AEG 8000012364 BAL manual

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42

Go to page of

A good user manual

The rules should oblige the seller to give the purchaser an operating instrucion of AEG 8000012364 BAL, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.

What is an instruction?

The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of AEG 8000012364 BAL one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.

Unfortunately, only a few customers devote their time to read an instruction of AEG 8000012364 BAL. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.

What should a perfect user manual contain?

First and foremost, an user manual of AEG 8000012364 BAL should contain:
- informations concerning technical data of AEG 8000012364 BAL
- name of the manufacturer and a year of construction of the AEG 8000012364 BAL item
- rules of operation, control and maintenance of the AEG 8000012364 BAL item
- safety signs and mark certificates which confirm compatibility with appropriate standards

Why don't we read the manuals?

Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of AEG 8000012364 BAL alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of AEG 8000012364 BAL, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the AEG service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of AEG 8000012364 BAL.

Why one should read the manuals?

It is mostly in the manuals where we will find the details concerning construction and possibility of the AEG 8000012364 BAL item, and its use of respective accessory, as well as information concerning all the functions and facilities.

After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.

Table of contents for the manual

  • Page 1

    Operating Instructions 8000012364 BAL, en Operating Instructions "UniVert 2" inverter and SBS option AEG Power Supply Systems GmbH Department: PPSD TED Name: Gleitsmann/Schenuit Revision: 01 Date: 06.08.2008[...]

  • Page 2

    "UniVert 2" inverter Page 2 of 42 8000012364 BAL, en Notes on these Operating Instructions Duty to Provide Information These operating instructions must be read carefully by all persons working with or on the inverter system prior to installation and initial start-up. These operating instructions are a composite part of the inverter syste[...]

  • Page 3

    "UniVert 2" inverter Page 3 of 42 8000012364 BAL, en Abbreviations The following abbreviations are used in these instructions: INV = Inverter SBS = Static Bypass Switch DOU = Display and Operation Unit SMPS = Switch Mode Power Supply PSM = Power Supply Monitoring Hotline Do you have any suggestions for improving these operating instructio[...]

  • Page 4

    "UniVert 2" inverter Page 4 of 42 8000012364 BAL, en Table of Contents Notes on these Operating Instructions ...........................................2 1 Safety Instructions!................................................................6 1.1 Important Instructions and Explanations ..................................6 1.2 Accident Preve[...]

  • Page 5

    "UniVert 2" inverter Page 5 of 42 8000012364 BAL, en 6 Maintenance .........................................................................29 7 Troubleshooting ...................................................................30 7.1 No Output Voltage or Output Current Present (with connected load) .......................................[...]

  • Page 6

    "UniVert 2" inverter Page 6 of 42 8000012364 BAL, en 1 Safety Instructions! 1.1 Important Instructio ns and Explanations The instructions for operation and maintenance, as well as th e following safety regulations must be complied with to ensure the safety of personnel as well as the availability of the unit. All personnel installing/dism[...]

  • Page 7

    "UniVert 2" inverter Page 7 of 42 8000012364 BAL, en 1.3 Danger during Maintenance and Repair Work CAUTION: The voltages applied to the INV can be fatal. Prior to start-up and/or maintenance work always disconnect the INV from the power supply and ensure that the unit cannot be switched on . The capacitors must be discharged. Free-standin[...]

  • Page 8

    "UniVert 2" inverter Page 8 of 42 8000012364 BAL, en 1.5 Safety Awareness The qualified personnel defined in chapter 1.4 are responsible for safety. They are also responsible for ensuring that only suitably qualified persons are permitted access to the IN V system or the safety area. The following points must be observed: All working proc[...]

  • Page 9

    "UniVert 2" inverter Page 9 of 42 8000012364 BAL, en 1.7 Liability No liability is accepted if the inverter system is used for applications not intended by the manufacturer. Any measures necessary for the prevention of injury, or damage to equipment is the responsibility of the operator or user. In the event of any claims in connection wi[...]

  • Page 10

    "UniVert 2" inverter Page 10 of 42 8000012364 BAL, en 2 General Information 2.1 System Description Depending on the system design, the following versions of safe AC power supply are possible (Figure 1): • Individual INV operation • Parallel operation of several INVs • Individual or parallel operation with SBS DC A C load INV = ~ Ind[...]

  • Page 11

    "UniVert 2" inverter Page 11 of 42 8000012364 BAL, en Individual INV operation: Here an INV is supplied with DC and itself supplies the AC load. In the event of INV fault or switch-off, the load is no longer supplied. Parallel INV operation: In order to increase redundancy or performance, up to 8 INVs of the same type and the same output [...]

  • Page 12

    "UniVert 2" inverter Page 12 of 42 8000012364 BAL, en Parallel INV operation: Prerequisite for parallel operation is that the INVs on the DC and AC side are connected in parallel, interconnected via CAN bus (16-pin, X7) and correctly addressed. The general behaviour of an individual INV is as described in the previous paragraph. The loads[...]

  • Page 13

    "UniVert 2" inverter Page 13 of 42 8000012364 BAL, en 2.3 Description of the INV Its electronic high-performance components make the INV suitable for universal applications. It has a very high degree of operational reliability, optimum efficiency and excellent communication capability with other systems thanks to integrated interfaces. Th[...]

  • Page 14

    "UniVert 2" inverter Page 14 of 42 8000012364 BAL, en Figure 2 illustrates the principle of a n INV. In normal operation, the load is supplied "Online" by the INV. With systems comprising several parallel INVs, the load current is divided in accordance with the number of INVs. Depending on the system design, a power supply using[...]

  • Page 15

    "UniVert 2" inverter Page 15 of 42 8000012364 BAL, en 2.5 Description of the SBS Its electronic high-performance components make the SBS highly overload-resistant and thus capable of quickly eliminating load short circuits. The SBS can be used as the central SBS for parallel operation of up to 8 INVs. Another outstanding characteristic of[...]

  • Page 16

    "UniVert 2" inverter Page 16 of 42 8000012364 BAL, en 2.6 Principle of Operatio n of the SBS, Electrical If the SBS is supplied by connecting the mains or the load voltage, the corresponding operating status is automatically activated after 3 to 5 seconds. With mains operation, the DOU displays load voltage and SBS current. With all other[...]

  • Page 17

    "UniVert 2" inverter Page 17 of 42 8000012364 BAL, en 3 Function of the Inverter For technical data or unit settings, refer to the Te chnical Data Sheet in chapter 8. 3.1 DC Input The inverter is operated with 48 V (or 60 V) DC voltage. The input voltage is fuse-protected outside the INV. For details, refer to the technical data. An integ[...]

  • Page 18

    "UniVert 2" inverter Page 18 of 42 8000012364 BAL, en 3.7 ON/OFF Switch The inverter is set ready for operation using the DOU switch on the front panel. The monitoring functions with their respective messages are only active when the inverter is switched on. After switch-off, all faults are acknowledged. The settings of the DIL switches a[...]

  • Page 19

    "UniVert 2" inverter Page 19 of 42 8000012364 BAL, en Switches S2.4, S2.5 and S2.6: Own Address (INV) The settings must be different on all INVs! Standard setting: Address 1: S2.4, S2.5 and S2.6 open S2.4 S2.5 S2.6 Address 1 0 0 0 Address 2 0 0 1 Address 3 0 1 0 Address 4 0 1 1 Address 5 1 0 0 Address 6 1 0 1 Address 7 1 1 0 Address 8 1 1[...]

  • Page 20

    "UniVert 2" inverter Page 20 of 42 8000012364 BAL, en 3.10 Signalling, Displays and Remote Signals The following signals are indicated via LEDs on the front panel: Display Colour Operating status Operation green INV operation U O OK green INV output voltage present U I < red Input voltage < 85% of rated voltage, INV has switched off[...]

  • Page 21

    "UniVert 2" inverter Page 21 of 42 8000012364 BAL, en 4 Function of the SBS (optional) For the technical data or unit settings, refer to th e chapter “Technical Data”. 4.1 Operating Statuses The following operating statuses are possible: "PowerUp": Status after PowerUp or Reset. The control system checks the ambient conditio[...]

  • Page 22

    "UniVert 2" inverter Page 22 of 42 8000012364 BAL, en 4.3 AC Mains Input (X1) The SBS is connected to a 230 V AC mains. The input voltage is fuse protected outside the S BS. For details refer to the technical data. The input voltage is continuously monitored (see chapter 4.4). When the mains voltage is present, the green "mains prese[...]

  • Page 23

    "UniVert 2" inverter Page 23 of 42 8000012364 BAL, en 4.10 CAN Bus Interfaces (X6, X7) The unit can be controlled and monitored via the 10-pin CAN bus connector X6, if the SBS is installed in a power supply cabinet with PSM control unit. The CAN bus connector X7 is always required for communication with the INV when operated with SBS. In [...]

  • Page 24

    "UniVert 2" inverter Page 24 of 42 8000012364 BAL, en Switches S3.7 and S3.8: number of redundant INVs S3.7 S3.8 0 INVs 0 0 1 INV 0 1 2 INVs 1 0 3 INVs 1 1 The settings must be the same on all INVs and the SBS! Standard setting: S3.7 and S3.8 open Switches S3.4 and S3.5: not used Switch S3.6: Switchover with gap (yes/no) Standard setting:[...]

  • Page 25

    "UniVert 2" inverter Page 25 of 42 8000012364 BAL, en With SBS ready: "U=230.0V" Load voltage " ready" Operating status With SBS blocked: "U=230.0V" Load voltage "blocked" Operating status With SBS Power Up: " " (nothing displayed) "PowerUp" Operating status With SBS fault: "[...]

  • Page 26

    "UniVert 2" inverter Page 26 of 42 8000012364 BAL, en Switchover with gap: The switchover from INV to SBS is carried out without interruption if the INV and SBS circuit are synchronous. If the INV and SBS circuit are not synchronous, the SBS does not block in this operating mode. If the INV is switched off due to asynchronism or if it fai[...]

  • Page 27

    "UniVert 2" inverter Page 27 of 42 8000012364 BAL, en 5 Start-Up 5.1 Installation When installing the INV, the following regulations must be observed: • The INV has been designed for use in a dry room, practically free of dust. • It is imperative to observe the specifications concerning ambient temperature and site altitude (see chapt[...]

  • Page 28

    "UniVert 2" inverter Page 28 of 42 8000012364 BAL, en Parallel INV operation: • Switch off the INV, switch on miniature circuit-breaker F1 • Set the DIL switches • Insert the AC fuses • Connect the DC supply • Switch on all INVs one after the other • (The output contactors K7 of the INVs start at the same time as soon as n-R I[...]

  • Page 29

    "UniVert 2" inverter Page 29 of 42 8000012364 BAL, en 6 Maintenance Attention! Disconnect the unit from the power supply prior to all maintenance work. Always observe the safety instructions! (See chapter 1.) The INV consists of state-of-the-art components which are almost non-wearing. We do, however, recommend regular visual and function[...]

  • Page 30

    "UniVert 2" inverter Page 30 of 42 8000012364 BAL, en 7 Troubleshooting Attention! All work on the unit may be carried out by specially trained qualified personnel only. Always observe the safety instructions! (See chapter 1.) 7.1 No Output Voltage or Output Current Present (with connected load) Individual INV operation: • DC present an[...]

  • Page 31

    "UniVert 2" inverter Page 31 of 42 8000012364 BAL, en 8 Technical Data 8.1 General Data INV DC input current ............................ < rated input current DC fuse required ........................... gL 80 A with type 3.3 kVA 48 V gL 63 A with type 3.3 kVA 60 V gL 20 A with type 3.3 kVA 220 V gL 80 A with type 1.5 kVA 24 V gL 36 A[...]

  • Page 32

    "UniVert 2" inverter Page 32 of 42 8000012364 BAL, en Messages ...................................... - Operation LED green - Output voltage ok LED green - Input undervoltage U E < LED red - Input overvoltage U E > LED red - Fault LED red - Overtemperature ϑ > LED red - Collective fault LED red Remote signals (X3) ..............[...]

  • Page 33

    "UniVert 2" inverter Page 33 of 42 8000012364 BAL, en Mechanical stability and vibration resistance ................. To VDE 0160 Version 5.88 Item 7.2.2 Surface painted with ...................... RAL 7032 (front panel) Dimensions (w x h x d) .................. 483 x 174 x 460 mm (19" x 4 height modules) (type 1.5 and 3.3 kVA) 483 x[...]

  • Page 34

    "UniVert 2" inverter Page 34 of 42 8000012364 BAL, en - Power cables ............................... Burst test in acc. with EN 61000-4-4, 2 kV Surge test in acc. with EN 61000-4-5, 2 kV asymmetrical - Control cables ............................. Burst test in acc. with EN 61000-4-4, 2 kV Surge test in acc. with EN 61000-4-5, 2 kV asymmet[...]

  • Page 35

    "UniVert 2" inverter Page 35 of 42 8000012364 BAL, en Protection class ............................. IP 20 Cooling .......................................... Forced air cooling Intake air temperature ................... At rated current 0°C to 45°C, measured below the SBS Storage temperature ...................... -20°C to +70°C Ambie[...]

  • Page 36

    "UniVert 2" inverter Page 36 of 42 8000012364 BAL, en 8.3 Electrical Data Typ e E-number G48 – 60 E230/14,4/2rfg-CFp3,3 3000000352 G220 E 230/14,4/2rfg-CFp3,3 300000601 Rated output capacity 3.3 kVA with power factor 0.8 Power factor range 0 inductive to 0 capacitive Rated output voltage 230 V ± 0.5 static, ± 3% dynamic at 100% load c[...]

  • Page 37

    "UniVert 2" inverter Page 37 of 42 8000012364 BAL, en Typ e E-number G48 – 60 E230/6,5/2rfg-CFp1,5 3000000351 G24 E230/6,5/2rfg-CFp1,5 3000000602 Rated output capacity 1.5 kVA with power factor 0.8 Power factor range 0 inductive to 0 capacitive Rated output voltage 230 V ± 0.5 static, ± 3% dynamic at 100% load ch ange Output frequency[...]

  • Page 38

    "UniVert 2" inverter Page 38 of 42 8000012364 BAL, en Typ e E-number G110 E230/10,9/2rfg-CFp2,5 3000000263 Rated output capacity 2.5 kVA with power factor 0.8 Power factor range 0 inductive to 0 capacitive Rated output voltage 230 V ± 0.5 static, ± 3% dynamic at 100% load ch ang e Output frequency 50 Hz ± 0.05% THD factor < 3% Rated[...]

  • Page 39

    "UniVert 2" inverter Page 39 of 42 8000012364 BAL, en Typ e E-number E230 E230/115/2-VFp26,5-8 3000000646 Rated output capacity 26.5 kVA Power loss < 200 W AC rated input voltage 230 V AC rated input frequency 50 Hz Monitoring system s AC mains undervoltage, blocking of the SBS Fault < 90% nominal (207 V), without delay Acknowledgem[...]

  • Page 40

    "UniVert 2" inverter Page 40 of 42 8000012364 BAL, en 9 Dimensional Dra wing Figure 6 Inverter dimensions (type 1.5 and 3.3 kVA)[...]

  • Page 41

    "UniVert 2" inverter Page 41 of 42 8000012364 BAL, en Figure 7 Inverter dimensions (type 2.5 kVA)[...]

  • Page 42

    "UniVert 2" inverter Page 42 of 42 8000012364 BAL, en Front vie w Rear vie w Air in let 483 7 PE connecti on X1, X2 X7 X6 X12 A ir ou tlet UniVert 2 460 11.5 37.7 101.6 177 (4 height mod. ) Figure 8 SBS dimensions[...]