Fisher 244ER manual

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64

Go to page of

A good user manual

The rules should oblige the seller to give the purchaser an operating instrucion of Fisher 244ER, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.

What is an instruction?

The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of Fisher 244ER one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.

Unfortunately, only a few customers devote their time to read an instruction of Fisher 244ER. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.

What should a perfect user manual contain?

First and foremost, an user manual of Fisher 244ER should contain:
- informations concerning technical data of Fisher 244ER
- name of the manufacturer and a year of construction of the Fisher 244ER item
- rules of operation, control and maintenance of the Fisher 244ER item
- safety signs and mark certificates which confirm compatibility with appropriate standards

Why don't we read the manuals?

Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of Fisher 244ER alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of Fisher 244ER, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the Fisher service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of Fisher 244ER.

Why one should read the manuals?

It is mostly in the manuals where we will find the details concerning construction and possibility of the Fisher 244ER item, and its use of respective accessory, as well as information concerning all the functions and facilities.

After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.

Table of contents for the manual

  • Page 1

    Models 244EH and 244ER PC-Pr ogrammable T emperatur e Tr a n s m i t t e r s 00809- 0100-473 7 English Rev. EA P r o d u c t D i s c o n t i n u e d[...]

  • Page 2

    [...]

  • Page 3

    ¢00809-0100-4737f ¤ 00809- 0100-473 7 Rev EA 10/00 Product Manual Models 244EH and 244ER PC-Pr ogrammab le T emperature T ransmitter s Fisher-Rosemount satisfies all obligations coming from legislation to harmonise product requirements in the European Union. © Rosemount Inc., 2000 Rosmeount Inc. 8200 Market Boulev ard Chanhassen, MN 55317 USA T [...]

  • Page 4

    [...]

  • Page 5

    1 T able of Contents SECTION 1 Introduction S a f e t yM e s s a g e s ..................................... 1 - 1 Transmitter Overview ................................. 1 - 1 M a n u a lO v e r v i e w.................................... 1 - 2 C o n s i d e r a t i o n s ...................................... 1 - 3 G e n e r a l ... ..............[...]

  • Page 6

    Rosemount Models 244EH and 24 4ER PC-Prog ramma ble T emperature T ra nsmitters 2 APPENDIX A Reference Data Transmitter Speci fication ............................. A - 1 F u n c t i o n a l ....................................... A - 1 P e r f o r m a n c e ..................................... A - 2 P h y s i c a l ...............................[...]

  • Page 7

    Section 1-1 1 Intr oduction S a f e t yM e s s a g e s . ...... .......... .......... .....p a g e 1 - 1 T r a n s m i t t e rO v e r v i e w .... ....... ......... .........p a g e 1 - 1 M a n u a lO v e r v i e w .... ...... .......... .......... ..p a g e1 - 2 C o n s i d e r a t i o n s ... ...... .......... .......... .....p a g e1 - 3 SAFET Y[...]

  • Page 8

    Rosemount Models 244EH and 244ER PC-Pr ogrammable T emperature T ransmitters 1-2 MAN U AL OVERV IEW This manual i s design ed to assi st in the ins tallatio n, operat ion, and maintenance of Rosemoun t ® Model 244E H and 244ER PC Programma ble T emperature T ransmitters and the Mod el 244EC Configuration Interf ace. Section 2 : Installati on • T[...]

  • Page 9

    1-3 CONSIDERATIONS General El ectrical temperatu re sensors suc h as RTDs and thermocoup les produce low -level signals proportion al to their sensed temperature. The Models 244 EH and 244E R transmit ters convert the low-level s ensor signal t o a standard 4–20 mA d c signal that is relat ively inse nsitive t o lead lengt h and electrical noise.[...]

  • Page 10

    [...]

  • Page 11

    Section 2-1 2 Installation S a f e t yM e s s a g e s . ...... .......... .......... .....p a g e 2 - 1 T o o l sn e e d e df o r I n s t a l l a t i o n ........ .......... .....p a g e2 - 2 Mounting . .... ......... .......... ...... .........p a g e 2 - 3 I n s t a l l a t i o nP r o c e d u r e s ......... ...... .......... ..p a g e 2 - 5 F i [...]

  • Page 12

    Rosemount Models 244EH and 244ER PC-Pr ogrammable T emperature T ransmitters 2-2 Figur e 2-1. T ransm itte r Inst alla tion Fl owchar t TO O L S N E E D E D F O R INSTALLATION The too ls needed for installat ion are as follows : Begin Here T ransmitter Config ured? Configu re T ransmitter Set Sensor Ty p e Set Number of Wires Set 50/60 Hz Filter Se[...]

  • Page 13

    2-3 MOUNTING The Model 2 44EH instal ls in a connect ion head or unive rsal head mounted direct ly on a se nsor assembly , apart from a senso r assembl y using a universal head, or to a DIN rail using an op tional mount ing clip. The Model 24 4ER mounts direct ly to a wall or to a D IN rail. The Models 244EH and 244ER transmi tters wi ll operate w [...]

  • Page 14

    Rosemount Models 244EH and 244ER PC-Pr ogrammable T emperature T ransmitters 2-4 Special Mounting Considerations Special mounting hardware is ava ilable for mounting a Model 244EH head mount transmitter to a DIN rail, or assembling a new Mode l 244EH to an existing thre aded senso r connection he ad (former op tion code L1). Mounting a Model 244EH [...]

  • Page 15

    2-5 INSTALLATION PROCEDU RES T ransmitte r Refer to the appropri a te pr ocedure and the accompanyi ng illustrations when in stalling t he trans mitter . Head Mount T ransmitter with DIN Plate Style Sensor The leas t compli cated assembl y uses: • an integral mount sensor with flying leads • an integral DIN style conne ction head •a s t a n d[...]

  • Page 16

    Rosemount Models 244EH and 244ER PC-Pr ogrammable T emperature T ransmitters 2-6 Head Mount T ransmitter with Threaded Sensor The leas t compli cated assembl y uses: • a th readed sensor with flying leads • the universal connection head • a union and nipple exten sion assembly •a t h r e a d e d t h e r m o w e l l Refer to V olume 1 of the[...]

  • Page 17

    2-7 Rail Mount T r ansmitter with Integral Mount Sensor The leas t compli cated assembl y uses: • an integral mount sensor with terminal block • an integral DIN style conne ction head •a s t a n d a r d e x t e n s i o n •a t h r e a d e d t h e r m o w e l l Refer to V olume 2 of the Rosemount Sensors Product Data Sheet (document number 00[...]

  • Page 18

    Rosemount Models 244EH and 244ER PC-Pr ogrammable T emperature T ransmitters 2-8 Rail Mount T ransmitter with Threaded Sensor The leas t compli cated assembl y uses: • a threaded senso r with flying heads • a threaded sensor connection head • a union and nipple exten sion assembly •a t h r e a d e d t h e r m o w e l l Refer to V olume 1 of[...]

  • Page 19

    2-9 Multichannel Installations Several transmitters can be connected to a single master power supply as show n in Figure 2-9. In t his case, the sys tem may be gro unded only at the nega tive power supp ly terminal. In multichannel ins tallations where sev eral transmit ters dep end on one power supply and the los s of all tran smitters wo uld caus[...]

  • Page 20

    Rosemount Models 244EH and 244ER PC-Pr ogrammable T emperature T ransmitters 2-10 Choose the pro cedure that matche s the operating sys tem you are using . Pr ocedure for Windows 3.1 or Windo ws for W orkgroups 3.11 1. If y ou do not have Win32s inst alled, install it now . F ollow the instru ction s on th e disk ette lab el. 2. Inser t the Model s[...]

  • Page 21

    2-11 Screen Conventions The Models 244EH and 244ER Configuratio n Software follow s the Microsoft W indows screen conventions with the following exception: Configuration parameters change co l or to indicate fields where information has change d. Before placing a new transmitter into service, or before returning a transmitter to service after chang[...]

  • Page 22

    Rosemount Models 244EH and 244ER PC-Pr ogrammable T emperature T ransmitters 2-12 5. Turn on the Model 244EC usi ng the power s witch on th e top side of the housing . NO TE V erify that the Model 2 44EC “Low B attery” L ED is not on be fore initiating communication with the transmitter . If the low battery LED is on, you w ill not be ab le to [...]

  • Page 23

    2-13 Use th e followin g steps to wire the transmit ter: 1. Co nnect the posit ive lead fro m the power s upply to th e transmitt er terminal marked “ + ” and the n egative le ad to the transmi tter terminal marked “ – ” (see Figure 2-11 and Figure 2-13) . 2. Tighten the terminal compression s crews to ensure adequate contact. No addition[...]

  • Page 24

    Rosemount Models 244EH and 244ER PC-Pr ogrammable T emperature T ransmitters 2-14 Sensor Lead Wire Resist ance Effect RT D Input When using a 4-wire RTD, the effect of le ad resistan ce is eliminated and has no impact on accuracy . However , a 3-wire sensor will not fully cancel lead resistance error because it cannot compensate for imbalances in r[...]

  • Page 25

    2-15 •P t 1 0 0 2 - w i r e R T D : Lead wire resistance seen by the transmitter = 150 m × 2 wires × 0.025 Ω /m = 7 .5 Ω Thermocouple or Milli v olt Inputs F or integral mounting a pplications , the thermocouple can be connected directly to the trans mitter . If mounting the transmitte r remotely from the se nsor , use appropriate thermocou[...]

  • Page 26

    Rosemount Models 244EH and 244ER PC-Pr ogrammable T emperature T ransmitters 2-16 Figure 2 -13. T ransmitte r P ower , Sensor , and Configur ation T er minal s FA ILURE MODE The Models 24 4EH and 244 ER features software driven alarm diagnost ics and an independ ent circuit. Thes e features are designed t o provide separate backup alarm ou tput in [...]

  • Page 27

    Section 3-1 3 Operation S a f e t yM e s s a g e s . ...... .......... .......... .....p a g e 3 - 1 P ower Supply . . . . . . . . . . . . . .... ...... .......... ..p a g e 3 - 1 C o n f i g u r a t i o n . ...... .......... ......... .........p a g e3 - 2 I n t e r m i t t e n t S e n s o rA l g o r i t h m ......... ....... .....p a g e3 - 5 SAF[...]

  • Page 28

    Rosemount Models 244EH and 244ER PC-Pr ogrammable T emperature T ransmitters 3-2 Gr ounding T he transmitter will op erate with the current signal loop either floati ng or groun ded. However , the extra noise in f l oati ng systems affe cts many types o f readout devices. If the s ignal appe ars noisy or erratic, grounding the curre nt signal loop [...]

  • Page 29

    3-3 Configuring a Single T ransmitte r NOTE See “Confi guration Softw are” on page 2-9 for ins tructions on how to install the co nfiguration software. T o configure a sing le Model 244EH or 24 4ER transmitt er , perform th e follow ing procedure: 1. Dis connect powe r to the transmitter if the transmitte r is install ed in a meas urement loop [...]

  • Page 30

    Rosemount Models 244EH and 244ER PC-Pr ogrammable T emperature T ransmitters 3-4 NOTE Each configuration pa rameter is explained in detail in the on-line help provided with t he software. T o access hel p, clic k the HELP bu tton on the main config uration window (see Figure 3-1). 5. Cli ck the SEND TO XMTR button to upload configuration informatio[...]

  • Page 31

    3-5 Vie wing the Process Va r i a b l e With version 2.0 and la ter of the Model 244EC Conf iguration Interface, users can view the measured t emperature (PV) by selecting SER VIC E from the menu bar of the main configu ration window (see Figure 3-2). In order to view a valid PV , a temperature sensor must be connected to the Model 2 44E transm itt[...]

  • Page 32

    Rosemount Models 244EH and 244ER PC-Pr ogrammable T emperature T ransmitters 3-6 Case Ex amples Case 1: Ope n Sensor If the algor ithm detects an o pen senso r , the tran smitter immediat ely goes into al arm (high or low , de pending on the position of the failure mode switch) . Case 2: T empera ture Change Greater t han the Threshold V alue(2% of[...]

  • Page 33

    3-7 D) If an open se nsor is vali dated at the end of t he first update cyc le (Time = 500 ms), the output w ill go dire ctly to alarm level. T he original s pike (at Time = 0 ms) will not be seen at the outp ut. Case 3: T emper ature Ch ange Withi n the Threshold V alue (2 % of Range) If the transm itter detect s an input change t hat is wit hin t[...]

  • Page 34

    Rosemount Models 244EH and 244ER PC-Pr ogrammable T emperature T ransmitters 3-8 Figure 4-1 ill ustrates an example of intermittent se nsor detect w ith damping en abled. If the temp erature undergo es a step change greate r than the t hreshold val ue, or from 1 00 degrees to 11 0 degrees , and the damping is s et to 5.0 s econds, the transmit ter [...]

  • Page 35

    3-9 T r ansmitter Behavior with Intermittent S ensor Detect ON When the I nterm itten t Se nsor D etect featu re is switch ed ON , the transmi tter can elim inate the outp ut pulse caused by intermit tent open sensor conditio ns. Process t emperature changes ( ∆ T) w ithin 2% of the output range wi ll be tracked normally by the transmitter’s ou[...]

  • Page 36

    [...]

  • Page 37

    Section 4-1 4 Maintenance and T r oubleshooting S a f e t yI n f o r m a t i o n ... .......... ......... .........p a g e4 - 1 T r o u b l e s h o o t i n g .. ......... ....... .......... .....p a g e4 - 1 SAFETY INF ORMATION Procedures and instructions in t his manual may req uire spe cial precau tions to ensure the saf ety of the pers onnel pe [...]

  • Page 38

    Rosemount Models 244EH and 244ER PC-Pr ogrammable T emperature T ransmitters 4-2 The “Informa tion T ransmit ter UNSUCCESSFUL ” me ssage ap pears because the transmitter did not accept the change made in the Intermittent Sensor Det ect field. However , any other configuration changes sent at the same time as the Intermittent Sensor Direct chang[...]

  • Page 39

    Appendix A-1 Appendix A Reference Data T r a n s m i t t e rS p e c i f i c a t i o n ........ ...... .......... ..p a g e A - 1 O r d e r i n gI n f o r m a t i o n . ...... .......... .......... ..p a g eA - 6 D i m e n s i o n a lD r a w i n g s ... .......... .......... .....p a g e A - 9 T RANSMITTER SPECIFICATION Functional Inputs User select[...]

  • Page 40

    Rosemount Models 244EH and 24 4ER PC-Prog ramma ble T emperature T ra nsmitters A-2 Failure Mode The values that the tra nsmitter driv es its output to in fail ure mode depend on whether it is factory configure d t o standard or NAMUR-compli ant ope ration. The values for st andard and NAMUR-complia nt are as follow s: Humidity Limits 0 to 99% rela[...]

  • Page 41

    A-3 Accuracy When using a Pt 100 ( α = 0.00385) sensor inpu t with a 7 5 to 150 ° C range, the accuracy w ill be 0.05% o f span + 0. 15 °C or 0.20 °C , whichever is g reater . Sa mple Calculatio n:[0.0005 (1 50-75) + 0 .15] = 0.19 °C, which is less than 0. 20 °C, so the accuracy equals 0.20 °C . T ABLE A-2. Model 244E Input Option s and Acc [...]

  • Page 42

    Rosemount Models 244EH and 24 4ER PC-Prog ramma ble T emperature T ra nsmitters A-4 Ambient T emperature Effect Tr ansmitters can be installed in lo cations where the ambie nt temperature is between –40 a nd 85 °C (–40 and 185 °F). At the f actory , each transm itter is indivi dually charac terized ove r this ambient temperate rang e. This sp[...]

  • Page 43

    A-5 Ph ysical Electrical Connections Materials of Construction Mounting The Model 2 44EH instal ls in a connect ion head or unive rsal head mounted direct ly on a se nsor assembly , apart from a senso r assembl y using a universal head, or to a DIN rail using an op tional mount ing clip. The Model 244ER mo unts directly to a wall or to a DIN rail. [...]

  • Page 44

    Rosemount Models 244EH and 24 4ER PC-Prog ramma ble T emperature T ra nsmitters A-6 OR DERING INFORMATION T ABLE A-4. Model 244EH and 244ER T emperatu re T ransmit ter Ordering Inf ormation • = Av ailable — = Not availab le Model P roduc t Descrip tion Head Moun t Rail Mount 244E H Head Mo unt T emperat ure T ransm itter • — 244E R Rail Mou[...]

  • Page 45

    A-7 T ABLE A-5. Model 2 44EC Configur ation Interf ace Ordering Inf ormation • = Av ailable — = Not ava ilable Mode l Pro duct Descriptio n 244EH 244EC Model 244 EC Configu rati on Interf ace Hardw are and Soft ware • T ypic al Mode l Number: 244EC T ABLE A-6. T ransmit ter Accessories P art Descripti on Par t N u m be r Alumi num Allow Unive[...]

  • Page 46

    Rosemount Models 244EH and 24 4ER PC-Prog ramma ble T emperature T ra nsmitters A-8 Or dering Flameproof and Explosion-proof Appr ov als f or T emperature Assemblies Both flameproo f and explosio n-proof protection depe nd on the enclosure type . C ompliance with flameproof and ex plosion-proof approv als requires an appropriat ely appro ved assemb[...]

  • Page 47

    A-9 DIMENSIONAL DRAWINGS T ransmitte r Enc losure and Model 2 44EC Configuration Interface Model 244ER Model 244EH Shown with Standar d Compression Screw T erminals Shown w ith W AGO ® Spring Clamp T erminals Dimensions are in millimeters (inches) 36 (1.4) 104 (4.1) 82 (3.2) Sensor T erminals P ower T erminals 644-11 05E01A . 1101A01 A 644-136 0B0[...]

  • Page 48

    [...]

  • Page 49

    Appendix B-1 Appendix B Appr o v als S a f e t yM e s s a g e s . ...... .......... .......... .....p a g e B - 1 Hazardous Locations Installations . . . . . . . . . .... .....p a g eB - 1 L o c a t i o n s C e r t i f i c a t i o n s . ....... ......... .........p a g e B - 2 I n s t a l l a t i o nD r a w i n g s .... ....... ......... .........p[...]

  • Page 50

    Rosemount Models 244EH and 24 4ER PC-Prog ramma ble T emperature T ra nsmitters B-2 LOCATIONS CERTIFICATIONS Factory M utual (FM) Appro vals E5 Explosion-Proo f for Class I, Divisi on 1, Groups B , C , and D . Dust-Ignitio n Proof for Class II, Divi sion 1, Groups E, F , and G . Dust -Ign ition Proof f or Clas s II I, Divi sion 1 haz ardou s locat [...]

  • Page 51

    B-3 KEMA Approv als ED ATEX II 2 G Flameproof (Z one 1) (Model 244EH onl y) EEx d IIC T6 (T amb = –40 to 65 °C). NOTE: Flameproo f certificat ion is only ava ilable as a complete as sembly with Rosemount universal head – option codes J5 or J6. British Approv a ls Service for Electrical Equipment in Flammable Atmospheres (BA SEEF A) Appro vals [...]

  • Page 52

    Rosemount Models 244EH and 24 4ER PC-Prog ramma ble T emperature T ra nsmitters B-4 N7 Type N Approva l , Ex n IIC T5 (T amb = 70 °C) Special Conditions f or Safe Use ( X ): The assemb ly must be ins talled such that its external terminals and communication pins are protected to at least t he requirements of IP54. E7 Flameproo f Approv al (Model 2[...]

  • Page 53

    B-5 Figure B-1. Can adian Standards Associ ation (CSA) Intrinsic S afety Install ation Dra wing 0 0644-1064, Re v . AB[...]

  • Page 54

    Rosemount Models 244EH and 24 4ER PC-Prog ramma ble T emperature T ra nsmitters B-6 Figure B-2. Can adian Standards Associati on (CSA) Explosion-Pro of Install ation Dra wing 0 0644-1059, Re v . AA 644-1059A01A[...]

  • Page 55

    B-7 Figure B-3. F actor y Mutual (FM) Intrinsi c Safet y Install ation Dra wing 00644-00 09, Rev . AA 644-0009A01A[...]

  • Page 56

    Rosemount Models 244EH and 24 4ER PC-Prog ramma ble T emperature T ra nsmitters B-8 Figure B-4. F actor y Mutual (FM) Explosi on-Proof Installa tion Drawing 00644-10 49, Rev . AB 644-1049A01A[...]

  • Page 57

    Appendix C-1 Appendix C Models 644 and 244E T emperature T ransmitter s Manual Supplement O l dT r a n s m i t t e r ...... .......... ...... .......... ..p a g eC - 2 N e wT r a n s m i t t e r .. ......... ....... .......... .....p a g eC - 3 S p e c i f i c a t i o n s .... ......... .......... .......... ..p a g e C - 4 This manual supplement i[...]

  • Page 58

    Rosemount Models 244EH and 24 4ER PC-Prog ramma ble T emperature T ra nsmitters C-2 OLD T RANSMITTER OLD T RANS MITTER T rans mitter D esig n Sensor Wiring Diagrams Special Mounting Considerations Models 6 44H and 244 EH Models 644 R and 244 ER T wo Mou nting Ho les Models 644 a nd 244E * Rosemo unt In c. provides 4-w ire senso rs for all singl e e[...]

  • Page 59

    C-3 NEW T RANSMITTER NEW TRANSMITTER T rans mitter D esig n Sensor Wiring Diagrams Special Mounting Considerations HAR T Communicator (Model 644H only) T o guarante e proper trans mitter function ality and com municatio n, your Model 275 HAR T Communicato r should contai n device revisio n Dev v5 DD v2 or higher . T o check software device r evisio[...]

  • Page 60

    Rosemount Models 244EH and 24 4ER PC-Prog ramma ble T emperature T ra nsmitters C-4 SPECIFICATIONS Old New B ASEFF A (1) Int rinsically Safe Installa tion Entity Paramet ers: P ower Loop U max:in 30 V dc 3 0Vd c I max:in 200 mA 200 mA Group II C Zones 0 and 1 W max :in 1.0 W 1.0 W 0.67 W •T 5 ( – 4 0 ≤ T a ≤ 40 °C) • • T 5( –6 0 ≤ [...]

  • Page 61

    I-1 Inde x A Alarm see Failure mode Ambient Temper ature . . . . . . . . A-4 Approvals . . . . . . . . . . . . . . . . . B-1 C Changing Swi tch Positio ns . . . 2-16 Configura tion . . . . . . . . . . . . . . 3-2 244EC Interface Ambient temper ature . . A-5 Humidity limits . . . . . . A-5 Custom . . . . . . . . . . . . . . . A-8 Proces s vari able [...]

  • Page 62

    Rosemount Model 3244MV M ultiV ariable T emperature T ransmitter with Profibus-P A I-2 Wiring diagrams . . . . . . . . . . . . . 2-13 Sensors diagram . . . . . . . 2-15 terminal . . . . . . . . . . . . . . 2-16[...]

  • Page 63

    [...]

  • Page 64

    © Rosemount Inc., 2000 Rosemount Inc. 8200 Market Boule vard Chanhassen, MN 55317 USA T el 1-800-999-9307 F ax (952) 949- 7001 Fisher-Rosemou nt Limited Heath Place Bognor R egis West Sussex PO2 2 9SH England T el 44 (1243) 863 121 F ax 44 (1243) 867 5541 Fisher-Rosemou nt Singapore Pte Ltd. 1 P and an Crescent Singapore 128461 T el (65) 777-82 11[...]