Warning: mysql_fetch_array() expects parameter 1 to be resource, boolean given in /home/newdedyk/domains/bkmanuals.com/public_html/includes/pages/manual_inc.php on line 26
Emerson 250-400kVA manuale d’uso - BKManuals

Emerson 250-400kVA manuale d’uso

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72

Vai alla pagina of

Un buon manuale d’uso

Le regole impongono al rivenditore l'obbligo di fornire all'acquirente, insieme alle merci, il manuale d’uso Emerson 250-400kVA. La mancanza del manuale d’uso o le informazioni errate fornite al consumatore sono la base di una denuncia in caso di inosservanza del dispositivo con il contratto. Secondo la legge, l’inclusione del manuale d’uso in una forma diversa da quella cartacea è permessa, che viene spesso utilizzato recentemente, includendo una forma grafica o elettronica Emerson 250-400kVA o video didattici per gli utenti. La condizione è il suo carattere leggibile e comprensibile.

Che cosa è il manuale d’uso?

La parola deriva dal latino "instructio", cioè organizzare. Così, il manuale d’uso Emerson 250-400kVA descrive le fasi del procedimento. Lo scopo del manuale d’uso è istruire, facilitare lo avviamento, l'uso di attrezzature o l’esecuzione di determinate azioni. Il manuale è una raccolta di informazioni sull'oggetto/servizio, un suggerimento.

Purtroppo, pochi utenti prendono il tempo di leggere il manuale d’uso, e un buono manuale non solo permette di conoscere una serie di funzionalità aggiuntive del dispositivo acquistato, ma anche evitare la maggioranza dei guasti.

Quindi cosa dovrebbe contenere il manuale perfetto?

Innanzitutto, il manuale d’uso Emerson 250-400kVA dovrebbe contenere:
- informazioni sui dati tecnici del dispositivo Emerson 250-400kVA
- nome del fabbricante e anno di fabbricazione Emerson 250-400kVA
- istruzioni per l'uso, la regolazione e la manutenzione delle attrezzature Emerson 250-400kVA
- segnaletica di sicurezza e certificati che confermano la conformità con le norme pertinenti

Perché non leggiamo i manuali d’uso?

Generalmente questo è dovuto alla mancanza di tempo e certezza per quanto riguarda la funzionalità specifica delle attrezzature acquistate. Purtroppo, la connessione e l’avvio Emerson 250-400kVA non sono sufficienti. Questo manuale contiene una serie di linee guida per funzionalità specifiche, la sicurezza, metodi di manutenzione (anche i mezzi che dovrebbero essere usati), eventuali difetti Emerson 250-400kVA e modi per risolvere i problemi più comuni durante l'uso. Infine, il manuale contiene le coordinate del servizio Emerson in assenza dell'efficacia delle soluzioni proposte. Attualmente, i manuali d’uso sotto forma di animazioni interessanti e video didattici che sono migliori che la brochure suscitano un interesse considerevole. Questo tipo di manuale permette all'utente di visualizzare tutto il video didattico senza saltare le specifiche e complicate descrizioni tecniche Emerson 250-400kVA, come nel caso della versione cartacea.

Perché leggere il manuale d’uso?

Prima di tutto, contiene la risposta sulla struttura, le possibilità del dispositivo Emerson 250-400kVA, l'uso di vari accessori ed una serie di informazioni per sfruttare totalmente tutte le caratteristiche e servizi.

Dopo l'acquisto di successo di attrezzature/dispositivo, prendere un momento per familiarizzare con tutte le parti del manuale d'uso Emerson 250-400kVA. Attualmente, sono preparati con cura e tradotti per essere comprensibili non solo per gli utenti, ma per svolgere la loro funzione di base di informazioni e di aiuto.

Sommario del manuale d’uso

  • Pagina 1

    AC P ow er For Business-Criti cal C on tinuity™ Li eber t ® NXL ™ Operation and Mainte nance Manual – 250-400k V A, 60Hz, Three Phase Single-Module[...]

  • Pagina 2

    B ATTERY C ABINET P RECAUTIONS The following warning appl ies to all battery cabine ts supplied with UPS syst ems. Additional warn- ings and cautions applicab le to battery cabinets may be found in Important Safety Instru ctions and 3.4 - Battery Maintenance . Cont acting Liebert for Support Contact Emerson Network Power Liebert Services fo r infor[...]

  • Pagina 3

    i T ABLE OF CONTENTS B ATTERY C ABINET P RECA UTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 IMPORT ANT SAF ETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.0 I NTRODUCTI ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [...]

  • Pagina 4

    ii 3.2 Liebert Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 3.2.1 Professional Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 3.3 Routine Maintenance . . . . . . . . . . . . . . . . .[...]

  • Pagina 5

    iii FIGURES Figure 1 Typical UPS system one-line diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Figure 2 Main component locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Figure 3 Main Display Screen, typical . . . .[...]

  • Pagina 6

    iv[...]

  • Pagina 7

    1 I MPORT ANT S AFETY I NSTRUCTIONS SAVE THESE INSTRUCTIONS This manual co ntains important instructio ns that should be followed du ring installation and ma inte- nance of your Liebert NXL UPS and batteries. This equipment contains circuitry th at is energized with high vol tage. Only test equipment designated for troubleshooting shou ld be use d.[...]

  • Pagina 8

    Introd uction 2 1.0 I NTRODUCTION 1.1 General Description The Liebert NXL UPS provides continuous, high-qua lity AC power to your business-critical equip- ment, such as telecommunications and data proce ssing equipment. The Liebert NXL UPS supplies power that is free of the disturbances and vari ations in voltage and frequency common to utility pow[...]

  • Pagina 9

    Introd uction 3 1.2.2 Byp ass Mode When the Liebert NXL is in bypass mode, the load is directly supported by utility power and is with- out battery backup protection. The Liebert NXL’s inverter and bypass static switch wi ll shift the load from the inverter to bypass mode without an interruption in AC power if the inv erter is synchr onous with t[...]

  • Pagina 10

    Introd uction 4 • Load Bus Synchronization —The Load Bus Sync (LBS) option keeps two independent UPS sys- tems (and therefore their critical load buses) in sync, even when the modules are operating on bat- teries or asynchronous AC source s. This means that critical load s connected to both load buses can switch seamlessly between the two. • [...]

  • Pagina 11

    Operation 5 2.0 O PERATION The Liebert NXL UPS is equipped with a microprocessor-based displa y touchscreen de signed for con- venient and reliable operat ion. The display is driv en by an easy-to- follo w, menu-prompted software. 2.1 Features The Liebert NXL interface display enables the operator to perform such tasks as: • Quickly check operat [...]

  • Pagina 12

    Operation 6 Figure 3 M ain Display S creen, typica l Figure 4 Mimic display Bypass Input —Displays the bypass input voltage and the bypass input frequency. The bypass cir- cuit breaker (BFB) is to the right of this block. T he circuit breaker st atus is shown as open or closed. UPS Input Power —Displays the UPS input v oltage, current and frequ[...]

  • Pagina 13

    Operation 7 Figure 5 Monitor/mimic display example: N ormal power flow Figure 6 Monitor/mimic display example: U tility fail Green – Norma l Orange – Marginal Gray – Absent Black – Unknown Green – Normal Orange – Marginal Gray – Absent Black – Unknown[...]

  • Pagina 14

    Operation 8 Figure 7 Monitor/mimic display example: Load on byp ass, UPS On Figure 8 Monitor/mimic display example: Load on byp ass, UPS module off Green – Norma l Orange – Marginal Gray – Absent Black – Unknown Green – Norma l Orange – Marginal Gray – Absent Black – Unknown[...]

  • Pagina 15

    Operation 9 2.2 T ouchscreen Navigation 2.2.1 Main Display Screen Several menu items can be accessed fr om the main display screen (see Figure 3 ). These menu items are detailed in subsequent sections. Figure 9 Menu tree Li ebe rt N XL Me nu Help Menu Meterin g Silenc e Reset Conf igur at ions S t at us Report s Startup Shut down T ransf er B a tte[...]

  • Pagina 16

    Operation 10 2.2.2 Configurations Menu Rating This menu item will display a popup showing the following parameters (see Figure 10 ). These parameters are entered during commiss ioning when th e UPS is installed. Figure 10 Rating Parameters • Nominal Input Volta ge • Unit Model • Nominal Bypass Vol tage • Unit Serial • Nominal Output Volta[...]

  • Pagina 17

    Operation 11 User Settings System Settings These display se ttings can be change d from the to uchscreen. Press the box to the left of each parame - ter to bring a popup window that will al low the parameter to be changed. • Backlight Brightness—High or Low (default: Low) • Time (24hr format) —Adjust Hour, Minute or Seconds • Date (MM DD,[...]

  • Pagina 18

    Operation 12 Adjust able Setpoint s These warning and alarm settings can be changed fr om the touchscreen. Press the box to the left of each parameter to bri ng a popup wi ndow that will al low the parameter to be changed. Max Load Alarm • Phase A (%)—1 0% to 105% (default: 95%) • Phase B (%)—1 0% to 105% (default: 95%) • Phase C (%)—1 [...]

  • Pagina 19

    Operation 13 Battery Test • Auto Test—Enable/Disabl e (default: disabled) • Test Cycle, weeks—1 to 26 (default: 13 weeks) • Time of day, hh:mm—Set Hour and Minute; sets the start time of the automatic battery test • Start Date, mm dd, yyyyy—Set Month, Day and Year • Test Duration, minutes—Autom atic, 0.5 minut e to 30% of full l[...]

  • Pagina 20

    Operation 14 Event Management This menu item permits changing how the Liebert NXL handles Alar ms, Faults and Status informa- tion. Each event can be configured for the following: • Latch (yes/no)—Event stays active in the even t window, even if the fault condition has be en cleared, until user acknowledges it by pressing the “Reset” button[...]

  • Pagina 21

    Operation 15 2.2.5 Shut down Menu This menu permits shutting down the UPS and indiv idual devices. Figure 15 Shut down menu Open Trap —Open the input trap filter Open MBD/BCB —Opens the associated MBD or BCB breaker UPS —Turns off inverter, rectifier and trips all bat tery breakers. Transfers to bypass, if available. Figure 16 UPS shut down p[...]

  • Pagina 22

    Operation 16 2.2.6 T ransfer Menu This menu permits switching between UPS and Bypa ss mode. A graph in the multipurpose window shows if the UPS is in synch wi th the bypass. If the UPS and bypass are in synch, pressing Bypass will switch the UP S to Bypass mode. Pressing UPS will switch back to Norm al (Inverter) Mode (see Figure 18 ). Figure 18 T [...]

  • Pagina 23

    Operation 17 2.2.7 Battery Management Menu This menu permits configuring battery settings. Time Remaining Graph —Displays the time remainin g graph in the mu ltipurpose window; plot the battery voltage against elapsed time during a Battery Discharge Cycle (see Figure 19 ). Figure 19 Time remaining display Manual Battery Test —Start/Stop Manual [...]

  • Pagina 24

    Operation 18 Figure 20 Battery cycle monitor Display summary (see Figure 21 ) • Battery Commission Date/Time • Last Ba ttery Dis charge Date/ Time • Active Battery Discharge Time • Active Battery Amp Hours • Active Battery KW • Total Number of Discharges Figure 21 Battery cycle monitor summar y[...]

  • Pagina 25

    Operation 19 Clear Log —This command resets the Date of First Discharge Cycle. A di alog box will wa rn that the data will be permanently lost and shou ld downloaded before proceeding (see Figure 22 ). Figure 22 Battery cycle monitor—cle ar log 2.2.8 Metering This button will place the metering tables in the mult ipurpose window. 2.2.9 Help Thi[...]

  • Pagina 26

    Operation 20 2.3.2 OK to T ransfer The OK to Transfer st atus message will b e displa yed when the bypass line an d UPS output power are both available, their voltag e, frequency and phase synchronization are matched wi thin specifications, and the Static Switch Disconnects are closed (ON) . An alarm message may be displayed to indicate Load On Byp[...]

  • Pagina 27

    Operation 21 2.3.3 Input Power Failure—Load on Battery If the utility AC p ower source fails or is outside the acceptable range, the battery plant becomes the power source for the UPS module inverters. The UP S continues to supply po wer to the critical load and also to the UPS controls. Use the Battery Time screen at th e UPS modules to monitor [...]

  • Pagina 28

    Operation 22 2.3.4 Off Battery The battery plant can be disconnected from the UPS, if required for battery maintenance, by opening the module battery disconnect (MBD ) circuit br eaker. In this situat ion the UPS module will cont inue to supply conditioned powe r to the critical load, but if input power fail s the UPS system cannot supply power to [...]

  • Pagina 29

    Operation 23 2.3.6 Remote Emergency Power Off The Remote Emergency Powe r Off (REPO) mode will transfer the critical load to the bypass line and remove power from all UPS module components exce pt the controls, bypass circuit breaker and the static switch. The Remote Emergency Power Off control is a us er -provided switch located remotely from the [...]

  • Pagina 30

    Operation 24 2.4.1 St artup Procedure If your installat ion includes a Maintenance Bypass, you may already be sup p lying power to the criti- cal load equip ment through the Maintenan ce Bypass. If there is no power to the critical load, apply power through the UPS bypass line per the following procedure. During startup, power is suppl ied to the c[...]

  • Pagina 31

    Operation 25 e. The “Close CB1” message will appear. Close CB1 (see Figure 2 ) f. The “Press OK to Issue Rectifier On Command” message will appear. Press “OK” This will start th e UPS’ rectifier. Load is still on internal bypass. g. The “Press OK to Issue Inverter On Command” message ap pears. Press “OK” The motorized Mod ule [...]

  • Pagina 32

    Operation 26 2.4.2 Load T ransfer Procedures Changing the load from the UPS system to the UP S bypass is called a transfer. Chang ing the load from UPS bypass to the UPS system is called a retransfer. Note that the UPS system control logic can initiate automatic load transfer s and retransfers. Refer to 2.6 - Automatic Operations . T ransfer Proced[...]

  • Pagina 33

    Operation 27 NOTICE Risk of equipment damage. The UPS system must be on internal bypass before performing the followin g procedures and op erating MIB or MBB, or dama ge to the UPS may occur and the critical load may be lost. Maintenance Byp ass Load T ransfers—If Load is on UPS Byp ass 1. If the ma intenance bypass cabi net or switchboard has an[...]

  • Pagina 34

    Operation 28 2.5 Shut down Procedures 2.5.1 Module Shut down Procedure Perform a Module Shutdo wn Procedure when you want to remove power from a UPS module . Read all wa rnings in 3.0 - Maintenance before performing any main tenance on your Liebert NXL UPS. These warnings and cautions must be observed during any work on the UPS. Use the module Moni[...]

  • Pagina 35

    Operation 29 Figure 32 Current-versus-time cur ves of overload cap acity 2.6.2 Automatic T ransfers to Byp ass (Overload Conditi on) The UPS system wi ll initiate an au tomatic load transfer to the bypass line if a n overload condition exceeds the current-versus-ti me curve of overload capacity or if specified UPS system faults occur. Load On Byp a[...]

  • Pagina 36

    Operation 30 2.6.3 Automatic T ransfers to Byp ass, UPS System Fa ult s For specified UPS system faults, the control logic will initiate an automatic tran sfer to bypass fol- lowed immediately by a shutdown and isolation of the UPS system. The output, battery (MBD) and input circuit breakers are open. The bypass b reaker will be closed if the bypas[...]

  • Pagina 37

    Maintenance 31 3.0 M AINTENANCE 3.1 Safety Precautions Observe the safety precautions in Battery Cabinet Precautions inside the front cover. Observe ALL of the WARNING S be low before performing ANY main tenance on the UPS Syst em and associated equipment. Also observe the manufacture r’s safety precautions pe rtaining to the battery, along with [...]

  • Pagina 38

    Maintenance 32 3.2 Liebert Services Startup, UPS maintenance, battery maintenance and training progra ms are available for the Liebert NXL UPS through your Lieb ert sales representative. 3.2.1 Professional S t artup UPS Startup —Liebert’s Customer Engineers pe rform a thorough non-powered insp ection of the units and will then conduct a comple [...]

  • Pagina 39

    Maintenance 33 The UPS is designed for unattended operation, but does require some common-sense maintenance. • Keep good records —Troubl eshooting is easier if you have histori cal background. • Keep it clean —Maint ain the UPS free of dust and any moisture. • Keep it cool —Battery systems must be kept in the range of 72-77°F (22-26°C[...]

  • Pagina 40

    Maintenance 34 3.3.3 Limited Life Component s The Liebert NXL U PS has a design life well in excess of 10 years. Well-maint ained units can continue to provide economic benefits for 20 years or more. Long-life components are used in the UPS w herever practical and cost-effective. H owe ver, due to the currently availa ble component material, manufa[...]

  • Pagina 41

    Maintenance 35 3.4.1 Battery Safety Precautions Servicing of batteries should be performed or supe rvised by personnel know ledgeable of batte ries and the required precautions. Keep unauthorized person nel away from batteries. When replacing batteries, use the sa me number and type of batteries. Lead-acid batteries can present a ri sk of fire beca[...]

  • Pagina 42

    Maintenance 36 Because individu al battery characteri stics are not identical an d may change over time, the UPS mod- ule is equipped with circuitry to equalize battery cell voltages. This circuit increases charging voltage to maintain floode d type battery cells at full capacity. Matching Battery Cabinet s—Optional Although the individua l batte[...]

  • Pagina 43

    Maintenance 37 Rack-Mounted Batteries If the UPS system uses a battery other than a fa ctory-supplied Matchi ng Battery Cabinet, perform maintenance on the battery as recommended in the battery manuf acturer’s maintenance manual, available on the manufacturer’s Web site. 3.4.2 T orque Requirements All electric al connection s must be tight. Tab[...]

  • Pagina 44

    Maintenance 38 3.6 Reporting a Problem If a problem occurs within the UP S, review all alarm messages alon g with other pertinent data. Con- tact Liebert Services at 1-800-LIEBERT to report a problem or to request assistance. 3.7 Corrective Actions For each alarm message on the Display Screen, you can find the re commended corrective action in Ta b[...]

  • Pagina 45

    SPECIFICA TIONS 39 4.0 S PECIFICA TIONS 4.1 Battery Operation The separate battery manufacturer ’s manual, availabl e on the manufacturer’s Web site, provides the necessary informati on for the insta llation, operatio n and maintenance of the battery. Use the battery manual in conjunction with this manual. The float charge voltage for a battery[...]

  • Pagina 46

    SPECIFICA TIONS 40 T able 6 Electrical specifications Liebert NXL Model Size 250 300 400 Input Parameters Input Voltage to Rectifier, VAC 480V 3-phase, 3-wire Input Voltage to Bypass, VA C 480V 3-phase, 3- or 4-wire Permissible Input Voltage Range, VAC 70% to 110% Input Frequency, Hz 60 Permissible Input Frequency Range, Hz 55 to 65 Input THDi at n[...]

  • Pagina 47

    SPECIFICA TIONS 41 System Parameter UPS Efficiency AC-AC 100% Load, % 93.9% 94% 94.2% UPS Efficiency AC-AC 50 % Load, % 93.2% 93.3% 93.4% Physical Parameters & Standards, in (mm) Width 71.8 (1823) 78.5(1993) 78.5(1993) Depth 33.5 (850) 33.5 (850) 39.4 (1000) Height 76.8 (1950) Weight, lb (kg) approx. 4165 (1889) 4890 (2218) 5450 (2472) Color Ch[...]

  • Pagina 48

    SPECIFICA TIONS 42[...]

  • Pagina 49

    UPS Alarm and Status Messages 43 A PPENDIX A-U P S A LARM AND S TA T U S M ESSAGE S Table 7 shows alarm and status messages as they ap pear in Lieber t NXL’s touchscreen and in the history log, alon g with a descrip tion and recommend ed actions, if an y. If the recommended action fails to correct the condition , contact your factory-auth orized [...]

  • Pagina 50

    UPS Alarm and Status Messages 44 Batt Discharging The UPS is on battery. The most common reason for going to batte ry is a loss of rectifier input power (power outage). This alarm is self-clearing. When the condi tion is no longer present, the alarm and any con trol activity tied to the alarm reverts to normal. Press “SILENCE” to silence the au[...]

  • Pagina 51

    UPS Alarm and Status Messages 45 Batt Ovtemp Limit One or more of the Batte ry Temperature Sens ors is reporting a temper ature above the limit setpoint. There are tw o user-adjust able Battery Temperature Setpoints: Battery Over Temperature Warning an d Battery Overtemperature Limit. The temperature in one or more battery compartments has risen ab[...]

  • Pagina 52

    UPS Alarm and Status Messages 46 Batt Temp Imbalance With more than one Battery Temperature Sensor installed, the controls are detecting too great a temperature difference between the individual sensors. Press “SILENCE” to silence the audible alarm. To attempt to identify which sensor is reporting an inconsistent temperature or an overheating b[...]

  • Pagina 53

    UPS Alarm and Status Messages 47 Breaker Close Fail This is a summary event th at informs the user that a circuit breaker th at was either signaled to close or was manually closed failed to report a closed status. The Breaker Close Fail event indicates a mismatch between the expected state of a breaker and the reported state of the breaker. Press ?[...]

  • Pagina 54

    UPS Alarm and Status Messages 48 Byp Overload Ph C The critical load is greater than 110% whi le the UPS is on by pass. The c ontrols may shut the unit down if the overload condition doe s not clear within the allotted time. Allotted time is variable, and is inversely proportional to the amplitude of the overload, i.e., the grea ter the ampli tude [...]

  • Pagina 55

    UPS Alarm and Status Messages 49 Controls Comm Fail The Controls Communication Failure event indicates a lo ss of communications between the Controls and Human Machine Interface (HMI). The Controls Communicati on Failure event is displayed when the HMI detects a loss of communication w ith Cont rols on the Control ler Area Networ k (CAN). An infreq[...]

  • Pagina 56

    UPS Alarm and Status Messages 50 EPO Shutdown The UPS shuts down in response to an active Emergency Power Off (EPO) command. Press “SILENCE” to silence the audible alarm. Resolve the issue that precipitated the EPO. For safety, the UPS latches an EPO event. There are two ways to clear the latch: 1. Press the EPO Reset pushbutton on the External[...]

  • Pagina 57

    UPS Alarm and Status Messages 51 Equip Ovtemp Limit This summary event occurs when one or more internal temperatures have exceeded the maximum temp erature setpo int. This is the second of two over temperature alarms. The fi rst, “Equipment Overtemperature Warn ing,” sets when the detected temperature is near the limit. The control s react to t[...]

  • Pagina 58

    UPS Alarm and Status Messages 52 Excess Auto Rexfers The UPS has re-transferred too many times and is now locked on byp ass. The UPS attempts to perform an automatic transfer back to Inverter, if the reason for the transfer to bypass i s determined by the controls to be automatically recover able; for example, a temporary overload. The number of ti[...]

  • Pagina 59

    UPS Alarm and Status Messages 53 Inp Phase Rotation The correct input phase rotation should be clockwise, or A-B-C. This alarm in dicates the sensed input phase rota tion is counter-clockwise. If this alarm occurs on an operational u nit, it typically indicates upstream work was performed (input side) an d the input wiring was connected incorrectly[...]

  • Pagina 60

    UPS Alarm and Status Messages 54 Input Current Limit An active Input Curre nt Limit alarm means the detected input current (RMS) exceeds the limit setpoint (default is 125%). Th is may be normal depending on various operating condi tions, such as input voltage level, output load level, and whether the batteries ha ve recently di scharged. This alar[...]

  • Pagina 61

    UPS Alarm and Status Messages 55 Inv Overload Ph B An overload conditio n is active on B phase. B phase load condi tion exceeds 105%. A countdown timer is displayed on the One-Lin e Display in response to this alarm, and ind icates the time remaining until a transfer to bypass occurs. The length of time remaining until transfer is directly proporti[...]

  • Pagina 62

    UPS Alarm and Status Messages 56 LBS Inhibited With LBS operation enabled, conditions requ ired to allow LBS operation are no t met. Voltage or Frequency diff eren ces sensed by the LBS control are preventing the ability of LBS to function correctly. This alarm is self-clearing. When the condi tion is no longer present, the alarm and any con trol a[...]

  • Pagina 63

    UPS Alarm and Status Messages 57 Low Power Factor The outpu t power factor is low. The output power factor is less than 70% leading or lagging. A simplified explana tion of power factor is the ratio of energy being supplied to energy being used by the load. For a given load, the current output of the UPS goes up as power factor decreases. This resu[...]

  • Pagina 64

    UPS Alarm and Status Messages 58 Manual Xfer Inhibi t This summary event means the conditions required to perfo rm a manual transfer to bypass are not met (Inverter must be in sync with bypass). This status message is se lf-clearing. When the condition is no longer present, the message and any control activity tied to th e status event reverts to n[...]

  • Pagina 65

    UPS Alarm and Status Messages 59 Multiple Fan Fa il This summary event is active when more than one fan has failed. Press “SILENCE” to silence the audible alarm. Press “RESET” to clear the alarm. If the alar m will not cl ear, contact yo ur factory- authorized service provider. On Gen Active The UPS input source i s generator. An external s[...]

  • Pagina 66

    UPS Alarm and Status Messages 60 Rectifier Fa ult This summary event indicates a potentially serious condition in the Rectifie r circuit. The controls respond to this by turning off the Rectifier, opening th e input filter contactor, and placing the UPS on battery operation. This fault is non-latching . When the underlying condition is no longer pr[...]

  • Pagina 67

    UPS Alarm and Status Messages 61 Regen Terminate d Regeneration Mode is a service mode that is normally controlled by the service technician. Regeneration Mode Status or Alarm messages are generally intended for the se rvice person. This status message informs the user that Regen Mode is no longer active. This status message is se lf-clearing. When[...]

  • Pagina 68

    UPS Alarm and Status Messages 62 Service Code Active This event is for info rmational pu rposes, and informs the user that Service Code is currently running. This status message is se lf-clearing. When the condition is n o longer present, the a larm and any control activity tied to the alarm reverts to normal. Under normal circumstances, none. If t[...]

  • Pagina 69

    UPS Alarm and Status Messages 63 NOTES[...]

  • Pagina 70

    UPS Alarm and Status Messages 64[...]

  • Pagina 71

    [...]

  • Pagina 72

    EmersonNetworkPower.com Ensuring The Hi gh Av ai lab ilit y 0f Mission-Critic al Dat a And App lic ations. Emerson Net work P ower , the global leader in enabling business-critical continuity , ensures network resilienc y and adaptability through a family of technologies—inc luding Liebert power and cooling technologies—that prot ect and suppor[...]