Emerson 300510EN Bedienungsanleitung

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246

Zur Seite of

Richtige Gebrauchsanleitung

Die Vorschriften verpflichten den Verkäufer zur Übertragung der Gebrauchsanleitung Emerson 300510EN an den Erwerber, zusammen mit der Ware. Eine fehlende Anleitung oder falsche Informationen, die dem Verbraucher übertragen werden, bilden eine Grundlage für eine Reklamation aufgrund Unstimmigkeit des Geräts mit dem Vertrag. Rechtsmäßig lässt man das Anfügen einer Gebrauchsanleitung in anderer Form als Papierform zu, was letztens sehr oft genutzt wird, indem man eine grafische oder elektronische Anleitung von Emerson 300510EN, sowie Anleitungsvideos für Nutzer beifügt. Die Bedingung ist, dass ihre Form leserlich und verständlich ist.

Was ist eine Gebrauchsanleitung?

Das Wort kommt vom lateinischen „instructio”, d.h. ordnen. Demnach kann man in der Anleitung Emerson 300510EN die Beschreibung der Etappen der Vorgehensweisen finden. Das Ziel der Anleitung ist die Belehrung, Vereinfachung des Starts, der Nutzung des Geräts oder auch der Ausführung bestimmter Tätigkeiten. Die Anleitung ist eine Sammlung von Informationen über ein Gegenstand/eine Dienstleistung, ein Hinweis.

Leider widmen nicht viele Nutzer ihre Zeit der Gebrauchsanleitung Emerson 300510EN. Eine gute Gebrauchsanleitung erlaubt nicht nur eine Reihe zusätzlicher Funktionen des gekauften Geräts kennenzulernen, sondern hilft dabei viele Fehler zu vermeiden.

Was sollte also eine ideale Gebrauchsanleitung beinhalten?

Die Gebrauchsanleitung Emerson 300510EN sollte vor allem folgendes enthalten:
- Informationen über technische Daten des Geräts Emerson 300510EN
- Den Namen des Produzenten und das Produktionsjahr des Geräts Emerson 300510EN
- Grundsätze der Bedienung, Regulierung und Wartung des Geräts Emerson 300510EN
- Sicherheitszeichen und Zertifikate, die die Übereinstimmung mit entsprechenden Normen bestätigen

Warum lesen wir keine Gebrauchsanleitungen?

Der Grund dafür ist die fehlende Zeit und die Sicherheit, was die bestimmten Funktionen der gekauften Geräte angeht. Leider ist das Anschließen und Starten von Emerson 300510EN zu wenig. Eine Anleitung beinhaltet eine Reihe von Hinweisen bezüglich bestimmter Funktionen, Sicherheitsgrundsätze, Wartungsarten (sogar das, welche Mittel man benutzen sollte), eventueller Fehler von Emerson 300510EN und Lösungsarten für Probleme, die während der Nutzung auftreten könnten. Immerhin kann man in der Gebrauchsanleitung die Kontaktnummer zum Service Emerson finden, wenn die vorgeschlagenen Lösungen nicht wirksam sind. Aktuell erfreuen sich Anleitungen in Form von interessanten Animationen oder Videoanleitungen an Popularität, die den Nutzer besser ansprechen als eine Broschüre. Diese Art von Anleitung gibt garantiert, dass der Nutzer sich das ganze Video anschaut, ohne die spezifizierten und komplizierten technischen Beschreibungen von Emerson 300510EN zu überspringen, wie es bei der Papierform passiert.

Warum sollte man Gebrauchsanleitungen lesen?

In der Gebrauchsanleitung finden wir vor allem die Antwort über den Bau sowie die Möglichkeiten des Geräts Emerson 300510EN, über die Nutzung bestimmter Accessoires und eine Reihe von Informationen, die erlauben, jegliche Funktionen und Bequemlichkeiten zu nutzen.

Nach dem gelungenen Kauf des Geräts, sollte man einige Zeit für das Kennenlernen jedes Teils der Anleitung von Emerson 300510EN widmen. Aktuell sind sie genau vorbereitet oder übersetzt, damit sie nicht nur verständlich für die Nutzer sind, aber auch ihre grundliegende Hilfs-Informations-Funktion erfüllen.

Inhaltsverzeichnis der Gebrauchsanleitungen

  • Seite 1

    www .rosemount-tg.com System Configuration Manual 300510EN, Rev AA December 2010 Raptor T ank Gauging System[...]

  • Seite 2

    [...]

  • Seite 3

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor www .rosemount-tg.com Rosemount Raptor Configuration with Rosemount T ankMaster WinSetup Cover Photo: system_config_fr ont.tif NOTICE Read this manual before working with t he produ ct. For personal and system safety , and for optimum product performance, make sure you thor[...]

  • Seite 4

    [...]

  • Seite 5

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor www .rosemount-tg.com T able of Content s SECTION 1 Introduction 1.1 Manual Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 1.2 Technical Document ation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2 SECTION 2 Rapt[...]

  • Seite 6

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor TOC -2 Table of Contents 5.3 Preferences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-16 5.3.1 Measurement Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-16 5.3.2 Ambient Air Temperature . . . . . . . . . . . . . . . .[...]

  • Seite 7

    System Configuration Manual 300510EN, Rev AA December 2010 TOC -3 Rosemount Raptor Table of Contents SECTION 6 Device Handling 6.1 To Change Device Configuration . . . . . . . . . . . . . . . . . . . . . . . . . 6-1 6.2 To Uninstall a Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3 SECTION 7 Service Functions 7.1 Sy[...]

  • Seite 8

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor TOC -4 Table of Contents[...]

  • Seite 9

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor www .rosemount-tg.com Section 1 Introduction 1.1 Manual Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . p age 1- 1 1.2 T echnical Documentation . . . . . . . . . . . . . . . . . . . . page 1-2 This manual describe s the recommended inst allation procedure for[...]

  • Seite 10

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 1-2 Section 1. Introducti on Section 7: Service F unctions A description of var ious functions su pported by T ankMaster WinSetup fo r service and maintenance of dif f erent Rapto r field devices. Section 8: Menu Guide A guide to menus and menu options in the T ankMaster Wi[...]

  • Seite 11

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor www .rosemount-tg.com Section 2 Raptor System Overview Raptor is a state-of-the art inventory and custody transfer radar t ank level gauging system. It is developed for a wide range of app lications at refineries, tank farms and fuel depots, and fu lfills the highest requir[...]

  • Seite 12

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 2-2 Section 2. Raptor System Overview Figure 2- 1. Raptor sy stem architecture 2230 Display 2240S T emperatu re T ransmitter 5900S Radar Level Gauge 2410 T ank Hub Ta n k b u s 5300 Level T ransmitter 5400 Level T ransmitter 3051S Pressure T ransmitter TRL2 Modbus Group bus[...]

  • Seite 13

    System Configuration Manual 300510EN, Rev AA December 2010 2-3 Rosemount Raptor Section 2. Raptor System Overview T ankMast er HMI Software T ankMaste r is a powerful Windows-based Human Machine Interface (HMI) fo r complete tank inve ntory management. It provides configuration, service, set-up, inventory , and custody transfer functio ns for Rapto[...]

  • Seite 14

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 2-4 Section 2. Raptor System Overview Rosemount 5300 Guided W ave Radar The Rosem ount 5300 is a premium 2 -wire guided wave radar f or level measurement s on liquids, to be used in a wide range of medium accuracy applications under vario us tank cond itions. Rosemount 53 0[...]

  • Seite 15

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor www .rosemount-tg.com Section 3 Using T ankMaster 3.1 What is T ankMaster? . . . . . . . . . . . . . . . . . . . . . . . . p age 3-1 3.2 T ankMaster Sof tware Package . . . . . . . . . . . . . . . . page 3-2 3.3 Inst alling the T ankMaster Sof tware . . . . . . . . . . . . [...]

  • Seite 16

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 3-2 Section 3. Using TankMaster 3.2 T ANKMASTER SOF TWARE PACKAGE Rosemount T ankMaster includes several software modules: •W i n O p i •W i n S e t u p • T ank Server • Master Protocol Servers • Slave Protoc ol Server • Batch Server • Administrator Figure 3-1[...]

  • Seite 17

    System Configuration Manual 300510EN, Rev AA December 2010 3-3 Rosemount Raptor Section 3. Using TankMaster The Master Protocol Ser ver transfers configuration data and measured data between the T a nk Server and connected devices in a Rosemount T ank Gauging system. The Master Protocol Server is able to communicate with various types of field de v[...]

  • Seite 18

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 3-4 Section 3. Using TankMaster 3.3 INST ALLING THE T ANKMASTER SOF TWARE 3.3.1 System Requirement s The following system specification is recomme nded to run T ankMaster version 5.B0 or higher (1) : NOTE A hardware key is not required to run WinSetUp. 3.3.2 Inst alled Sof [...]

  • Seite 19

    System Configuration Manual 300510EN, Rev AA December 2010 3-5 Rosemount Raptor Section 3. Using TankMaster 3.3.3 Inst allation Procedure T o install the T ankMa ster soft ware package do the following: 1. Insert the T ank Master CD-ROM. The installa tion wizard starts automatically and the T ankMaster inst allation CD start-up screen appears: NOTE[...]

  • Seite 20

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 3-6 Section 3. Using TankMaster 3.4 INST ALLING A T ANK LEVEL GAUGING SYSTEM Setting up a T ank Level Gauging system comprises installation an d configuration of devices and tanks. T ank inst allation T ank installation includes specifying t ank type, specifying transmitter[...]

  • Seite 21

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor www .rosemount-tg.com Section 4 The WinSetup Main W indow 4.1 Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p age 4-3 4.2 T oolbar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-4 4.3 St atus bar . . . . . . . [...]

  • Seite 22

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 4-2 Section 4. T he WinSet up Main Wind ow The Workspace window can be moved anywhere on the Main window . It can be docked to either side of the Main window , or it can be left floating. Figure 4-3. The WinSetup workspace Right click in the Workspace window and choos e All[...]

  • Seite 23

    System Configuration Manual 300510EN, Rev AA December 2010 4-3 Rosemount Raptor Section 4. The WinSetup Main Window 4.1 MENUS The menu bar at the to p of the screen contain s menus such as File , Vie w , Service , To o l s , and Help. Figure 4-4. The WinSetup menu Service menu o ptions are also availabl e by clicking the right mouse button. Diffe r[...]

  • Seite 24

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 4-4 Section 4. T he WinSet up Main Wind ow 4.2 T OOLBAR The toolbar provides butto ns acting as shortcuts to certain menu options. Normally the T oolbar is visible. T o hi de it, open the View menu an d deselect the T oolbar option: Figure 4-7. The WinSetup T oolbar The fol[...]

  • Seite 25

    System Configuration Manual 300510EN, Rev AA December 2010 4-5 Rosemount Raptor Section 4. The WinSetup Main Window 4.3 ST ATUS BAR The status bar is located at the bo tt om of the T ankMaster main window . It provides general in formation about the current system state. Normally , th e T ankM aster status bar is visible. T o hide it, open the Vie [...]

  • Seite 26

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 4-6 Section 4. T he WinSet up Main Wind ow 4.4 WORKSP ACE - VIEWING T ANKS AND DEVICES The worksp ace displays an overview of all devices and t anks. Y ou can switch between two dif ferent views: Logical and Physical view . Figure 4- 10. The Win setup workspace Lo gical and[...]

  • Seite 27

    System Configuration Manual 300510EN, Rev AA December 2010 4-7 Rosemount Raptor Section 4. The WinSetup Main Window 4.4.1 Worksp ace The Workspace window shows the installed tanks and devices and availa ble communication protocols. It a lso provides information about the configuration of installed devices. Ex.1 In the Logical View all installed tan[...]

  • Seite 28

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 4-8 Section 4. T he WinSet up Main Wind ow 4.4.2 Icons In the Workspace windo w the different t anks and devices are represented by the following icons: Rosemount 2410 T ank Hub Rosemount 2410 T ank Hub (Simulatio n Mode) Rosemount 5900S Radar Level Gauge Rosemount 5400 Ser[...]

  • Seite 29

    System Configuration Manual 300510EN, Rev AA December 2010 4-9 Rosemount Raptor Section 4. The WinSetup Main Window 4.5 USER MANAGEMENT T ankMaster provides several protection levels allowing you to preven t unauthorized changes. These protection levels are categorized as User Access Levels and User Sub Access Levels . The User Access Levels are Ch[...]

  • Seite 30

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 4-10 Section 4. T he WinSet up Main Wind ow 4.5.1 Logging On to T ankMaster 1. From the File menu choose Log On or click the Log On button in the WinSetup toolbar . 2. T ype your Username and Passwor d. The password is case sensitive but the username is not. NOTE! If loggin[...]

  • Seite 31

    System Configuration Manual 300510EN, Rev AA December 2010 4-1 1 Rosemount Raptor Section 4. The WinSetup Main Window 4.5.2 T o Administrate User Account s T ankMaster allows you to setup a number of users at dif ferent levels and sub levels. Y ou must be logged on as an Administr ator in order to add new user accounts or to change the existing use[...]

  • Seite 32

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 4-12 Section 4. T he WinSet up Main Wind ow 6. Check that the new user appears in the User Manager window . Select the “Use first account...” box if you want a default user name to appear in the Log On dialog wh enever it is opened. If this box is unmarked the User Name[...]

  • Seite 33

    System Configuration Manual 300510EN, Rev AA December 2010 4-13 Rosemount Raptor Section 4. The WinSetup Main Window 4.5.3 T o Set Required Access Levels In T ankMaster WinSetup, you can set the access level requir ed for the following actions: • T ank/Device Install and Uninstall • T ank/Device Configuration • Replace, Restore and Rest art D[...]

  • Seite 34

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 4-14 Section 4. T he WinSet up Main Wind ow 4.5.4 T o Change Protection Level of Sep arate Windows In T ankMaster it is possible to set a Protection Level for a specific window , e.g. the Properties win dow for a Rosemount 5900S Radar Level Gauge. This function is only avai[...]

  • Seite 35

    System Configuration Manual 300510EN, Rev AA December 2010 4-15 Rosemount Raptor Section 4. The WinSetup Main Window 4.5.5 T o Change Password T ankMaster allows you to change your password at any time: 1. From the T o ols/Admini strative T ools menu choose the Set Passwor d option. 2. Select the T ankServer on which your user account is valid. Y o[...]

  • Seite 36

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 4-16 Section 4. T he WinSet up Main Wind ow 4.5.6 T o Change Inactivity Timeout T ankMaster WinSetup incl udes the optio n to set a timeout after which the current user is automatically logged of f. The timeout period is reset each time the user performs an activity that re[...]

  • Seite 37

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor www .rosemount-tg.com Section 5 Inst alling a Raptor Level Gauging System 5.1 System Configuration Overview . . . . . . . . . . . . . . . page 5-2 5.2 Communication Protocol Setup . . . . . . . . . . . . . . . page 5-6 5.3 Preferences . . . . . . . . . . . . . . . . . . . .[...]

  • Seite 38

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-2 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.1 SYSTEM CONFIGURATION OVERVIEW 5.1.1 Prep arations Before installing a Rosemount T ank Gaug ing system you shou ld ensure that the following information is available: • A plan of all field devices and tanks. •[...]

  • Seite 39

    System Configuration Manual 300510EN, Rev AA December 2010 5-3 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System Figure 5-1. Raptor system installation procedu re GROUP BUS FIELD BUS Rosemount 2410 Ta n k H u b Rosemount 2160 Field Communication Un it Plant Host Computer T ank Master workst attion Rosemount 2180 Field Bus Modem [...]

  • Seite 40

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-4 Section 5. Installing a Ra ptor Level Gauging Sy stem 4 Inst allation and Configuration of Ros emount 2410 T ank Hub The Rosemount 2410 sh ould be installed af ter the Rosemount 2160 Field Communication Unit. In case the Rosemount 2410 is connected dir ectly to a T ankM[...]

  • Seite 41

    System Configuration Manual 300510EN, Rev AA December 2010 5-5 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.1.3 Using the Device Inst allation Wiza rd The device inst allation wizard guides you step-by-step through the inst allation procedure. The wizard can be started in dif ferent ways: See chapter 5.6 to 5.10 for det a[...]

  • Seite 42

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-6 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.2 COMMUNICATION PROTOCOL SETUP The TRL2 Modbus Master protocol is available as default protocol when Rosemount T ankMaster is installed on a T ankMaster wor k station. Other protocols, such as the Mo dbus Slave pro[...]

  • Seite 43

    System Configuration Manual 300510EN, Rev AA December 2010 5-7 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.2.1 Master Protocol Channel Configuration T o configure a communication protocol do the following: 1. Open the Protocols folder in the Workspace window . 2. Select the icon that corresponds to the particular protoco[...]

  • Seite 44

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-8 Section 5. Installing a Ra ptor Level Gauging Sy stem 7. Select the Communication tab. Parameters that control the communi cation between a T ankMaster work station and the field device s are configured in the Communication ta b. Y ou can spe cify the type of informatio[...]

  • Seite 45

    System Configuration Manual 300510EN, Rev AA December 2010 5-9 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System Modbus Master channel 1 is enabled[...]

  • Seite 46

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-10 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.2.2 Slave Protocol Channel Configuration A Slave protocol allows you to collect dat a from the T ankMaster workstation to a host computer . NOTE! A hardware key must be in stalled in order to r un a slave protocol[...]

  • Seite 47

    System Configuration Manual 300510EN, Rev AA December 2010 5-1 1 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 7. Select the Communication tab. 8. Select the Enable Channel check box to act ivate the pr otocol cha nnel. 9. Ensure that the following communication parameters are set: NOTE! If handshaking includes DSR, no q uer[...]

  • Seite 48

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-12 Section 5. Installing a Ra ptor Level Gauging Sy stem Advanced Configuration T o con figure dela y times and time-outs perform the following steps: 1. In the Slave Protocol Channel Configuration window , select the Communication ta b and click the Advanced butt on: 2. [...]

  • Seite 49

    System Configuration Manual 300510EN, Rev AA December 2010 5-13 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System T ank mapping configuration The slave protocol allows yo u to send data from a Rosemou nt T ank Gauging system to a host computer . In the T ank Mapping window you can specify fr om which tanks to collect data for th[...]

  • Seite 50

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-14 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.2.3 Log File Configuration See chapter “Saving the Communication Log to File” on p age 7-39 for information on how to store a communication log on disk. 5.2.4 Changing the current Protocol Channel Configuratio[...]

  • Seite 51

    System Configuration Manual 300510EN, Rev AA December 2010 5-15 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.2.5 Protocol Server Configuration Y ou can specify which protocol serv ers that will be connected wh en starting T ankMaster WinSetup. T o change the current configuration do the following: 1. In the WinSetup works[...]

  • Seite 52

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-16 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.3 PREFERENCES 5.3.1 Measurement Unit s S pecify units for inven tory calculations and measured variables such as level and temperature. T o change measureme nt units do the following: 1. Select the desired server [...]

  • Seite 53

    System Configuration Manual 300510EN, Rev AA December 2010 5-17 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.3.2 Ambient Air T emperature T o change the Ambient Air T emperature preference s do the following: 1. Select the desired server (e.g. “This Workst ation”) in the WinSetup workspace. 2. Click the right mous e b[...]

  • Seite 54

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-18 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.3.3 Inventory Local Gravity and Ambient Air Density calculations are used for automatic density measurement s. T o change the Inventory settings do the following: 1. Select the desired server (e.g. “This W orkst[...]

  • Seite 55

    System Configuration Manual 300510EN, Rev AA December 2010 5-19 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.3.4 Miscellaneous T o change parameters such as type of T ank Capacity T able, or Reference T emperature, do the following: 1. Select the desired server (e.g. “This Workst ation”) in the WinSetup workspace. 2. [...]

  • Seite 56

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-20 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.3.5 Setting the Name Ta g P r e f i x e s T ankMaster Wi nSetup allows you to specify defaul t name tag prefixes that will appear automatically when installing new tanks a nd devices. These prefixes can be ignored[...]

  • Seite 57

    System Configuration Manual 300510EN, Rev AA December 2010 5-21 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.3.6 T ank V iew Layout The Setup T ank View tab is used to sp ecify variables to be presented in the T ank V iew window , see Section 7: Vi ewing T ank Data . T ankMaster Win Setup allows you to create a new tank v[...]

  • Seite 58

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-22 Section 5. Installing a Ra ptor Level Gauging Sy stem 8. Click the Save A s button if you wish to st ore the cu rrent tank view table for future use. 9. Click the OK button to save the cur rent T ank View settings and close the window . NOTE! When clicking the Apply or[...]

  • Seite 59

    System Configuration Manual 300510EN, Rev AA December 2010 5-23 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.3.7 T ank V isibility The T anks Visibility tab let s you configure tanks on a remote t ank server to make them vis ible on the current W inOpi client. T o specify tanks to be visible on the curren t WinOpi client:[...]

  • Seite 60

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-24 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.4 FIELD DEVICE INST ALLATION - OVERVIEW The Rosemount T ankMa ster configuration software suppo rts configuration of all devices supporte d by the Raptor system: • Rosemount 5900S Radar Leve l Gauge • Rosemoun[...]

  • Seite 61

    System Configuration Manual 300510EN, Rev AA December 2010 5-25 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.5 INST ALLING A ROSEMOUNT 2160 FCU 5.5.1 Introduction Installing a Rosemount 2160 Field Communication Unit (FCU) in a Rosemount Raptor system incl udes the following basic steps: 1. S pecify device type and name ta[...]

  • Seite 62

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-26 Section 5. Installing a Ra ptor Level Gauging Sy stem 3. FCU 2160 communication setup. Choose the communication proto col channel which is associated with the T ankMaster workstation communicat ion po rt that is connected to the 2160 FCU. T o check which channels are e[...]

  • Seite 63

    System Configuration Manual 300510EN, Rev AA December 2010 5-27 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System NOTE! In case several FCUs are connecte d us ing th e same default ad dress (245), you will have to change th e addresses of the FCUs before the V erify command can be used. See ”How to ch ange the Modbus address o[...]

  • Seite 64

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-28 Section 5. Installing a Ra ptor Level Gauging Sy stem 6. Configure the Group Bus (GB) and Field Bus (FB) port s on the FCU. a. Check that the correct port type is selected (1) . The Rosemount 2160 has six communication port s. They are normally co nfigured a s two Grou[...]

  • Seite 65

    System Configuration Manual 300510EN, Rev AA December 2010 5-29 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 7. Configure the Slave Database. The FCU Slave Data base ensures th at the 2160 FCU req uests information from all the co nnected field devices. The 2160 FCU is compatible with the TRL2 and Rex systems. Therefore, tw[...]

  • Seite 66

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-30 Section 5. Installing a Ra ptor Level Gauging Sy stem T o configure the FCU Slave Database: a. Select a free database position (1A, 2A ...) for the level gauge device to be configured. b. Choose Slave type= 2410 Level . The corresponding Slave Dat abase position (1B, 2[...]

  • Seite 67

    System Configuration Manual 300510EN, Rev AA December 2010 5-31 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System Summary of FCU Slave Dat abase entry fields Slave type 2410 Level, (pos 1A-32A) or 2410 T emp, (pos 1B-32B) Address The Modbus address used for the connected d evices. For level gauges it is recommended that addr ess[...]

  • Seite 68

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-32 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.5.3 Examples of 2160 FCU Slav e Dat abase Configuration The following examples illustrate how to configure Modbu s addresses for level gauges such as the Rosemount 5900S, an d A TD devices such as the Rosemount 22[...]

  • Seite 69

    System Configuration Manual 300510EN, Rev AA December 2010 5-33 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System For each level gauge the 24 10 Level address in the 2160 FCU Slave Database mu st be equal to the Level Modbus address in th e 2410 T ank Database. In this exam ple the Le vel Modbus address f or tank TK-1 is entered[...]

  • Seite 70

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-34 Section 5. Installing a Ra ptor Level Gauging Sy stem The 2410 T emp addre ss in the 2160 FCU Slave Database must be equal to the A TD Modbus address in the 2410 T ank Database . For tank TK-1 the A TD Modbus address is entered in po sition 1B in the 2160 FCU Slave Dat[...]

  • Seite 71

    System Configuration Manual 300510EN, Rev AA December 2010 5-35 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System Example 2: several T anks connect ed to one 2410 T ank Hub This example includes three t anks, each of which has one Rosemount 5400 Radar Level T ransmitter and one Rosemount 2240 S Multi-input T emperature T ransmit[...]

  • Seite 72

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-36 Section 5. Installing a Ra ptor Level Gauging Sy stem Figure 5- 7. The same Level addresses must be co nfigured in the Slave Database and the T ank Database The 2410 T emp Modbus addresses in the 2160 FCU Slave Dat abase must be equal to the A TD Modbus addresses in th[...]

  • Seite 73

    System Configuration Manual 300510EN, Rev AA December 2010 5-37 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.5.4 Summary of 2160 Inst allation and Configuration Select device type FCU 2160. Communication setup. Assign address and choose communication channe l. FCU Configuration. S pecify communication parameters for each [...]

  • Seite 74

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-38 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.6 INST ALLING A ROSEMOUNT 2410 T ANK HUB The installation wizard covers basic configura tion of a Rosemoun t 2410 T ank Hub. If further configuration of Prim ary Bus, Secondary Bus, Relay Output, and Hybrid Densit[...]

  • Seite 75

    System Configuration Manual 300510EN, Rev AA December 2010 5-39 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System Device T ype 3. From the Device T ype drop-down list, choose th e 2410 T ank Hub optio n. 4. T ype a name in the 2410 HUB T ag input field. The 2410 HUB tag will be used as an identifier for th e Rosemount 2410 T ank[...]

  • Seite 76

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-40 Section 5. Installing a Ra ptor Level Gauging Sy stem Communication Setup 6. S pecify whether T ankMaster commun icates directly with the 2410 T ank Hub, or via a 2160 Field Communication Un it. 7. If the 2410 T ank Hub is connected to a 21 60 FCU, select the appropria[...]

  • Seite 77

    System Configuration Manual 300510EN, Rev AA December 2010 5-41 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 9. T o verify co mmunication with the 2410 T ank Hub, type the current Modbus address and click the V erify Communication button. The Unit Id will appear if the correct Modbus address was ente red (the 2410 is shippe[...]

  • Seite 78

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-42 Section 5. Installing a Ra ptor Level Gauging Sy stem T ank Data base Setup Each tank is re presented by a position in th e Rosemount 2410 ta nk database. Each device connected to the 2410 is mapped to a t ank position. For each tank position, a name is assign ed as an[...]

  • Seite 79

    System Configuration Manual 300510EN, Rev AA December 2010 5-43 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 14. For each tank, specify a Modbus add ress in the Level Modbus Ad dress column to be associated with the level gauge. This must be the same Modbus address as configured in the 2160 FCU Slave Dat abase. The Level Mo[...]

  • Seite 80

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-44 Section 5. Installing a Ra ptor Level Gauging Sy stem Device T ag Setup Level T ags and AT D Ta g s are configured automatically based on th e tank names in the 2410 T ank Hub T ank Dat abase window and the configuration of tag prefixes in the Preference s/T ag Prefix [...]

  • Seite 81

    System Configuration Manual 300510EN, Rev AA December 2010 5-45 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System Local Display Setup Choose the p arameters to be displayed on the integral displa y panel on the Rosemount 2410 T ank Hub. The display will alternate betw een the selected items at a rate given by the Disp lay T oggl[...]

  • Seite 82

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-46 Section 5. Installing a Ra ptor Level Gauging Sy stem 23. Enter the Display T oggle T ime . Information on the local display alternates between the selecte d items at a rate given by the Displ ay T oggle T ime value. 24. Click the Next button to continue the installati[...]

  • Seite 83

    System Configuration Manual 300510EN, Rev AA December 2010 5-47 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System Configuration Summary The 2410 T ank Hub Summary window shows information about all devices included in the 2410 T ank Dat abase for the current installation. 25. V erify that all Modbu s addresses, level tags and A [...]

  • Seite 84

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-48 Section 5. Installing a Ra ptor Level Gauging Sy stem Figure 5-9. The devices ap pear in the WinSet up workspace window Advanced Configuration The installation wizar d does not include all configuration options available for the 2410 T ank Hub. Further configuratio n c[...]

  • Seite 85

    System Configuration Manual 300510EN, Rev AA December 2010 5-49 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.6.2 Summary of T ank Hub Inst allation and Configuration Select device type 2410 T ank Hub Communication setup. Choose how the 2 410 connects to the T ankMaster work station. Assign address and choose communication[...]

  • Seite 86

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-50 Section 5. Installing a Ra ptor Level Gauging Sy stem Local Display Setup. Choose the desired measurement unit s for the dif ferent tank p arameters. Select tanks and parameters. Set the display parameter to ggle time. V erify the configuration. Choose whether the slav[...]

  • Seite 87

    System Configuration Manual 300510EN, Rev AA December 2010 5-51 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.7 INST ALLING A ROSEMOUNT 5900S RADAR LEVEL GAUGE The Rosemount 5900S Radar Le vel Gauge is typically installed in T ankMaster WinSetup as part of the Rosemoun t 2410 T ank Hub installation procedure. In a followin[...]

  • Seite 88

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-52 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.7.1 Configuration via the Properties Window This section describes the ba sic configuration procedure of a Rosemount 5900S Radar Le vel Gauge through the 5900S RLG Proper ties window . For a basic configuration of[...]

  • Seite 89

    System Configuration Manual 300510EN, Rev AA December 2010 5-53 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 3. Select the Communication tab. 4. V erify the communication settings. The Connected to HUB field indicates which tank that the 59 00S is associ ated with in the 2410 T ank Database. Normally , the single tank ve rs[...]

  • Seite 90

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-54 Section 5. Installing a Ra ptor Level Gauging Sy stem a. Enter the Un it ID . When changing the devi ce address, the Unit Id is used as an unique identifier of the device. The Unit Id can be found on a label mounted on the device. b. Set the desired address in the Set [...]

  • Seite 91

    System Configuration Manual 300510EN, Rev AA December 2010 5-55 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System The following antenna types are available: 5900S with Horn Antenna •H o r n 5900S with Parabolic Antenna • Parabolic 5900S with Still-pipe Array Antenna • S till-Pipe Array Fixed • S till-Pipe Array Hatch 590[...]

  • Seite 92

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-56 Section 5. Installing a Ra ptor Level Gauging Sy stem 10. In the 5900S RLG Properties window select the Geometry ta b: 1 1. Enter the tank geometry p arameters: a. T ank Reference Height (R) The T ank Reference Height (R) is the dist ance from the hand dip nozzle (T an[...]

  • Seite 93

    System Configuration Manual 300510EN, Rev AA December 2010 5-57 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System c. Minimum Level Dist ance (C) The Minimum Level Dist ance (C) is defined as the distance between the Zero Level (Dipping Datum Po int) and the minimum leve l (tank bottom) for th e product sur face. By specifying a [...]

  • Seite 94

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-58 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.7.2 Inst alling a 5900S Using the Inst allation Wiza rd The installation wizar d in T ankMaster WinSetup is a tool tha t may be used to install and configu re a Rosemount 5900S Radar Level Gauge an d other devices[...]

  • Seite 95

    System Configuration Manual 300510EN, Rev AA December 2010 5-59 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System Using the inst allation wizard T o con figure a Ros emount 59 00S by using the WinSetup installation wizar d perform the following step s: 1. In the Workspace window selec t the Devices folder . 2. Click the right mo[...]

  • Seite 96

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-60 Section 5. Installing a Ra ptor Level Gauging Sy stem 6. In the 2410 T ank HUB T ag drop-down list choose the Rosemount 241 0 T ank Hub that the 5900S Radar Level Gauge is conne cted to. Normally , there is one 2410 for each t ank equipped with a 5900S Radar Level Gaug[...]

  • Seite 97

    System Configuration Manual 300510EN, Rev AA December 2010 5-61 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 12. In the 5900S RLG Summary window click the Finish button to verify the configuration and finish the inst allati on wizard. In case the configuration needs to be changed, click the Back button until the desired win[...]

  • Seite 98

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-62 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.7.3 Advanced Configuration In addition to the bas ic configurat ion, there are advanc ed configur ation options available for the Rosemount 5900S Radar L evel Gauge. These may be used to optimize measurement perfo[...]

  • Seite 99

    System Configuration Manual 300510EN, Rev AA December 2010 5-63 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System T ank Environment Certain tank conditions ma y require ad ditio nal configuration of the 5900S Radar Level Gaug e in order to optimize measureme nt performance . By considering environment al conditions in the tank, [...]

  • Seite 100

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-64 Section 5. Installing a Ra ptor Level Gauging Sy stem The Advanced Configuration T ab The Advanced Co nfiguration tab pr ovides further configuration option s. The following optio ns are availa ble: • Ta n k S c a n (1) • Empty T ank Handling (1) • Surface Echo T[...]

  • Seite 101

    System Configuration Manual 300510EN, Rev AA December 2010 5-65 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.8 INSTA LLIN G AUXILIA RY T ANK DEVICES Auxiliary T ank Devices (A TDs) such as the Rosemount 2240S Multi-input T emperature T ransmitter and the Rosemou nt 2230 Graphical Field Display , are typically installed as[...]

  • Seite 102

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-66 Section 5. Installing a Ra ptor Level Gauging Sy stem 3. The 22XX A TD window includes basic and advanced configuration tabs. Configure the A TD devices (Rosemount 2240S Multi-input T emperature T ransmitter , Rosemount 2230 Graphical Field Display) by choosing the app[...]

  • Seite 103

    System Configuration Manual 300510EN, Rev AA December 2010 5-67 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.8.2 Communication Parameter Setup The Communication t ab lets you verify the A TD communication settings. 1. In the 22xx A TD w indow selec t the Communication tab: 2. In the Connected to HUB field verify that the [...]

  • Seite 104

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-68 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.8.3 T emperature Sensor Configuration The 2240S MTT T emperature Sensor tab let s you configure a sensor connected to the Rosemount 2240S Mu lti-input T emperature T ransmitter . The 2240S MTT T emperature Sensor [...]

  • Seite 105

    System Configuration Manual 300510EN, Rev AA December 2010 5-69 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System Manual Configurat ion 1. Ensure that the Use Auto Sensor Configuration check box is unchecked. 2. Choose conversion method in the Method input field. For more info rmation on conversion m ethods such as User defined [...]

  • Seite 106

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-70 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.8.4 A verage T emperature Calculation This section gi ves a brief descr iption of how to configure av erage temp erature calculations for a temp erature se nsor connected to the Rosemount 2240S Multi-input T emper[...]

  • Seite 107

    System Configuration Manual 300510EN, Rev AA December 2010 5-71 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 6. Y ou may exclude a certain te mperature element from the average temperature ca lculation by selecting the Exclude check box in the column next to the Position field. This optio n may be useful in case you would l[...]

  • Seite 108

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-72 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.8.5 Auxiliary Sensor Configuration The 2240S MTT Auxiliary Sensor tab let s you configure a water level sensor connected to a Rosemount 224 0S Multi-input T emperature T ransmitter . All input fields in the 2240S [...]

  • Seite 109

    System Configuration Manual 300510EN, Rev AA December 2010 5-73 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 3. Enter the resulting level of fset value in the Level Offs et (X) input f ield. 4. Enter the Upper Dead Zone ( UDZ) and the Lower Dead Zone (LDZ) if needed. See the Rosemount 2 240S Multi-I nput T emperat ure T r a[...]

  • Seite 110

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-74 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.8.6 Advanced Parameter Source Configuration The Advanced Para meter Source Configuration t ab lets you ma p the output of various me asurement instruments (s ource device s) to tank measu rement variables such as [...]

  • Seite 111

    System Configuration Manual 300510EN, Rev AA December 2010 5-75 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 3. In the Source Device T ype/ID/No colum n, choose a me asurement device such as a pressure transmitter or any other type of instrument. The default setting lists only the devices mapped to the current tan k positio[...]

  • Seite 112

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-76 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.8.7 2230 Graphical Field Display This section gives a brief description of how to configure a Rosemoun t 2230 Graphical Field Display . All fields in the 2230 Graph ical Field Display tab are disa bled if no g rap[...]

  • Seite 113

    System Configuration Manual 300510EN, Rev AA December 2010 5-77 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 6. If a second graphical field display is used, click the Configure T ank Display No 2 button and repeat step 1 th rough 4 above. 7. If a third graphical field display is used, click the Configure T ank Display No 3 [...]

  • Seite 114

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-78 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.9 INST ALLING A ROSEMOUNT 5400 The Rosemount 5 400 Radar Level T ransmit ter is most conven iently installed in T ankMaster WinSetup by utilizing the in tegrated option incl uded as part of the Rosemount 2410 T an[...]

  • Seite 115

    System Configuration Manual 300510EN, Rev AA December 2010 5-79 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.9.1 Configuration via 5400 Properties This section describes the ba si c configuration procedure for a Rosemount 5400 series radar transmitter by using the 5400 RL T window . T o con figure the R osemoun t 5400 Ra [...]

  • Seite 116

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-80 Section 5. Installing a Ra ptor Level Gauging Sy stem 4. V erify the tank positi on. The Connected to HUB field shows the name of the 2410 T ank Hub and the tank positi on that the 5400 is mapped to in the 2410 t ank database. The t ank position indicates which ta nk t[...]

  • Seite 117

    System Configuration Manual 300510EN, Rev AA December 2010 5-81 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 7. Select the Antenna tab . 8. Chose Antenna T ype . It is possible to choose between predefine d antenna types or User Defined fo r non-standard anten nas. For a predefined antenna a numb er of transmitter paramete [...]

  • Seite 118

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-82 Section 5. Installing a Ra ptor Level Gauging Sy stem 1 1. For still pipe applications select the E nable still pipe/Bridle Measurement s check box and enter the P ipe Inner Diameter . See the Rosemoun t 5400 Referen ce Manual (Docu ment No. 00809-0100-4 026) for more [...]

  • Seite 119

    System Configuration Manual 300510EN, Rev AA December 2010 5-83 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System c. Minimum Level Dist ance (C) . The Minimum Level Distance (C) is defined as the dist ance between the Zero Level (Dipping Datum Point) and the minimum level for the product surface ( tank bottom). By specifying a C[...]

  • Seite 120

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-84 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.9.2 Inst alling a 5400 Using the Inst allation Wiza rd The installation wizar d in T ankMaster WinSetup is a tool tha t may be used to install and configu re a Rosemount 5400 Radar Level T ransmitter and other dev[...]

  • Seite 121

    System Configuration Manual 300510EN, Rev AA December 2010 5-85 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System Using the inst allation wizard T o con figure a Ros emount 54 00 by using the WinSetup installation wizar d perform the following step s: 1. In the Workspace window selec t the Devices folder . 2. Click the right mou[...]

  • Seite 122

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-86 Section 5. Installing a Ra ptor Level Gauging Sy stem 6. In the 2410 HUB T ag drop-down list choo se the Rosemount 2410 T ank Hub that the 5400 Radar Level T ransmitter is connected to. 7. Enter the Modbus address that is used for the 5400 level transmitter . Note that[...]

  • Seite 123

    System Configuration Manual 300510EN, Rev AA December 2010 5-87 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 13. In the 5400 RL T Summary window , click the Finish button to finish the installation wizard. If the configurat ion needs to be changed click the Back button until the desired window appears.. Further configuratio[...]

  • Seite 124

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-88 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.9.3 Advanced Configuration In addition to the basic configu ration there are some advanced co nfiguration options available for the Rosemount 5400 transmitter. Ta n k S h a p e The T ank T ype and T ank Bottom T y[...]

  • Seite 125

    System Configuration Manual 300510EN, Rev AA December 2010 5-89 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System T ank Environment Certain product conditions in the t ank may require special configuration options to be used in order to optimi ze measuremen t performance of the 5400 Radar Level T ransmitter . By configuring the [...]

  • Seite 126

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-90 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.10 INSTALLING A ROSEMOUNT 5300 The Rosemou nt 5300 Guided W ave Radar is most conveniently inst alled in T ankMaster WinSetup by utilizing the integrated option in cluded as part of the Rosemount 2410 T ank Hub in[...]

  • Seite 127

    System Configuration Manual 300510EN, Rev AA December 2010 5-91 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.10.1 Configuration via 5300 Properties This section describes the ba si c configuration procedure for a Rosemount 5300 Guided W ave Radar by using the 5300 GWR window . T o configure the Rose mount 5300 Guided W av[...]

  • Seite 128

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-92 Section 5. Installing a Ra ptor Level Gauging Sy stem 3. Select the Communication tab. 4. V erify the position in the t ank database. The Connected to HUB field shows the name of the 2410 T ank Hub and the t ank position that the 5300 is mapped to in the 2410 ta nk dat[...]

  • Seite 129

    System Configuration Manual 300510EN, Rev AA December 2010 5-93 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 7. Select the Probe tab . 8. Choose a Probe T ype that corresponds to the probe that is used on the 5300. It is possible to choose a prede fined (standard) prob e, or User Defined for non-st andard probes. When using[...]

  • Seite 130

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-94 Section 5. Installing a Ra ptor Level Gauging Sy stem 12. Select t he Geometry tab. 13. Enter the T ank Refere nce Height (R) . The T ank Reference he ight is defined as the dist ance from the Upper Reference Point to the Zero Reference Point 14. Enter the Reference Di[...]

  • Seite 131

    System Configuration Manual 300510EN, Rev AA December 2010 5-95 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.10.2 Inst alling a 5300 Using the Inst allation Wiza rd The installation wizard in T ankMaster WinSetup is a tool th at may be used to insta ll and configure a Rosemount 5300 Guided W ave Radar and other devices. H[...]

  • Seite 132

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-96 Section 5. Installing a Ra ptor Level Gauging Sy stem Using the inst allation wizard T o configure a Rosemount 5 300 by using the WinSetup in stallation wizard perform the following step s: 1. In the Workspace window select the Devices folder . 2. Click the right mouse[...]

  • Seite 133

    System Configuration Manual 300510EN, Rev AA December 2010 5-97 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 6. In the 2410 T a g drop-down list choose the Rosemount 2410 T a nk Hub that the 5300 radar is conne cted to. 7. Enter the Modbus address that is used for the 5300 . Note that this address must be stored in the 2160[...]

  • Seite 134

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-98 Section 5. Installing a Ra ptor Level Gauging Sy stem 13. In the 5300 GWR Summary win dow click the Finish button to finish the installation wizard. If the conf iguration nee ds to be ch anged click th e Back button until the desired window ap pears. Further configurat[...]

  • Seite 135

    System Configuration Manual 300510EN, Rev AA December 2010 5-99 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.10.3 Advanced Configuration In addition to the b asic configuration there are advanced config uration options available for the Rosemount 5300 Gu ided Wave Ra dar . Environment conditions such as rapid level change[...]

  • Seite 136

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-100 Section 5. Installing a Ra ptor Level Gauging Sy stem For Meas urement Mode Liquid Product Level enter the Product Dielectric Range . In some applications there is heavy vap or above the product surface having a significant influence on the level measurement. This may[...]

  • Seite 137

    System Configuration Manual 300510EN, Rev AA December 2010 5-101 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.1 1 INST ALLING A T ANK 5.1 1.1 Overview Basically the purpose of the t ank installation procedure is to associate various devices to the right t anks. It also in cludes mapp ing variables such as Free W ater Leve[...]

  • Seite 138

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-102 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.1 1.2 St arting the T an k Inst allation Wiza rd T o start the t ank installation wizard do the following: See also “Installing a New T ank” on page 5-103 . 1. In the Logical View select the Ta n k s folder .[...]

  • Seite 139

    System Configuration Manual 300510EN, Rev AA December 2010 5-103 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.1 1.3 Inst alling a New T ank T o install and configure a t ank by using the WinSetup installation wizard do the following: 1. S tart the T ankMaster WinSetup program. 2. S tart the tank inst allation wizard (see [...]

  • Seite 140

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-104 Section 5. Installing a Ra ptor Level Gauging Sy stem 6. Assign devices to the current tank. Choose a device from the list in the A vailable Devi ces pane and click the arrow button to move the de vice to the Select ed Devices pane. NOTE! It is recommended that de vic[...]

  • Seite 141

    System Configuration Manual 300510EN, Rev AA December 2010 5-105 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System Show 2160 FCU Slave Positions ( Advanced) The “Show Slave Positions” check bo x sh ould only be used for advanced ta nk configuration of device s which are not supporte d by the Raptor syst em. A Rosemount Rapto[...]

  • Seite 142

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-106 Section 5. Installing a Ra ptor Level Gauging Sy stem 8. Configure the tank. The T a nk Configuration window lets you ena ble tank measurement variable s such as V apor T emperat ure , V apor Pressure , Liquid Pressu re , and Free W ater Level (FWL) to be used fo r ca[...]

  • Seite 143

    System Configuration Manual 300510EN, Rev AA December 2010 5-107 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System Figure 5-1 1. A measur ement instrument which is mapped in the 22XX A TD/Advanced Parameter Sour ce Configurat ion window can be selected in the T ank Configurat ion window 22XX A TD/PARAMETER SOURCE WINDOW T ANK CO[...]

  • Seite 144

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-108 Section 5. Installing a Ra ptor Level Gauging Sy stem Advanced Configuration The Advanced T ank Setup window allows you to ch ange mapping of tank measurement variables to gauge outpu t. This option can for example be used to map relay status present ation in the T an[...]

  • Seite 145

    System Configuration Manual 300510EN, Rev AA December 2010 5-109 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 10. S pecify parameter value range to be used in various windows for present ation of measurement data. Also choose whether to use measurement values (Automatic) fr om the available instrumen ts or manual values. Th[...]

  • Seite 146

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-1 10 Section 5. Installing a Ra ptor Level Gauging System The Va l u e R a n g e parameters ( Minimum and Maximum) let s you to scale bar graphs in the T ank View window and other windows (in Winsetup as well as WinOpi) where bar graphs are used to display product levels.[...]

  • Seite 147

    System Configuration Manual 300510EN, Rev AA December 2010 5-1 1 1 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.1 1.4 Summary of T ank Inst allation and Configuration Ta n k Ty p e Choose the tan k type option that corresponds to the actual tan k. Select Devi ces Associate devices with the t ank. T ank Configuration S pec[...]

  • Seite 148

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-1 12 Section 5. Installing a Ra ptor Level Gauging System 5.1 1.5 T o Change T ank Configuration When the t ank is installed and configured the current settin gs can be modified at any time by opening the corr esponding Properties dialog. T o open the Properties dialog fo[...]

  • Seite 149

    System Configuration Manual 300510EN, Rev AA December 2010 5-1 13 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.1 1.6 T o Uninst all a Ta n k T o remove a tank from the WinSetup wor kspace do the following : 1. In the Workspace window selec t the tank you want to remove. 2. Click the right mous e button and choose the Unin[...]

  • Seite 150

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-1 14 Section 5. Installing a Ra ptor Level Gauging System 5.12 ADDING A T ANK TO A RAPTOR SYSTEM New tanks can easily be added to a Raptor system. The procedure will be slightly diffe rent depending on the spec ific system configuration. It can be summarized as follows: O[...]

  • Seite 151

    System Configuration Manual 300510EN, Rev AA December 2010 5-1 15 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.12.1 Adding a New T ank and a New 2410 T ank Hub T o add a new tank and new field devices to a Raptor system do the following: 1. S tart the T ankMaster WinSetup program. 2. In the WinSetup workspace, right-click[...]

  • Seite 152

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-1 16 Section 5. Installing a Ra ptor Level Gauging System 7. Configure the Slave Databa se with Modbus addresses for the new level gauge and A TD devices, see “In stalling a Rosemoun t 2160 FCU” on page 5-2 5 for more information. 8. Install and configure a Rosemount [...]

  • Seite 153

    System Configuration Manual 300510EN, Rev AA December 2010 5-1 17 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.12.2 Adding a New Ta n k t o a n Existing 2410 Ta n k H u b In case the new devices are connected to an existing 2410 T ank H ub, you will have to update the 2410 t ank database, and inst all and configure the ne[...]

  • Seite 154

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-1 18 Section 5. Installing a Ra ptor Level Gauging System 7. Select the T ank Dat abase tab: 8. V erify that the new device s connec ted to the T ankbus appear in the Device T ype column. Devices that appear in th e list are communicating properly on the T ankbus. Devices[...]

  • Seite 155

    System Configuration Manual 300510EN, Rev AA December 2010 5-1 19 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 1 1. V erify that a new t ank position appears in the right-hand pane of the Ta n k Database window . In the ex ample above, the new devices are ma pped to tank position 4, and a t ank position was added to the lis[...]

  • Seite 156

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-120 Section 5. Installing a Ra ptor Level Gauging Sy stem 12. T ype a name in the Ta n k N a m e field. This tank name shou ld also be used at a later st age when installing the ta nk to be associated with the current 2410 T ank Hub, see “I nstalling a T ank” on page [...]

  • Seite 157

    System Configuration Manual 300510EN, Rev AA December 2010 5-121 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 17. V erify that the T a nkMaster Le vel T ag is correct or enter a ne w one. 18. V erify that the T a nkMaster A T D T ag is correct or enter a new one. In case there are no A TD device associate d with the tank, t[...]

  • Seite 158

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-122 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.13 LEVEL GAUGE CALIBRATION Normally a minor level gauge adjus tment is needed in order to achieve good agreement between m easured and actual product levels. For example, a deviation may result from minor er rors[...]

  • Seite 159

    System Configuration Manual 300510EN, Rev AA December 2010 5-123 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.13.2 Using the Calibrate Function The Calibrate function is a tool which allows you to calculate the Correction Factor for still-pipe measur ements and the Calibration Distance. It optimizes measurement performanc[...]

  • Seite 160

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-124 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.14 T ANK CAPACITY The tank geometr y can be defined in a strapping table; the T ank Cap acity Ta b l e (TCT). The TCT is used to convert a product level to a vo lume. Different TCT types can be specified: Raw; In[...]

  • Seite 161

    System Configuration Manual 300510EN, Rev AA December 2010 5-125 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.15 T ANK ENTRY The T ank Entry window is used for s pecifying a number of product parame ters to be used for inventory calculatio ns. T ankMaste r can use measured data, or data that is manually entered. T o open [...]

  • Seite 162

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-126 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.16 SETTING UP A HYBRID SYSTE M This is a description of how to inst all a Rosemount Raptor on-line d ensity measurement system to be used for mass calculations. Before starting the setup make sure the 2160 FCU Sl[...]

  • Seite 163

    System Configuration Manual 300510EN, Rev AA December 2010 5-127 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 8. For Local Gravity choose calculation method Manual or Calculated . The Local Gravity is used as input for calculating the Observed Density . Manual : enter a local gravity value in th e “V alue” field. Calcul[...]

  • Seite 164

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-128 Section 5. Installing a Ra ptor Level Gauging Sy stem 13. V erify that the p arameters V apor Pressure and Liquid Pressure are mapped to the correct pressur e sensors (Source Device). See “Advanced Parameter Source Configuration” on pa ge 5-74 for further informat[...]

  • Seite 165

    System Configuration Manual 300510EN, Rev AA December 2010 5-129 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 18. Choose source parameter and measurement unit for V apor Pressure and Liquid Pressure. 19. V erify measurement s by opening the Ta n k V i e w window ( Service>T anks>Open T ank View ). 20. Configure the Li[...]

  • Seite 166

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-130 Section 5. Installing a Ra ptor Level Gauging Sy stem 22. Enter the P1 Senso r Position , i.e. the cent er position o f the Liquid Pressure se nsor memb rane. 23. Enter the Hybrid Min Level . This value specifies th e low est produc t level at which T ankMaster calcul[...]

  • Seite 167

    System Configuration Manual 300510EN, Rev AA December 2010 5-131 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 28. Make sure that the Reference Density is measu red au tomatically , i.e. the check b ox is unmar ked. 29. Click the Apply button to save the con figuration, or click the OK button to save the configuration and cl[...]

  • Seite 168

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-132 Section 5. Installing a Ra ptor Level Gauging Sy stem 33. Ensure that V alue Source is set to Automatic for the Liquid Pressure and V apor Pressure measurement varia bles. 34. Click the OK button to save the configuration and close the window . 35. Check the result in[...]

  • Seite 169

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor www .rosemount-tg.com Section 6 Device Handling 6.1 T o Change Device Configuration . . . . . . . . . . . . . . page 6-1 6.2 T o Uninstall a Device . . . . . . . . . . . . . . . . . . . . . . . . page 6-3 6.1 T O CHANGE DEVICE CONFIGURATION Once a device is installed a nd c[...]

  • Seite 170

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 6-2 Section 6. Device Handling A number of tabs are available fo r configuration of communication parameters, t ank geometry , device specific parameter s and advanced configuration options. Some of the tabs refer to the different steps in the device installation wiz ard. S[...]

  • Seite 171

    System Configuration Manual 300510EN, Rev AA December 2010 6-3 Rosemount Raptor Section 6. Device Handling 6.2 T O UNINST ALL A DEVICE A device can be uninstalled from the WinSetup workspace at any time. However , the associated tank must be un installed first. As an alternative you may keep the t ank by disconnecting t he device from the associate[...]

  • Seite 172

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 6-4 Section 6. Device Handling 3. Click the Change button. 4. In the right-hand side of the Select Devices window , select the device and click the arrow button. The device will be removed from the Selected Devices pane to the Availa ble Devices pane on the left-hand side. [...]

  • Seite 173

    System Configuration Manual 300510EN, Rev AA December 2010 6-5 Rosemount Raptor Section 6. Device Handling 6. Open the Ta n k s folder: 7. V erify that the device (L T -TK-1 in this case) is no longer associated with the tank. 8. Open the Devices folder: 9. Select the device and click the right mouse button. 10. Choose the Uninstall optio n. Now th[...]

  • Seite 174

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 6-6 Section 6. Device Handling[...]

  • Seite 175

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor www .rosemount-tg.com Section 7 Service Functions 7.1 System St atus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p age 7-1 7.2 Customizing the T ools Menu in WinSetup . . . . . . . page 7-2 7.3 User Defined T emperature Conver sion . . . . . . . . . p age 7-[...]

  • Seite 176

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-2 Section 7. Service Fu nctions 7.2 CUSTOMIZING THE T OOLS MENU IN WINSETUP T o add custom options to the T ools menu do the following: 1. Choose the T ools> Applicatio ns menu option. Response: the Customize win dow appears: 2. Click the Add button to add a new menu o[...]

  • Seite 177

    System Configuration Manual 300510EN, Rev AA December 2010 7-3 Rosemount Raptor Section 7. Service Functions 4. Press the button next to the Command field. 5. Browse to the program file that will be associated with the new T ools menu option as given in the Menu T ext field. 6. Click the Open button and return to the Customize window . 7. In the Ar[...]

  • Seite 178

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-4 Section 7. Service Fu nctions 7.3 USER DEFINED T EM PERATURE CONVERSION The Rosemount 2240S Mul ti-input T emperature T ransmitter supports the use of non-standa rd spot temperature sens ors. For these typ e of temperature elements you can spec ify the relation between [...]

  • Seite 179

    System Configuration Manual 300510EN, Rev AA December 2010 7-5 Rosemount Raptor Section 7. Service Functions 7.3.1 User Defined Linearization Ta b l e When using a resistance temperature sensor , the electrical resist ance values can be converted to tempe rature values by using a table of resist ance and temperature value s. T o create a conversion[...]

  • Seite 180

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-6 Section 7. Service Fu nctions 7.3.2 User Defined Formula For a res istance temperat ure sens or , the relatio n between t emperatur e and resistance ca n be specified by a mathematical formula: R=R 0 *(1+A* T+B*T 2 ) where R is the resistance at t emperatur e T , R 0 is[...]

  • Seite 181

    System Configuration Manual 300510EN, Rev AA December 2010 7-7 Rosemount Raptor Section 7. Service Functions 7.3.3 User Defined Individual Formula When using User Defined Individual Formula, a mathematical formula is used for each individ ual temperature element: R=R 0 *(1+A N *T+B N *T 2 +C N *T 3 ), wher e • R is the re sistance at temp erature[...]

  • Seite 182

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-8 Section 7. Service Fu nctions 7.4 VIEWING INPUT AND HOLDING REGISTERS In a Rosemount Raptor system measuremen t data is cont inuously stored in Input registers of devices such as the Rosemount 2410 T ank Hub, Rosemount 5900S Radar Level Gau ge, and other devices. By vie[...]

  • Seite 183

    System Configuration Manual 300510EN, Rev AA December 2010 7-9 Rosemount Raptor Section 7. Service Functions 7.5 T O EDIT HOLDING REGISTERS Most Holding registers can be edited simply by typi ng a new value in the appropriate Va l u e input field. Some holding registers (marked gr ey in the V alue column) can be edited in a separ ate window . In th[...]

  • Seite 184

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-10 Section 7. Service Fu nctions 4. Click the Apply button to store the register data, or click the Close button to store and close the window .[...]

  • Seite 185

    System Configuration Manual 300510EN, Rev AA December 2010 7-1 1 Rosemount Raptor Section 7. Service Functions 7.6 VIEW DIAGNOSTIC REGISTERS The V iew Diagnostic Registers window sho ws a predefined set of diagnostic input and holding registers. For each device there is a default set of diag nostic registers which can be changed in the Configure Di[...]

  • Seite 186

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-12 Section 7. Service Fu nctions A grey back ground colo r of the table cell in th e V alue column mean s that the register is of either Bitfield or ENUM type. An expanded Bitf ield/ENUM window can be ope ned for that type of registers. Double -click the cell to open the [...]

  • Seite 187

    System Configuration Manual 300510EN, Rev AA December 2010 7-13 Rosemount Raptor Section 7. Service Functions 4. The order in which registers are displaye d in the View Diagnost ic Registers window can be configured. Select a register in the right pane and press to move it upwards, or to move it downwards in the list. 5. The Log Setup button provid[...]

  • Seite 188

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-14 Section 7. Service Fu nctions 7.7 LOGGING MEASUREMENT DAT A Raptor device s such as the Ros emount 2410 and Rosemoun t 5900S suppor t logging of diagnostic registers. This fu nction is useful for verifying that the gauge works proper ly . The logging function can be ac[...]

  • Seite 189

    System Configuration Manual 300510EN, Rev AA December 2010 7-15 Rosemount Raptor Section 7. Service Functions 7.8 SAVING AND LOADING DAT ABASE REGISTERS Input and Holding Reg isters of the Rosemount 5900S a nd the 2410 can be stored on disk. This can be useful fo r backup purposes and troubleshooting . Input and Holding registers can be saved for a[...]

  • Seite 190

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-16 Section 7. Service Fu nctions 7.8.2 T o Save Device Registers Multiple Devices T o save a backup copy of the current configuration for multip le devices, do the following: 1. In the T ankMa ster WinSet up workspace, select the Devices folder . 2. Click the right mous e[...]

  • Seite 191

    System Configuration Manual 300510EN, Rev AA December 2010 7-17 Rosemount Raptor Section 7. Service Functions 7.8.3 T o Recover a Device Dat abase T ankMaster WinSetup of fers the option to replace the current hold ing register database with a backup database s tored on d isk. This can be useful, f or example, when recovering co nfiguration data. T[...]

  • Seite 192

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-18 Section 7. Service Fu nctions 7.9 UPGRADING THE DEVICE SOF TWARE T ankMaster WinSetup allows you to upgrade the software of Rosemount Raptor level gauges and othe r devices. T o uploa d new softwa re do the following: 1. Make sure the devices are properly prep ared for[...]

  • Seite 193

    System Configuration Manual 300510EN, Rev AA December 2010 7-19 Rosemount Raptor Section 7. Service Functions 7. Click the St art Programming button to activate device progr amming. See, for example, th e Rosemount 5900 S Reference Manu al (Docum ent No. 300520EN) or the Rosemoun t 2410 Reference Manual (Document No. 300530EN) for further in format[...]

  • Seite 194

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-20 Section 7. Service Fu nctions 7.10 T ANK SCAN The Ta n k S c a n window allows you to view tank echoes an d setup the most important p arameters to enable a radar level gau ge such as the Rosemount 5900S to sep arate a surface echo from disturbing echoes and noise. T o[...]

  • Seite 195

    System Configuration Manual 300510EN, Rev AA December 2010 7-21 Rosemount Raptor Section 7. Service Functions 4. The T ank Scan window cont ains the Graph Area, Legend/Op tions area, File S torage buttons, and vario us action buttons.[...]

  • Seite 196

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-22 Section 7. Service Fu nctions 7.10.1 Graph Area When the Ta n k S c a n window opens, WinSetup reads tank dat a from the gauge. The proces s is indicated by a progress bar in the lower right corn er of the T ank Scan w indow . Once the reading process is fin ished, a t[...]

  • Seite 197

    System Configuration Manual 300510EN, Rev AA December 2010 7-23 Rosemount Raptor Section 7. Service Functions 7.10.2 Legend/Options The following items can be shown in the graph ar ea (check the appropriate box for each item to be shown): T ank Echo The black line shows the latest T ank Echo curve, and the grey lines show previous T ank Echo curves[...]

  • Seite 198

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-24 Section 7. Service Fu nctions A TP (Amplitude Threshold Points) A weak disturbing echo can be filtered out by creating a curve of Amplitude Threshold Point s . Holdoff Distance The Holdoff Dist ance defines how close to the Gauge Reference Point a level value is accept[...]

  • Seite 199

    System Configuration Manual 300510EN, Rev AA December 2010 7-25 Rosemount Raptor Section 7. Service Functions T ank Bottom The Ta n k B o t t o m is shown in red: Echo Peaks Echo Peaks are shown in black for the Surface Ech o and in green for un known echoes: Peak Labels Peak Labels are shown fo r the Surface Echo and for unknown echo es: Previous [...]

  • Seite 200

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-26 Section 7. Service Fu nctions 7.10.3 File Storage T o save T ank Scan dat a displayed in the Graph Area 1. In the T ank Scan window click the Save button. 2. Enter a name to identify the tank scan data. Y ou may also type a comment in the Comment field (n ot required).[...]

  • Seite 201

    System Configuration Manual 300510EN, Rev AA December 2010 7-27 Rosemount Raptor Section 7. Service Functions T o export t ank scan dat a to an external file T ank sc an data can be saved to file for viewing w ith the T ank Echo Viewer (T ools>T ank Echo Viewer): 1. In the T ank Scan window click the Save button to open the Save T ank Scan Data [...]

  • Seite 202

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-28 Section 7. Service Fu nctions 7. Press Ye s to create t he file. 8. Press OK . 9. Press OK to export the tank scan data.[...]

  • Seite 203

    System Configuration Manual 300510EN, Rev AA December 2010 7-29 Rosemount Raptor Section 7. Service Functions T o load data from a saved file into the Graph Area 1. In the T ank Scan window press the Stored Echoe s button. 2. Select the file to be loaded. 3. Press the Load button. T o delete a saved file 1. In the T ank Scan window press the Stored[...]

  • Seite 204

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-30 Section 7. Service Fu nctions 7.10.4 Action Buttons The following buttons can be found in the Ta n k S c a n window: Save See “File S torage” on p age 7-26. S tored Echoes See “File S torage” on page 7-26. Reread From Gauge At any time, you can refresh t ank ec[...]

  • Seite 205

    System Configuration Manual 300510EN, Rev AA December 2010 7-31 Rosemount Raptor Section 7. Service Functions 7.10.5 Editing All the element s having handles can be edited. Each handle may be moved by using the mouse pointer . Clicking the right mouse button on a handle opens a dialog window . The Properties option allows you to review or ch ange p[...]

  • Seite 206

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-32 Section 7. Service Fu nctions T o add a False Echo Area or an Amplitude Thresh old Point 1. Click the right mous e button in the graph area where you would like to add a False Echo Area or an Amplitude Th reshold Point : 2. Select a me nu item in th e popup me nu. In t[...]

  • Seite 207

    System Configuration Manual 300510EN, Rev AA December 2010 7-33 Rosemount Raptor Section 7. Service Functions 7.1 1 V IEWING T ANK DAT A WinSetup offers the op tion to view data from a single tank or a group of t anks. V arious parame ters such as L evel, Leve l Rate, and Average T emperature can be displayed. The Setup T ank View window lets you s[...]

  • Seite 208

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-34 Section 7. Service Fu nctions 7.1 1.2 Viewing Dat a From a Single Ta n k T o view measurement data for a single tank, do the following: 1. In the WinSetup workspace, select the desired t ank icon. 2. Click the right mouse button and choose the Open T ank View option, o[...]

  • Seite 209

    System Configuration Manual 300510EN, Rev AA December 2010 7-35 Rosemount Raptor Section 7. Service Functions 7.12 VIEWING ALARM STAT US WinSetup lets you view alarm status for all tanks, a cert ain tank group, or a single tank. T o view the current alarm status for all t anks do the following: 1. In the WinSetup workspace, select the T ankMaster w[...]

  • Seite 210

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-36 Section 7. Service Fu nctions T o v iew the ala rm status of a single ta nk : 1. Open the Ta n k s folder and select the desired t ank: 2. From the Vi ew menu choose Alarms . The Alarm S tatus window presents the cur rent alarms for the selected tank:[...]

  • Seite 211

    System Configuration Manual 300510EN, Rev AA December 2010 7-37 Rosemount Raptor Section 7. Service Functions 7.13 PROTOCOL HANDLING 7.13.1 Logging the Channel Communication WinSetup allows you to log communication on the var ious communication protocol channels. Y ou can log specific devices, as well as filter out certain function codes and error [...]

  • Seite 212

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-38 Section 7. Service Fu nctions 4. Click the OK button to open the Communication Log window . The Channel Commu nication Log window is continuously updated with new data. T o stop WinSetup from feeding new dat a click the right mouse button and choose Freeze . By clickin[...]

  • Seite 213

    System Configuration Manual 300510EN, Rev AA December 2010 7-39 Rosemount Raptor Section 7. Service Functions 7.13.2 Saving the Communication Log to File T o save the communication log to file: 1. Select the protocol channel icon. 2. Click the right mouse button and choose Properties, or from the Service menu choose Channels/Properties . 3. Select [...]

  • Seite 214

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-40 Section 7. Service Fu nctions 5. The Multiple Log files section allows you to op timize file size for storing on floppy disk. Choose the One File option if you pref er the log t o be stored in a single file. By choosing the Several Files radio button, logging con tinue[...]

  • Seite 215

    System Configuration Manual 300510EN, Rev AA December 2010 7-41 Rosemount Raptor Section 7. Service Functions 9. Choose the Selected Function Code option if you would like to log a specific function . 10. Choose one of the device address options; Any Address or Select ed Address . Choose Selected Address if y ou want to log communi cation to a cert[...]

  • Seite 216

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-42 Section 7. Service Fu nctions 7.13.3 Searching for Connected Devices Y ou can se arch for devices on the communication protocol channe ls: 1. In the WinSetup workspace , open the Protocols folder and th e appropriate protocol sub folder . 2. Select the desire d protoco[...]

  • Seite 217

    System Configuration Manual 300510EN, Rev AA December 2010 7-43 Rosemount Raptor Section 7. Service Functions 7.13.4 Channel Stat is t i cs The Protocol S tatistics function is a tool which can be used to check the quality of communication between the T ankMaster workst ation and the connected field devices. T o view statistical data for a protocol[...]

  • Seite 218

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-44 Section 7. Service Fu nctions 7.14 T ANKMASTER ADMINISTRATOR The T ankMaster Administrator program provides the option to select which T ankMaster programs that will start automatically when the PC is turned on. It also allows you to check which T ank Master processes [...]

  • Seite 219

    System Configuration Manual 300510EN, Rev AA December 2010 7-45 Rosemount Raptor Section 7. Service Functions 7.14.1 Log on T o be able to make any changes in the T ankMaster Administrator window you need to use the Log on function. T o log on to the T ankMaster Administrator do the fo llowing: 1. Open the T ankMaster Admi nistrator window by click[...]

  • Seite 220

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-46 Section 7. Service Fu nctions 7.14.2 Changing the Admini strator Program password T o change the T ankMaster Administrator password, do th e following: 1. Open the T ankMaster Ad ministrator window . 2. Log on to the Administrator . 3. Click the Change Password button.[...]

  • Seite 221

    System Configuration Manual 300510EN, Rev AA December 2010 7-47 Rosemount Raptor Section 7. Service Functions 7.14.3 Autost art The Autostart fun ction lets you specify programs to st art automatically when the T ankMaster computer is st arted. T o con figure the A utostart option: 1. Open the T a nkMaster Ad ministrator window . 2. Select the chec[...]

  • Seite 222

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-48 Section 7. Service Fu nctions 7.14.4 Backup The backup function can be used to save configuration dat a for devices and tanks as well as worksp ace settings for WinSetup and WinOpi. T o make backup copies of the current config uration do the following: 1. Open the T an[...]

  • Seite 223

    System Configuration Manual 300510EN, Rev AA December 2010 7-49 Rosemount Raptor Section 7. Service Functions 4. Choose the desired file destinatio n. T an kMaster automatically creates subdirectories for WinOpi, WinSetup, and T ankserver files. 5. Click the OK button to close the Browse for Folder window and return to the Backup window . 6. In the[...]

  • Seite 224

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-50 Section 7. Service Fu nctions 7.14.5 Restore If the PC operating system has crashed resulting in corrupt T ankMaster files, the T ankMaster settings can be restored by using the backup files. T o restore the T ankMaster configuration and dat a files do the following: 1[...]

  • Seite 225

    System Configuration Manual 300510EN, Rev AA December 2010 7-51 Rosemount Raptor Section 7. Service Functions 5. The Restore Bac kup Wizard lets you restore tank and device configuration, BatchServe r data and Historical dat a. Y ou may also restore WinOpi and WinSetup configurations such as group s, color , network set tings etc. 6. Click the Next[...]

  • Seite 226

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-52 Section 7. Service Fu nctions 8. The following options will also need to be specified: 9. The first option, Cr eate a backup of the current configuration, should not be used if the restor e function is us ed to replace corru pt configuration files. The Delete old confi[...]

  • Seite 227

    System Configuration Manual 300510EN, Rev AA December 2010 7-53 Rosemount Raptor Section 7. Service Functions 12. The Copy Log button can be used to store the restore log in the ...RosemountServer Log directory . Click the Ne xt button to continue. 13. Check that no errors occured during the restore pr ocess and click the Finish button to close t[...]

  • Seite 228

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-54 Section 7. Service Fu nctions 7.14.6 File V ersion Information The File Info option allows you to view a list of all the files included in the T ankMaster software p ackage. The list presents file versions and brief descriptions. The list can be stored by using the Sav[...]

  • Seite 229

    System Configuration Manual 300510EN, Rev AA December 2010 7-55 Rosemount Raptor Section 7. Service Functions 7.14.7 Processes T o view the ru nning T an kMaster prog rams, click the Processes button in the T ankMaster Admin istrator window: The Shut down TM button let s you close all T ankMaster programs except the T ankMaster Administrator . In c[...]

  • Seite 230

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-56 Section 7. Service Fu nctions[...]

  • Seite 231

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor www .rosemount-tg.com Section 8 Menu Guide 8.1 File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 8-2 8.2 View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 8-2 8.3 Service . . . . . . . . . . . . . . . .[...]

  • Seite 232

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 8-2 Section 8. Menu Guide 8.1 FILE If a workstation is selected , new options are available in the File menu: 8.2 VIEW New Connection Connect to another tank server . Install New > T ank Install new tanks by starting the t ank installation wizard. Install New > Device[...]

  • Seite 233

    System Configuration Manual 300510EN, Rev AA December 2010 8-3 Rosemount Raptor Section 8. Menu Guide 8.3 SERVICE The service options are found in the Service menu or by clicking the right mouse button on a specific folder , device, or tank. Servers > Rename Change the server name. Disconnect Disconnect from the current server . Configure Digita[...]

  • Seite 234

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 8-4 Section 8. Menu Guide When selecting a t ank in the T anks folder , new options are a vailable under the Service > T anks menu: When selecting a device in the device folder , new option s are available under the Service > Devices menu: T anks > Unist all Remove[...]

  • Seite 235

    System Configuration Manual 300510EN, Rev AA December 2010 8-5 Rosemount Raptor Section 8. Menu Guide 2410 T ank Hub See the Rosemount 2410 T ank Hub Reference Manual ( Document no. 300530EN) for more information. Devices > Expand all Show all devices connected to the selected Rosemount 2410 T ank Hub. Collapse All Close the device folder . Unin[...]

  • Seite 236

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 8-6 Section 8. Menu Guide 5900S Radar Level Gauge See the Rosemount 5900S Reference Manual (Document no. 300520EN) for more information. Devices > Uninstall Remove the selected device. Save Database to File Save the current holding register setup to file. This function c[...]

  • Seite 237

    System Configuration Manual 300510EN, Rev AA December 2010 8-7 Rosemount Raptor Section 8. Menu Guide Auxiliary T ank Devices (A TDs) (2240S, 2230 etc.) For more information about the various A TD devices, see the reference manual for the specific device. Devices > Uninstall Remove the selected device. Save Database to File Save the current hold[...]

  • Seite 238

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 8-8 Section 8. Menu Guide When selecting a specific protoc ol, new options will be available: Protocols > Disable Disable the selected protocol. Properties Open the protocol Properties window and choose a communication channel. Channels > Find Devices S earch for devi[...]

  • Seite 239

    System Configuration Manual 300510EN, Rev AA December 2010 8-9 Rosemount Raptor Section 8. Menu Guide 8.4 T OOLS 8.5 HELP Applications Customize the T ools menu. Administrative T ools > User Manager Manage the user accounts. User Information Display information about the current user . Set Password Change the password for the current user . Set [...]

  • Seite 240

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 8-10 Section 8. Menu Guide[...]

  • Seite 241

    System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor www .rosemount-tg.com Index Numerics 2160 FCU Slave Database 5-29 , 5-32 , . . . . . . . . . . 5-35 , 5-38 , 5-43 , 5-120 2160 Field Communication Uni t . 2-3 2240S temperature sensor conversion method . . . . . . . . 5-69 2240S Temperatu re Sensor . . . 5-68 22XX ATD windo[...]

  • Seite 242

    Rosemount Raptor Index-2 System Configuration Manual 300510EN, Rev AA December 2010 F FCU . . . . . . . . . . . . . . . . . . 2-3 , 5-25 communication setup . . . . . 5-26 slave database setup . . . . . 5-29 FCU Slave Database . . . . . . . . 5-29 Field Bus ports . . . . . . . . . . . . . 5-28 Field Communication Unit . 2-3 , 5-2 , 5-25 File Info O[...]

  • Seite 243

    Index-3 Rosemount Raptor System Configuration Manual 300510EN, Rev AA December 2010 Protocols folder . . . . . . . . . . . . . . 5-7 Protocols/Properties . . . . . . . . . . 5-7 R Rapid Level Change 5-63 , 5-89 , 5- 99 Recover database . . . . . . . . . . 7-17 Redundant server . . . . . . . . . . . . 3-5 Reference Density . . . . . . . . . 5-131 Re[...]

  • Seite 244

    Rosemount Raptor Index-4 System Configuration Manual 300510EN, Rev AA December 2010 Tank Bottom Type . . . . . . . . . . . 5-62 Tank Capacity Table . . . 5-19 , 5-124 Tank Configuration . . . 5-106 , 5 - 111 Tank Connection Length .5 - 5 5 , 5-81 Tank Connection Length (TCL) .5 - 5 4 Tank Database 5-30 , 5-32 , 5-35 , 5-42 Tank Echo Viewer . . . . [...]

  • Seite 245

    [...]

  • Seite 246

    System Configuration Manual 300510EN, Rev. AA December 2010 Rosemount Raptor Emerson Process Management © 2010 Rosemount T ank Radar AB. All rights reserved. Rosemount and the Rosemount logotype are trademarks o f Rosemount Inc. HART is a trademark of the HART Communication Foundation. AMS Suite is a trademark of Emerson Process Management. F OUND[...]