American Water Heater 395T2506NOX manual

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32

Go to page of

A good user manual

The rules should oblige the seller to give the purchaser an operating instrucion of American Water Heater 395T2506NOX, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.

What is an instruction?

The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of American Water Heater 395T2506NOX one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.

Unfortunately, only a few customers devote their time to read an instruction of American Water Heater 395T2506NOX. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.

What should a perfect user manual contain?

First and foremost, an user manual of American Water Heater 395T2506NOX should contain:
- informations concerning technical data of American Water Heater 395T2506NOX
- name of the manufacturer and a year of construction of the American Water Heater 395T2506NOX item
- rules of operation, control and maintenance of the American Water Heater 395T2506NOX item
- safety signs and mark certificates which confirm compatibility with appropriate standards

Why don't we read the manuals?

Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of American Water Heater 395T2506NOX alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of American Water Heater 395T2506NOX, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the American Water Heater service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of American Water Heater 395T2506NOX.

Why one should read the manuals?

It is mostly in the manuals where we will find the details concerning construction and possibility of the American Water Heater 395T2506NOX item, and its use of respective accessory, as well as information concerning all the functions and facilities.

After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.

Table of contents for the manual

  • Page 1

    PRINTED IN THE U . S .A. 01 13 325257-000 SERVICING SHOULD ONL Y BE PERFORMED BY A QUALIFIED SERVICE TECHNICIAN Service Handbook COMMERCIAL GAS W A TER HEA TERS FOR MODELS: BCL 381T1206NOX, 381T1546NOX, 395T1806NOX, 395T1996NOX, 395T2506NOX UL TRA LOW NOx SERIES 104 INST ALLA TION CONSIDERA TIONS - PRE SERVICE CHECKS - CONSTRUCTION - OPERA TION &am[...]

  • Page 2

    [...]

  • Page 3

    1 Servicing should only be performed by a Qualied Service T echnician T ABLE OF CONTENTS INTRODUCTION ...................................................................... 2 QUALIFICA TIONS ..................................................................... 2 TOOLS REQUIRED .................................................................... [...]

  • Page 4

    2 Servicing should only be performed by a Qualied Service T echnician INTRODUCTION The service handbook is designed to aid in servicing and troubleshooting American W ater Heaters BCL commercial water heaters in the field. No duplication or reproduction of this book may be made without the express written authorization of American W ater Heaters[...]

  • Page 5

    3 Servicing should only be performed by a Qualied Service T echnician T OOLS REQUIRED • Electrical multimeter capable of measuring continuity/ ohms, ac & dc volts, amperes, microamperes, millivolts, and frequency (hz) • UEi Model DL289 or equivalent • Digital manometer + 60" w . c., resolution 0.01" increments Note: A digi[...]

  • Page 6

    4 Servicing should only be performed by a Qualied Service T echnician INST ALLA TION CONSIDERA TIONS GAS AND ELECTRICAL CHARACTERISTICS MODELS GAS TYPE GAS SUPPL Y PRESSURE VOL TS/HZ AMPERES MINIMUM MAXIMUM All Models Natural 3.5" WC (0.87 kPa) 14.0" WC (3.48 kPa) 120/60 < 5 All models require a minimum gas supply pressure of 3.5”[...]

  • Page 7

    5 Servicing should only be performed by a Qualied Service T echnician AIR SUPPL Y : Stoichiometric or theoretical complete combustion requires 10 cubic feet of air per 1,000 BTU of gas supplied. The National Fuel Gas Code also recommends an additional 2.5 cubic feet of “excess” air . For information on minimum make-up air opening sizes for v[...]

  • Page 8

    6 Servicing should only be performed by a Qualied Service T echnician MAKE-UP AIR – DIRECT COMMUNICA TION WITH OUTDOORS: A fresh supply of make-up air for combustion can be supplied to the water heater through make-up air ducts, which directly communicate with the outdoors. (Not Direct V ent.) T wo openings are required: one within 12 inches ([...]

  • Page 9

    7 Servicing should only be performed by a Qualied Service T echnician AIR REQUIREMENTS: For safe operation an adequate supply of fresh uncontaminated air for combustion and ventilation must be provided. An insufficient supply of air can cause recirculation of combustion products resulting in contamination that may be hazardous to life. Such a co[...]

  • Page 10

    8 Servicing should only be performed by a Qualied Service T echnician Upper Thermostat Probe/ECO Lower Thermostat Probe Control Box Assembly Drain V alve Gas Control V alve FEA TURES AND COMPONENTS Inlet T ube T & P Relief V alve Gas Control V alve Clean Out Cover The Eliminator Exhaust/V ent Outlet T ube[...]

  • Page 11

    9 Servicing should only be performed by a Qualied Service T echnician BLOWER AND BURNER ASSEMBL Y BURNER REPLACEMENT : 1. T urn off the gas supply and electricity to the water heater and remove the blower cover . 2. Disconnect the spark ignition cable and ground wire plus the flame sensor wire at their connection points on the flange plate. 3. D[...]

  • Page 12

    10 Servicing should only be performed by a Qualied Service T echnician 8. Support the blower and burner assembly in a vertical position with the burner extending downward. 9. Remove the 3 brass locknuts holding the blower adapter to the flange plate. 10. Separate the blower from the flange plate. 1 1. Clean the flange plate surfaces removing any[...]

  • Page 13

    11 Servicing should only be performed by a Qualied Service T echnician SP ARK IGNITER, FLAME SENSOR, SIGHT GLASS The spark igniter and the flame sense rod are shown below . Also shown is the burner sight glass. These features are typical for all models. SP ARK IGNITER / FLAME SENSOR / CONTROL TIMING SP ARK IGNITER This water heater is equipped w[...]

  • Page 14

    12 Servicing should only be performed by a Qualied Service T echnician VENTING INST ALLA TION – VENTING CA TEGOR Y AND MA TERIALS BCL VENTING Category I • Non-condensing, negative pressure in vent, below atmospheric. T ype venting • Must be installed Conventional V ent; uses room air for combustion and discharges flue gases to the outdoor [...]

  • Page 15

    13 Servicing should only be performed by a Qualied Service T echnician EXTERIOR CLEARANCES The illustration below shows the required clearances for venting units using natural draft venting. The vent must extend at least 3 feet above the highest point where it passes through a roof of a building and at least 2 feet higher than any portion of a b[...]

  • Page 16

    14 Servicing should only be performed by a Qualied Service T echnician VENTING T ABLES – TECHNICAL VENTING DA T A TYPE B GAS VENT Multiple Gas Fired T ank-T ype Heaters When venting multiple tank type heaters using T ype B vent pipe, follow the installation diagram and tables below which give sizing and data based upon NFP A 54 ANSI Z223.1. Mo[...]

  • Page 17

    15 Servicing should only be performed by a Qualied Service T echnician OPERA TION AND SERVICE SEQUENCE OF OPERA TION: 1. Switch power on to unit. 2. Thermostat calls for heat. 3. UGB (Universal Gas Board) sends PWM signal to blower to start the blower . 4. Blower runs at high prepurge speed for 20 seconds. 5. Combustion Blower initiates air flow[...]

  • Page 18

    16 Servicing should only be performed by a Qualied Service T echnician SEQUENCE OF OPERA TION – FLOW CHART Thermostat calls for heat Switch power on to unit Blower engages Prover Switch Aer 30 seconds, Ignion Control provides power to Spark Igniter and opens Gas Valv e Ignion Control maintains spark for up to 4 seconds and monitors Fl[...]

  • Page 19

    17 Servicing should only be performed by a Qualied Service T echnician LIGHTING AND OPERA TING LABEL S N O I T C U R T S N I G N I T A R E P O G N I T A R E P O E R O F E B D A E R Y T E F A S R U O Y R O F 1. 2. STOP! Read the safety information above on this label. Set the ON/OFF switch on the control box to the “OFF” position. 6. Tu rn on[...]

  • Page 20

    18 Servicing should only be performed by a Qualied Service T echnician TROUBLESHOOTING COMPLAINT CAUSE REMEDY USER QUALIFIED AGENCY *W ater not hot enough. Thermostat set too low . Set thermostat dial to a higher temperature Upper and/or lower temperature probe out of calibration. Call qualied agency . Check continuity and resistance (Ohms) o[...]

  • Page 21

    19 Servicing should only be performed by a Qualied Service T echnician CONTROLS OVER VIEW - CONTROL BOX ASSEMBL Y PRESSURE SWITCHES – ALL MODELS All BCL 120 thru 250 models are provided with one blower prover switch with +0.38" w .c. setpoint. The blower prover switch is provided on the heater to verify that the fan is operating. It is a [...]

  • Page 22

    20 Servicing should only be performed by a Qualied Service T echnician HIGH LIMIT SWITCH/ DIGIT AL THERMOST A T The digital thermostat contains the high limit (energy cut out) switch. The high limit switch interrupts burner gas flow should the water temperature reach 203°F (95°C). In the event of high limit switch operation, the water heater c[...]

  • Page 23

    21 Servicing should only be performed by a Qualied Service T echnician DISPLA Y LIGHTS – DIGIT AL THERMOST A T LED ST A TUS INDICA TION ACTION Calling for heat Normal status. No action required. The ECO (Energy Cut-Out) has opened. • Check for excessively hot water (203° F or higher). • Check the resistance of the temperature probes and c[...]

  • Page 24

    22 Servicing should only be performed by a Qualied Service T echnician CONTINUITY CHECK OF HIGH LIMIT (ECO) Continuity check of ECO (energy cut-out, high limit) Black to Black wires of upper probe. Power is off. IF ......... THEN............ Continuity is indicated (ZERO “0.0” Resistance) Opens at 203° F; closes at 193° F . If water is bel[...]

  • Page 25

    23 Servicing should only be performed by a Qualied Service T echnician UPPER TEMPERA TURE PROBE CONTINUITY CHECK OHMS RESIST ANCE T ABLE ° F OHMS 70° 1 1,884 120° 3,759 140° 2,488 180° 1,169 Upper T emperature Probe continuity check Red wire to red wire – T urn supply power "Off" for this test. IF ......... THEN............ T es[...]

  • Page 26

    24 Servicing should only be performed by a Qualied Service T echnician LOWER TEMPERA TURE PROBE CONTINUITY CHECK OHMS RESIST ANCE T ABLE ° F OHMS 70° 1 1,884 120° 3,759 140° 2, 488 180° 1, 169 Lower T emperature Probe continuity check Red wire to red wire – T urn supply power "Off" for this test. IF ......... THEN............ T [...]

  • Page 27

    25 Servicing should only be performed by a Qualied Service T echnician IGNITION CONTROL Each heater is equipped with an ignition control. The solid state ignition control, ignites the burner by utilizing a spark igniter . The spark igniter shuts of f during the heating cycle and the burner flame is sensed through a remote flame sensor . The igni[...]

  • Page 28

    26 Servicing should only be performed by a Qualied Service T echnician ST ART UP/ FLAME RECOVER Y/ SAFETY LOCKOUT ST ART UP - HEA T MODE When a call for heat is received from the thermostat supplying 24 volts to to UGB J5.6, the UGB will enable blower run at prepurge speed, which will cause the blower prover switch closing, and allow 24vac power[...]

  • Page 29

    27 Servicing should only be performed by a Qualied Service T echnician F AUL T CONDITIONS The water heater is equipped with an ignition control that incorporates a diagnostic system to assist in troubleshooting the appliance. The indicator codes on the ignition module are as follows: LED INDICA TION F AUL T MODE 2 Flashes Flame sensed without ca[...]

  • Page 30

    28 Servicing should only be performed by a Qualied Service T echnician UGB – BLOWER SPEED CONTROL The BCL 120 thru 250(A) models are equipped with a UGB PWM output control board for blower speed control. When the UGB J5.6 is energized by T -stat Call-for-heat, the UGB will provide 90% duty cycle PWM signal to the blower for 20 seconds prepurge[...]

  • Page 31

    29 Servicing should only be performed by a Qualied Service T echnician WIRING DIAGRAM[...]

  • Page 32

    COMMERCIAL GAS W A TER HEA TERS 30 Visit the "Information Central" link of www .americanwaterheater .com for a listing of available Service Handbooks. For additional information contact: American W ater Heaters PO Box 1597, 500 Princeton Road Johnson City , TN 37605 1-800-456-9805 www .americanwaterheater .com ©2013 American Water Heater[...]