Temperature and Pressure Relief Valve 5. I nstall a relief valve overflow pipe to a nearby floor drain. CAUTION: No valve of any ty pe should be installed between the relief valve and tank or in the drain line. FILLING THE HEATER 1. Completely close the [...]

  • Page 12

    12 SECTION III - SCHEDULED MAINTE NANCE AND OPERATION WARNING / CAUTION Before performing any maintenance procedure, make certain power supply is OFF and cannot accidentally be turned on. MAINTENANCE AND OPERATION The water heater is automatic in its operation. I t will maintain a full tank of water at the temperature setting of the thermostat. The[...]

  • Page 13

    13 ANNUAL INSPECTION 1. Flush tank as follows a. Shut off power supply . b. Close valve on hot water outlet piping. c. Open valve on drain piping. d. Cold water inlet line pressure will be strong enough to flush sediment from the bottom of the tank out through the drain. L et water run for 3-4 minutes. e. Close drain valve. f. Open hot water valve.[...]

  • Page 14

    14 SECTION IV – TROUBLESHOOTING Symptom Probable Cause Corrective Action / Remedy Circuit breaker tripped at source. Reset circ uit breaker. On/Off switch in ‘OF F’ position, if installed. Turn switch to ‘ON’ position. Circuit breaker at control cabinet trippe d, if installed. Reset circ uit breaker. Blown fuse in element fuse block, if i[...]

  • Page 15

    15 Faulty thermostat. Chec k thermostat adjustment. Monitor thermostat as described in S e ct i o n III, Q u a rt e r l y In s p e c t i on. Replace if necessary. Blown fuse in element fuse block, if installed. Replace fuse. Heating element not worki ng on all phases Check to see th at heating element is working on all phases, by checking the resis[...]

  • Page 16

    16 SECTION V - SERVICING & REPLACEMENT OF PARTS WARNING / CAUTION Before servicing or replacing any part make sure to turn the power supply switch to the OF F position. SURFACE TEMPERATURE HIGH LIMIT CUT -OFF 1. Disconnect power from unit. 2. Remove access cover. 3. Disconnect the four (4) 14 gauge wires. Control Wires 4. Remove the two (2) mou[...]

  • Page 17

    17 IMMERSION TEMPERATURE HIGH L IMIT CUT-OFF 1. Disconnect power from unit. 2. Remove access cover. 3. Remove high limit c over screw and cover. Cover Cover Screw Reset Switch 4. Disconnect the two (2) 14 gauge wires. Wires Capillary Tube 5. Remove capilla ry tube a nd bulb from thermowell 6. Remove two (2) mounting screws. Mounting Screws 7. Remov[...]

  • Page 18

    18 HEATING ELEM ENT 1. Disconnect power from unit. 2. Shut off incoming water supply . 3. Attach hose to drain connection. 4. Lift manual release lever on relief valve to let air into sy stem or break union on outgoing water line. 5. Drain water from tank. 6. Disconnect the wires from the heating elem ent terminal s. 7. Remove the 3/8-16 nuts. Tank[...]

  • Page 19

    19[...]

  • Page 20

    20 SURFACE MOUNTED THE RMOSTAT 1. Disconnect power from unit. 2. Remove access cover and locate t hermostat. 3. Disconnect the two (2) 14 gauge wires. Control Wires 4. Remove two (2) mounting screws. Mounting Screws 5. Replace thermost at using the reverse procedure.[...]

  • Page 21

    21 IMMERSION THE RMOSTAT 1. Disconnect power from unit. 2. Remove access cover and locate t hermostat. 3. Remove high limit c over screw and cover. Cover Cover Screw 4. Disconnect the two (2) 14 gauge wires. Wires Capillary Tube 5. Remove capilla ry tube a nd bulb from thermowell. 6. Remove two (2) mounting screws. Mounting Screws 7. Replace thermo[...]

  • Page 22

    22 MAGNETIC CONTACTOR 1. Disconnect power from unit. 2. Disconnect line and load wires to contactor. 3. Disconnect two (2) 14 gaug e control circuit wires. Control Wires Line Wires Load Wires 4. Loosen two (2) holding screws and remove contactor. Mounting Screws (Bottom screw not shown) 5. Replace with new cont actor using reverse procedure.[...]

  • Page 23

    23 RELIEF VALVE 1. Disconnect power from unit. 2. Shut off incoming water supply . 3. Lift test lever on relief valve to relieve pressure in tank. 4. Disconnect overflow piping. 5. Unscrew relief valve, remove assemb ly and repl ace with new one. 6. Connect overflow piping. 7. Turn on incoming water supply and check for leaks. 8. Turn safety switch[...]

  • Page 24

    24 SECTION VI – MISCELL ANEOUS CHARTS AND FORMULAS ELEMENT CHA RT Resistance (Ohms) Element Part # I mmersion L ength Hairpin 1 Φ 3 Φ DELTA 3 Φ WYE 2-38683N 13" 57.6 19.2 57.6 38.6 3-38683N 13" 43.2 14.4 43.2 28.9 4-38683N 13" 34.4 11.5 34.4 23.0 5-38683N 13" 27.9 9.3 27.9 18.7 6-38683N 13" 21.6 7.2 21.6 14.5 7-38683N [...]

  • Page 25

    25 TORQUE VALUE S BOLT SIZE 18-8 S/S IN. - LB S . BRASS IN. - LB S . SI LI CON BRONZE IN. - LB S . ALUMI NUM 2024-T4 IN. - LB S . 316 S/S IN. - LB S . MONEL IN. - LB S . 4-40 5.2 4.3 4.8 2.9 5.5 5.3 4-48 6.6 5.4 6.1 3.6 6.9 6.7 5-40 7.7 6.3 7.1 4.2 8.1 7.8 5-44 9.4 7.7 8.7 5.1 9.8 9.6 6-32 9.6 7.9 8.9 5.3 10.1 9.8 6-40 12.1 9.9 11.2 6.6 12.7 12.3 8[...]